FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

6

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum BTU/Hr

the space can support)

Example: 2304 cu. ft. (volume of space) ÷ 50 cu. ft. = 46.1 or 46,100 (maximum BTU/Hr the space can support)

3. Add the BTU/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ BTU/Hr

Gas water heater*

 

___________________ BTU/Hr

Gas furnace

 

 

___________________ BTU/Hr

Vented gas heater

 

___________________ BTU/Hr

Gas fireplace logs

 

___________________ BTU/Hr

Other gas appliances*

+ ___________________ BTU/Hr

Total

= ___________________ BTU/Hr

Example: Gas water heater

 

40,000

BTU/Hr

Vent-free heater

+

10,000

BTU/Hr

Total

=

 

 

BTU/Hr

50,000

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum BTU/Hr the space can support with the actual amount of BTU/ Hr used.

_________________

BTU/Hr (maximum the space can support)

_________________

BTU/Hr (actual amount of BTU/Hr used)

Example: 46,100

BTU/Hr (maximum the space can support)

50,000

BTU/Hr (actual amount of BTU/Hr used)

The space in the above example is a confined space because the actual BTU/Hr used is more than the maximum BTU/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING

WARNING ICON

G 001

You must provide additional ventilation air in a confined space.

099404

Image 6
Contents OWNER’S Operation and Installation Manual Model CGN10 What to do if YOU Smell GASContents Safety Information Safety Information Product Identification Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemVentilation Fresh AIR ForCombustion Producing Adequate VentilationFresh AIR for Combustion and Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation AIR Ventilation Air From OutdoorsNever install the heater A bathroom A recreational vehicle Installing To WallInstallation Items Check GAS TypeInstalling Heater to Wall Marking Screw LocationsInstalling Two Mounting Screws Folding AnchorPlacing Heater On Mounting Screws Connecting to GAS Supply Connecting to GAS Supply Checking GAS Connections Pressure Testing GAS Supply Piping SystemGAS Pressure Testing Heater GAS ConnectionsChecking ConnectionsFor Your Safety Read Before Lighting Operating HeaterHeater OperatingShutting Off Heater Operating Heater Inspecting BurnerPilot Flame Pattern Shutting Off Burner Only pilot stays litBurner Flame Pattern Correct Burner Flame PatternCabinet Cleaning and Maintenance Trouble ShootingODS/PILOT and Burner Orifice Air PassagewaysSee Cleaning TROUBLE- ShootingObserved Possible Remedy Problem Cause Trouble Shooting Parts Under Warranty Technical ServiceService Hints Replacement Parts Parts Not Under WarrantyService Publications Accessory Parts CentralsValve GA5010 Heater Exploded View Parts List CGN10 Warranty Information Keep this Warranty

CGN10 specifications

Desa CGN10 represents a significant advancement in the realm of sustainable energy solutions, particularly within the context of decentralized energy generation. This innovative concept is engineered to promote efficiency and sustainability, making it a noteworthy option for both urban and rural applications.

One of the defining features of Desa CGN10 is its versatility. The system can be deployed in various environmental contexts, accommodating diverse energy needs ranging from residential to industrial applications. Its modular design allows for scalability, enabling users to customize their energy generation capabilities according to their specific requirements.

Incorporating cutting-edge renewable energy technologies, Desa CGN10 offers multi-source energy generation, including solar, wind, and bioenergy. The integration of these sources enhances energy reliability and diminishes dependence on traditional fossil fuels. The solar component utilizes high-efficiency photovoltaic panels, designed to capture maximum sunlight and convert it into usable energy. Wind turbines included in the system leverage advanced aerodynamic designs for improved performance in varying wind conditions. Additionally, bioenergy capabilities allow for the conversion of organic waste into energy, fostering circular economy principles.

Another significant characteristic of the Desa CGN10 is its advanced energy management system (EMS). This intelligent framework optimizes energy generation and consumption, ensuring that the available resources are used in the most efficient manner. The EMS employs real-time data analytics, allowing for predictive maintenance, which in turn minimizes downtime and enhances overall system reliability.

Furthermore, Desa CGN10 prioritizes user experience through a user-friendly interface that grants users control over their energy production and consumption. This interface provides insights into energy usage patterns, enabling users to make informed decisions and contribute to energy conservation efforts.

Overall, Desa CGN10 is a forward-thinking solution that represents a fusion of innovative technologies and sustainable practices. It empowers communities and businesses to harness renewable energy, reduce carbon footprints, and take significant strides toward energy independence. As the world shifts toward cleaner energy solutions, Desa CGN10 is poised to play a crucial role in the transition to a more sustainable future.