Desa LSFG20NT, VSF30PT installation manual AIR for Combustion Ventilation, Ventilation AIR

Page 6

AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (6.1 m) (length) x

16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

___________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example:2560 cu. ft. (72.4 m3) (volume of space) x 20

= 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances* +____________ Btu/Hr

Total

=____________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

40,000

 

Gas water heater

 

Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Total

=

60,000

Btu/Hr

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" (30.4 cm) of the ceiling and one within 12" (30.4 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

12"

Figure 2 - Ventilation Air from Inside

Building

www.desatech.com116307-01C

Image 6
Contents Residential Models SF20NT, SF20PTGarage Models Table of Contents Safety InformationSafety Information Local Codes Safety InformationProduct Features Product IdentificationAir For Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location AIR for Combustion Ventilation Ventilation AIRVentilation Air From Inside Building Check GAS Type InstallationInstallation Items Ventilation Air From OutdoorsInstalling Heater to Wall Locating HeaterPlacing Heater On Mounting Screws Connecting to GAS SupplyMarking Screw Locations Locate hardware packet behind left side door of heaterNatural Gas Propane/LPTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Pressure Testing Heater Gas ConnectionsChecking GAS Connections Open equipment shutoff valve see FigureFor Your Safety Read Before Lighting Installing Refractory and Front PanelOperating Heater Shutting Off Heater Lighting InstructionsTo Turn OFF GAS To Appliance Shutting Off Burner Only pilot stays litOperation Manual Lighting ProcedureInspecting Heater Pilot Flame PatternBurner Pilot Air Inlet Cleaning MaintenanceODS/PILOT and Burner CabinetTroubleshooting Observed Problem Possible Cause RemedyTroubleshooting When heated, vapors from Turn heater off when using Noise when burner is litDirty or partially clogged Clean burner see Cleaning Turn off air supplyWhen Gas Pressure Is Too Low Technical ServiceService Publications Service Hints Gas leak. See WarningVSFG20NT VSGF20PT SpecificationsLSF20NT, LSFG20NT, VSF20NT LSF20PT, LSFG20PT, VSF20PT SF30NT SF30PTAccessories Replacement PartsParts Central Illustrated Parts Breakdown Parts List Warranty Information Keep this WarrantyConsumidor Conserve este manual para referencias futuras ModelosModelos Para Cochera Tabla de contenido Información de seguridadInformación de seguridad Desempaque Códigos localesIdentificación del Producto Características del ProductoConstrucción inusualmente sellada Aire para combustión VentilaciónCómo Procurar LA Ventilación Adecuada Espacio confinado y no confinadoAire Para Combustión Ventilación Aire Para VentilaciónAire del interior de la construcción para Ventilación Instalación Verifique EL Tipo DE GASArtículos DE Instalación De las partes anterior, superior Ubicación DEL CalentadorDonde cortinas, muebles, ropa Fuertes corrientes de aireColocación del calentador en los Tornillos de montaje Instalación DEL Calentador EN LA ParedDoble en anclaje de pared como se muestra en la figura Coloque el calentador en los tornillos de montajeConexión AL Suministro DE GAS Ventila apuntando hacia abajoRevisión DE LAS Conexiones DE GAS Gas naturalRepare todas las fugas inmediatamente Instalación del panel anterior y el refractario Abra la válvula de cierre del equipo consulte la figuraInstale el panel anterior y el refractario Instale un difusor frontal como se muestra en la figuraFuncionamiento del Calentador Instrucciones DE EncendidoFuncionamiento DEL Inspección del CalentadorCómo Cerrar EL Suministro DE GAS AL Aparato Encendido ManualInspección del Limpieza y MantenimientoPatrón DE LA Llama DEL Calentador SF30NT EspecificacionesGabinete LSF30NT, VSF30NTSolución de problemas Causa Posible RemedioSolución DE Problemas Combustión El problema desapareceráLlama amarilla durante la No hay suficiente aire En el quemadorConsejos para servicio Servicio técnicoPublicaciones de servicio Al inicio de la páginaCentral de piezas AccesoriosPiezas de repuesto Válvula DE Cierre DEL Equipo GA5010Clasificación ilustrada de piezas Lista DE Piezas Información de garantía Guarde Esta Garantía

VSF30PT, LSFG20NT specifications

The Desa VSF30PT and LSFG20NT represent two significant innovations in the HVAC (Heating, Ventilation, and Air Conditioning) industry, catering to diverse consumer needs and preferences.

The Desa VSF30PT is a powerful and efficient forced-air heater designed for residential and light commercial applications. One of its primary features is its high-efficiency output, providing a substantial heating capacity while consuming minimal energy. The unit is equipped with a robust heat exchanger that enhances its performance, ensuring optimal heat distribution throughout the space. A notable characteristic of the VSF30PT is its user-friendly digital thermostat, allowing for precise temperature control, which can significantly improve comfort levels and reduce energy consumption.

Additionally, the Desa VSF30PT incorporates advanced safety features, such as automatic shut-off protection in case of overheating or airflow obstruction. Its compact design makes it easy to install in tight spaces, providing flexibility in placement without compromising on effectiveness. The unit operates quietly, minimizing noise disturbances, which is especially important in residential settings.

On the other hand, the LSFG20NT is an innovative gas furnace that combines performance with energy efficiency. This model is equipped with a variable-speed blower motor that allows for consistent airflow and improved humidity control, making it an excellent choice for homeowners who prioritize comfort. Its multi-stage heating design ensures that the furnace operates at different levels according to the heating demand, optimizing energy usage and enhancing overall efficiency.

The LSFG20NT also features a modulating gas valve, which adjusts the burner output to provide just the right amount of heat for any given situation. This not only improves comfort but also contributes to significant energy savings over time. Furthermore, the LSFG20NT is designed with advanced filtration systems that improve indoor air quality by trapping dust, allergens, and other particles.

Both units showcase the latest technology in HVAC systems, emphasizing energy efficiency, safety, and user convenience. With their unique features and characteristics, the Desa VSF30PT and LSFG20NT stand out in the market, making them ideal choices for those seeking reliable and efficient heating solutions. Whether for residential or light commercial applications, these models promise performance that meets the demands of modern-day heating needs.