Dutchwest
Fireplace Installations -
Through the Fireplace
The Convection heaters may be installed either without legs* as a fireplace insert, or with standard legs at- tached - depending on the safety regulations that apply to your situation, the height of the fireplace opening and your own preference. For either situation, the chimney connector/positive connection kit extends back from the stove, enters the fireplace cavity, and turns upward. It then passes through the fireplace damper opening and smoke chamber and connects to the chimney flue.
In such installations, a “positive connection” must be made to the chimney flue with a special kit available from your local dealer. Also, special clearance and floor protection provisions must be observed. These provi- sions are discussed in the Clearance and Floor Protec- tion sections respectively.
Wall Pass-Throughs
Whenever possible, design your installation so the con- nector does not pass through a combustible wall. If you must use a wall
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall
All combustible material in the wall is cut away a suffi- cient distance from the
The following wall
•Use a section of listed
•Place a chimney connector pipe inside a ventilated thimble, which is then separated from combustibles by six inches (152 mm) of fiberglass insulating mate- rial.
•If the stove is installed without legs, we recommend the use of noncombustible tiles or pavers as shims to allow air flow into the convection air inlets under the stove. Make sure not to block air slots instove bottom with shims or remove fan cover.
•Place a chimney connector pipe inside a section of listed
| 12” |
Chimney Con- | (305mm) |
| |
nector |
|
12” (305mm)
ST420
Fig. 10 Wall pass-through enclosed with noncombustible materials.
18” |
|
(450mm) |
|
Empty Space | Sheet Metal |
All Around | |
the Chimney | Cover |
Connector | (One side |
| only) |
ST421
Fig. 11 Hollow wall pass-through.
chimney connector and having 1 inch (25.4 mm) or more of insulation and maintaining a minimum 2 inch air space between the outer wall of the chimney and combustibles.
DO NOT CONNECT THE HEATER TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
In Canada: The Canadian Standards Association has established different guidelines. Figure 11 shows one method, in which all combustible material in the wall is cut away to provide the required 18” (450 mm) clear- ance for the connector. The resulting space must remain empty.
8 | 7001135 |