Desa GWP30TA Installation, Ventilation AIR, Check GAS Type, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Com- bustion and Ventilation for required size of ventilation grills or ducts.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

Installation

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not

Ventilation

 

Grills into

Or

Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

install this heater as your pri- mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

12"

Figure 2 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermo- stat-controlled power vent. Heated air entering the attic will activate the power vent.

WARNING: A qualified ser- vice person must install heater. Follow all local codes.

CHECK GAS TYPE

Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

WARNING: This appliance is equipped for natural or pro- pane/LP gas. Field conversion is not permitted.

119344-01Bwww.desatech.com

Image 7
Contents Models GWN20TA, GWP20TA, GWN30TA, GWP30TA, WMN20a, WMP20a What to do if YOU Smell GASSafety Information Table of ContentsSafety Information Unpacking Safety InformationProduct Features Local CodesConfined and Unconfined Space Air For Combustion VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building InstallationVentilation AIR Check GAS TypeThis heater is designed to be mounted on a wall InstallationInstallation Items Locating HeaterInstalling Heater to Wall Attaching To Wall Anchor Method 30,000 Btu/Hr Models20,000 Btu/Hr Models Attaching To Wall Stud MethodMounting Base Feet to Heater Installing Bottom Mounting ScrewsMounting heater to floor With optional floor kit Heater WallTypical Inlet Pipe Diameters Connecting to GAS SupplyTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsCorrect all leaks at once Pressure Testing Heater Gas ConnectionsDo not try to light any appliance For Your Safety Read Before LightingOperating Heater Lighting InstructionsThermostat Control Operation Manual Lighting ProcedureOperating Heater To Turn OFF GAS To AppliancePilot Flame Pattern Inspecting HeaterBurner Flame Pattern Cabinet Cleaning MaintenanceODS/PILOT and Burner Burner Pilot Air InletObserved Problem Possible Cause Remedy TroubleshootingTroubleshooting Burner orifice Observe minimum installaSlight smoke or odor during BlockedStatement above Gas leak. See WarningTechnical Service SpecificationsService Hints Replacement PartsModels WMN20A, WMP20A, GWN20TA, GWP20TA, GWN30TA and GWP30TA Illustrated Parts BreakdownNJF 8C Parts ListElectronic ignitor Kit GA435 Not Shown AccessoriesEquipment Shutoff Valve GA5010 Base Kit GA4550Parts Centrals Industrial Drive P.O. Box 119344-01 Rev. B Warranty InformationKeep this Warranty Model Serial No Date of Purchase