Heath Zenith 5318 manual Test and Adjustment, Bottom of Sensor, Avoid aiming the control at

Page 4
Clamp Screw
Ball Joint
Aim Sensor
Down for Short
Coverage
Aim Sensor
Higher for Long
Coverage

TEST AND ADJUSTMENT

Turn on the circuit breaker and light switch.

NOTE: Sensor has a 1 1/2 minute warm up period before it will detect motion. When first turned on, wait 1 1/2 minutes.

NOTE: Meets the ENERGY STAR® guidelines when DualBrite® function is off and ON-TIME is 1 or 5 minutes and when used with 120 W Max bulbs.

Turn the RANGE control to the medium position (halfway between MIN and MAX), DualBrite® to OFF, and the ON-TIME control to the TEST position.

MAX

 

 

 

 

B

O

ON - TIME

DUAL BRITE

 

 

O

 

 

 

S

 

 

 

MIN

T

 

 

 

TEST 1 5 2 0

OFF 3 6

DUSK TO

RANGE

 

MINUTES

HOUR

DAWN

Bottom of Sensor

Avoid aiming the control at:

Objects that change temperature rapidly, such as heating vents and air conditioners. These heat sources could cause false triggering.

Areas where pets or traffic may trigger the control.

Nearby large, light-colored objects reflecting light may trigger the shut-off feature. Do not point other lights at the sensor.

240°

8 ft.

(2.4 m)

70 ft.

100 ft.

 

(21 m)

(30.5 m)

 

 

Boosted

 

Maximum Range

Maximum

Coverage Angle

NOTE: If fixture is mounted higher than 8 ft.(2.4 m), aiming the sensor down will reduce coverage distance.

The detector is less sensitive to motion directly towards it.

MotionMotion

 

Sensor

Least Sensitive

Most Sensitive

Loosen the clamp screw in the sensor ball joint and gently rotate the sensor.

Walk through the coverage area noting where you are when the lights turn on (also, the LED will flash several times when motion is detected).Move the sensor head up, down, or sideways to change the cover- age area. Keep the sensor at least 1" (25 mm) away from the bulbs.

Adjust the RANGE as needed.

RANGE set too high may increase false triggering.

Secure the sensor head by tightening the clamp screw.

Do not overtighten the screw.

Set the amount of TIME you want the lights to stay on after motion is detected (1, 5, or 20 minutes).

Set the DualBrite® switch to the amount of time after dusk you want the lights on at low level (Off, 3, 6 Hrs., Dusk-to-Dawn).

WARNING - Risk of fire. Do not aim the bulbs at a combustible surface within 3 ft. (1 m).

595-5731-07

Image 4
Contents Features DualBrite Motion Sensor Light ControlOperation RequirementsInstallation Mode Switching SummaryDualBrite Timer Wall MountJunction box ground wire to green ground screw on fixture Mounting Black to White to StrapTest and Adjustment Turn on the circuit breaker and light switchBottom of Sensor Avoid aiming the control atSpecifications Troubleshooting GuideTechnical Service No Service Parts Available for this ProductControl de luz y detector de movimiento DualBrite FuncionamientoCaracterísticas RequisitosInstalacion Resumen de las modalidades del interruptorLuz de Adorno DualBrite Montaje en pared Montaje en aleroAdvertencia Desconecte la energía en el disyuntor Lámina de Negro a Blanco a MontajePrueba Y Ajuste Parte de abajo del detectorPrenda el cortacircuitos y el interruptor de luz Evite apuntar el control haciaEspecificaciones Guia DE Investigacion DE AveriasServicio Técnico No hay piezas de servicio disponibles para este productoCommande d’éclairage DualBriteMD à détecteur de mouvement FonctionnementCaractéristiques ExigencesRésumé du mode de commutation Minuterie DualBriteMDMontage sous Montage mural Avant-toitCâblage de la Commande D’éclairage NoirBas du détecteur Essais ET RéglagesÉviter de pointer l’appareil Fiche Technique Guide DE DépannageService Technique Aucune pièce de rechange n’est disponible pour ce produit595-5731-07 Nº de modelo / N de modèle