Desa LSL3124N Ventilation Air From Inside Building, Ventilation Air From Outdoors, Continued

Page 6
Inside Building.

6

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location (Cont.) Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the

extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From

Inside Building.

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills

Into Adjoining Room,

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors.

Room,

Or

Option 2

Option 1

Remove

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

VENTILATION AIR WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Door into Adjoining Room, Option Ventilation Air From Inside Building 3

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

Ventilation Air From OutdoorsFigure 2 - Ventilation Air from Inside BuildingFigure 3 - Ventilation Air from OutdoorsManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

111347-01B

Image 6
Contents UNVENTED VENT-FREE GAS LOG HEATER WHAT TO DO IF YOU SMELL GASDo not try to light any appliance TABLE OF CONTENTS SAFETY INFORMATIONWARNINGS Continued LOCAL CODESUNPACKING SAFETY INFORMATIONPRODUCT IDENTIFICATION PRODUCT FEATURESSAFETY DEVICE AIR FOR COMBUSTION AND VENTILATIONUnusually Tight Construction PROVIDING ADEQUATE VENTILATIONDETERMINING FRESH-AIRFLOW FOR HEATER LOCATION Confined and Unconfined SpaceVentilation Air From Outdoors VENTILATION AIRVentilation Air From Inside Building AIR FOR COMBUSTION AND VENTILATIONMINIMUM FIREPLACE CLEARANCE TO INSTALLATIONCHECK GAS TYPE COMBUSTIBLE MATERIALSSafe Installation Minimum Noncombustible Material ClearancesINSTALLATION ContinuedDetermining Minimum Mantel Clearance MANTEL CLEARANCESFLOOR CLEARANCES INSTALLATIONArea of Various Standard Round Flues INSTALLING HEATER BASE ASSEMBLYInstallation Items Needed INSTALLATIONInstallation Items Needed CONNECTING TO GAS SUPPLYINSTALLATION ContinuedCHECKING GAS CONNECTIONS Pressure Testing gas Supply Piping systemPressure Testing Heater Gas Connections INSTALLATIONINSTALLATION INSTALLING LOGSVariable Manually-ControlledModels LSL ContinuedREAD BEFORE LIGHTING MANUALLY-CONTROLLEDMODELS FOR YOUR SAFETYOPERATING HEATER LIGHTING INSTRUCTIONSVARIABLE CONTROL OPERATION OPERATING HEATERContinued TO TURN OFF GAS TO APPLIANCE MANUAL LIGHTING PROCEDURETHERMOSTAT MODELS FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING HEATER THERMOSTAT CONTROL OPERATIONMANUAL LIGHTING PROCEDURE ContinuedPILOT FLAME PATTERN CLEANING AND MAINTENANCEINSPECTING BURNERS BURNER PRIMARY AIR HOLESCLEANING AND MAINTENANCE SPECIFICATIONSLOGS ContinuedPOSSIBLE CAUSE TROUBLESHOOTINGOBSERVED PROBLEM REMEDYRefer to Air for Combustion and Venti For morevisit www TROUBLESHOOTINGOBSERVED PROBLEM ing Gas Connections, pages 12 andTROUBLESHOOTING ContinuedOPTIONAL POSITIONING OF THERMOSTAT SENSING BULB For Masonry and Factory-BuiltMetal FireplaceECHO VALLEY OAK LOG MODELS LSL3124N, LSL3124P ILLUSTRATED PARTS BREAKDOWNVARIABLE MANUALLY- CONTROLLED 3 - ODS PilotECHO VALLEY OAK LOG MODELS PARTS LISTVARIABLE MANUALLY-CONTROLLED PARTS LISTILLUSTRATED PARTS BREAKDOWN THERMOSTATICALLY- CONTROLLEDMEADOWBROOK OAK LOG MODELS CDL3924NT, CDL3924PT ILLUSTRATED PARTS BREAKDOWNPARTS LIST THERMOSTATICALLY- CONTROLLED MEADOWBROOK OAK LOGPARTS LIST PART NUMBER FORTECHNICAL SERVICE ACCESSORIESSERVICE HINTS REPLACEMENT PARTSOWNERS REGISTRATION FORM TAPE Postage Required2701 Industrial Drive P.O. Box Bowling Green, KY TAPEPage NOT A UPC WARRANTY INFORMATIONLIMITED WARRANTY VENT-FREEGAS LOG HEATERS Model Serial No Date Purchased