Desa CGN10R installation manual Determining FRESH-AIR Flow for Heater Location

Page 6

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

6

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr

the space can support)

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. =

51.2 or 51,200 (maximum

Btu/Hr the space can support)

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

10,000

Btu/Hr

Total

=

 

 

Btu/Hr

50,000

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 46,100

Btu/Hr (maximum the space can support)

50,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

101867

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information Safety Information Product Identification Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemUnusually Tight Construction Fresh AIR for Combustion and VentilationProviding Adequate Ventilation Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Ventilation Air from OutdoorsInstallation Items Check GAS TypeLocating Heater Installing Heater to Wall Marking Screw LocationsInstalling Two Mounting Screws Folding AnchorPlacing Heater On Mounting Screws Connecting to GAS Supply To GAS Supply ConnectingPressure Testing GAS Supply Piping System Checking GAS ConnectionsPressure Testing Heater GAS Connections Manual Shutoff ValveFor Your Safety Read Before Lighting Operating HeaterPilot To Select Heating Level To Turn OFF GAS to Appliance Manual Lighting ProcedureOperating Heater Inspecting Burner Pilot Flame PatternBurner Flame Pattern Correct Burner Flame PatternCabinet Cleaning and Maintenance Trouble ShootingODS/PILOT and Burner Orifice Air PassagewaysSee Cleaning TROUBLE- ShootingMaintenance , TROUBLE- Shooting Technical Service Ing statement atTop Service Hints Replacement Parts Parts Under WarrantyParts Not Under Warranty Service Publications Accessory Parts CentralsValve GA5010 Parts List CGN10R Illustrated Parts BreakdownWarranty Information Keep this Warranty