DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = __________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_______________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

 

 

 

 

Gas water heater*

 

_____________ Btu/Hr

Example:

 

 

 

Gas furnace

 

_____________ Btu/Hr

 

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

 

 

Vent-free heater

+

33,000

Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

 

 

=

 

 

Other gas appliances*

+

_____________ Btu/Hr Total

73,000

Btu/Hr

Total

=

_____________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

105070

5

Image 5
Contents What to do if YOU Smell GAS Also DESIGN-CERTIFIED AS a Vented Decorative ApplianceSafety Information Local Codes Product FeaturesUnpacking Product IdentificationProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation Clearances InstallationCheck GAS Type Vent-Free Operation OnlyMinimum NonCombustible Material Clearances If Using MantelMantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstallation Items Needed Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Attaching Flexible Gas Hose to Heater Gas Regulator Connecting to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Installing Front Logs #1L and #1R Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater Inspecting Burners Specifications Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole LogsObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Variable Manually Controlled Models VFN18MV VFN24MV VFN30MV Illustrated Parts BreakdownVFN18MV VFN24MV VFN30MV Parts ListVariable MANUALLY- Controlled Models Technical Service Service HintsReplacement Parts Accessories 105070 Warranty Information