Desa CGN10RLA AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Heater Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

 

 

 

 

Gas water heater*

___________________ Btu/Hr

Example:

 

 

 

Gas furnace

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

___________________ Btu/Hr

Vent-free heater

+

10,000

Btu/Hr

50,000

Gas fireplace logs

___________________ Btu/Hr

Total

=

Btu/Hr

Other gas appliances* + ___________________ Btu/Hr

 

 

 

 

Total

= ___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 46,100 Btu/Hr (maximum the space can support) 50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

104276

5

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualNatural GAS Heater Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Items InstallationInstalling Heater to Wall Check GAS TypeInstalling Bottom Mounting Screw Installing Two Mounting ScrewsPlacing Heater on Mounting Screws Removing Front Panel of HeaterGas Connection Connecting to GAS SupplyPressure Testing Gas Supply Piping System For Your Safety Read Before LightingPressure Testing Heater Gas Connections Operating HeaterLighting Instructions Manual Lighting ProcedureTo Select Heating Level To Turn OFF GAS To ApplianceInspecting Burner Cleaning and MaintenanceObserved Problem Possible Cause Remedy TroubleshootingTurn control knob until it locks at desired Observed Problem Possible Cause Replacement Parts SpecificationsTechnical Service Service HintsBaltimore Electric Washer Equipment Co Dayton Hardware Parts CentralsTarantin Tank Co Heater and Fireplace Store Cans Unlimited, IncCGN10RLA Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListWarranty Information

CGN10RLA specifications

Desa CGN10RLA is a cutting-edge generator that exemplifies modern engineering and design, making it a popular choice among residential and commercial users alike. This generator stands out for its reliability and efficiency, characteristics that are essential for those who require a consistent power supply in various situations, from home use during outages to outdoor recreational activities.

One of the main features of the Desa CGN10RLA is its robust engine, which delivers a powerful output of up to 10,000 watts. This high capacity makes it suitable for running heavy-duty appliances and tools. Whether you need to power your air conditioning unit during a summer heatwave or run multiple devices on a construction site, this generator has the power to meet your needs.

The CGN10RLA also boasts impressive fuel efficiency. Its advanced fuel management system allows for longer run times on a single tank, which is a significant advantage for users looking to minimize interruptions and maximize productivity. This generator is designed to accommodate a variety of fuel types, providing flexibility and convenience for users.

Equipped with a state-of-the-art inverter technology, the Desa CGN10RLA guarantees stable power output with less than 3% total harmonic distortion. This feature is particularly important for sensitive electronic devices, ensuring that they are safeguarded against power surges that could lead to damage. Thus, users can confidently run their office equipment, computers, and other delicate electronics without concern.

Portability is another highlight of the CGN10RLA. The generator is designed with integrated wheels and a folding handle, making it easy to transport. Its compact size means it can fit into tight storage spaces, while still providing ample power when needed.

In terms of safety, the Desa CGN10RLA incorporates several protective features such as low oil shutdown and overload protection, ensuring the safe operation of the unit. This generator is also equipped with a user-friendly control panel, allowing for straightforward operation and accessibility.

Overall, the Desa CGN10RLA is a versatile generator that combines power, efficiency, and convenience. Whether for home use, travel, or professional projects, its advanced technology and user-centric design make it an excellent choice for anyone in need of reliable power.