Quadra-Fire 7100FP-NL-B, 7100FP-BK-B Getting Started, Design and Installation Considerations

Page 6

R

7100FP EPA Woodburning Fireplace

2 Getting Started

A. Design and Installation Considerations

CAUTION

Check building codes prior to installation.

Installation MUST comply with local, regional, state and national codes and regulations.

Consult insurance carrier, local building inspector, fire officials or authorities having jurisdiction about restrictions, installation inspection and permits.

When planning a fireplace installation, it is necessary to de- termine the following information before installing:

Where the fireplace is to be installed. See Sections 3 and 4.

The vent system configuration to be used. See Sections 5 and 6.

Electrical wiring. See Section 3.

Framing and finishing details. See Sections 3, 6 and 8.

Whether optional accessories are desired. See Section 12.

Draft is the pressure difference needed to vent fireplaces successfully. Considerations for successful draft include:

Preventing negative pressure

Location of fireplace and chimney

WARNING

Asphyxiation Risk

Negative pressure can cause spillage of combustion fumes and soot. Fire needs to draft properly for safe operation.

B. Negative Pressure

Negative pressure results from the imbalance of air avail- able for the fireplace to operate properly. Causes for this imbalance include:

Exhaust fans (kitchen, bath, etc.).

Range hoods.

Combustion air requirements for furnaces, water heaters and other combustion appliances.

Clothes dryers.

Location of return-air vents to furnace or air conditioning.

Imbalances of the HVAC air handling system.

Upper level air leaks: recessed lighting, attic hatch opening, duct leaks.

To minimize the effects of negative air pressure, the follow- ing must be considered:

Install the outside air kit.

Ensure adequate outdoor air is supplied for combustion appliances and exhaust equipment.

Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the fireplace.

Avoid installing the fireplace near doors, walkways or small isolated spaces.

Recessed lighting should be a “sealed can” design; attic hatches weather stripped or sealed; attic mounted duct work and air handler joints and seams taped or sealed.

Location of the fireplace and chimney will affect performance. As shown in Figure 7.1, on page 7, the chimney should:

Be installed through the warm airspace enclosed by the building envelope. This helps to produce more draft, especially during lighting and die-down of the fire.

Penetrate the highest part of the roof. This minimizes the effects of wind turbulence.

Be located away from trees, adjacent structures, uneven roof lines and other obstructions.

Offsets can restrict draft so their use should be minimized. Consider the fireplace location relative to floor and ceiling and attic joists.

The 7100FP Fireplace requires a minimum flue draft of -0.10 inches of water column on High, and -0.04 inches of water column on Low, as measured with a draft meter. Most deal- ers have draft meters available to measure your flue draft if you suspect a problem.

If the fire is difficult to start, and smoke spills out of the door, or you find it hard to establish and maintain a moderately high burn rate, then the flue draft is too low and corrective measures must be taken.

NOTE: Cold air infiltration can cause frosting on glass.

Page 6

433-1390D

September 7, 2007

Image 6
Contents 7100FP-BK-B 7100FP-GD-B 7100FP-NL-B Fire Risk7100FP EPA Woodburning Fireplace 007Location on hang tag on right side of fireplace Table of Contents Listing and Code Approvals Appliance CertificationMobile Home Approved 7100FP EPA Woodburning Fireplace Glass Specifications BTU & Efficiency SpecificationsNegative Pressure Design and Installation ConsiderationsGetting Started Asphyxiation RiskSeptember 7 433-1390D 7100FP EPA Woodburning Fireplace Typical Fireplace System Typical Fireplace System7100FP EPA Woodburning Fireplace Tools and Supplies Needed Inspect Fireplace and ComponentsFire Risk Explosion Risk Framing and Clearances Selecting Fireplace LocationModel #7100FP 7100FP EPA Woodburning Fireplace Clearances Clearances to Combustible MaterialsNon-Combustible Materials Frame the FireplaceMinimum Clearances to Combustibles Combustible MaterialsElectrical Access and Wiring Diagram Suggestions7100FP EPA Woodburning Fireplace Construct the Chase MaterialsInstallation of Fireplace Install the Outside Air KitFire Risk Asphyxiation Risk Risk of Smoke SpillageHandle Left Closed Handle Right Open Auxiliary Convection Air System Attic spaceConvection Air Lock Level the Fireplace 7100FP EPA Woodburning Fireplace Secure the FireplacePosition the Fireplace Place the Protective Metal Hearth StripsChimney Assembly 7100FP EPA Woodburning Fireplace Chimney Requirements Chimney Termination Requirements7100FP EPA Woodburning Fireplace Using Offsets/Returns ExampleAssembling Chimney Sections for the SL- 300 Series Assembling Chimney SectionsInstall the Ceiling Firestops Installing Flex PipeDouble-check the Chimney Assembly Secure the ChimneyChimney Termination Requirements See Figures 26.1 Complete the EnclosureChimney Termination 2-10-03 Rule Slanted RoofsMark the Exit Point of the Roof Install the Roof FlashingInstall the Chimney Air Kit required in Canada Cut Out the Hole in the RoofConsult local codes for framing details Install the Termination Cap 7100FP EPA Woodburning Fireplace Chase TopChase Top Framing For installations utilizing a Round Telescoping Termination Blower Replacement Instructions AccessoriesBlower Replacement Blower Cord LocationDoor and Door Gasket Right Door7100FP EPA Woodburning Fireplace Heat Zone Kit Minimum Clearance to CombustiblesRun Length Cut Pipe 20 40 ft 6-12m 20 ft 3 6m 10 ft 1 3mBracket 7100FP EPA Woodburning Fireplace Timer Assembly Replacement Remove 2 screwsTimer Plate 7100FP EPA Woodburning FireplaceFinishing Hearth ExtensionModel # 7100FP Positioning the Protective Metal Hearth StripsOuter Can Flange Fascia Tile or Marble Combustible Floor Non-Combustible Sealant Material Finishing MaterialNon-Combustible Material Cardboard or Metal TemplateComplete installation Risk of Fire7100FP EPA Woodburning Fireplace Mantel Mantel SpecificationsOperating Instructions General InformationKeep open during use Firescreen 7100FP EPA Woodburning Fireplace Outside AirClear Space Near the Fireplace Glass DoorsWood Fuel Hardwood vs. Softwood 7100FP EPA Woodburning Fireplace Blower OperationHeat Zone Operation Minimum Clearance to Combustible 1 in mm from the B-Vent7100FP EPA Woodburning Fireplace Moisture content SeasoningStoring Wood 7100FP EPA Woodburning Fireplace Starting a Fire Final stage Kindling or 1st stage2nd stage Slide Air ControlBurn Rates Emissions, follow these operating procedures7100FP EPA Woodburning Fireplace Burning Guidelines Opacity For maximum operating efficiency with the lowestOverfiring Fire Safety Chimney FireTroubleshooting Understanding Vent ProblemsDraft Problems Factory-built Fireplaces Troubleshooting Diagnostic Question Possible Causes of Condition Solutions If I can’t get a good fire going, what am I doing wrong?Don’t get enough/any heat. What can I do about it? Maintenance and Servicing the Fireplace General MaintenanceDisposal of Ashes Glass ReplacementGlass Cleaning Fire Risk Injury RiskVide brick dimension or copy this page, mark the desired 7100FP EPA Woodburning Fireplace Brick ReplacementUse Part 832-2370 when ordering individual brick. Pro Brick and take it to your authorized dealerMaintenance Task List Inspect Maintenance TasksFireplace Dimensions Reference Materials7100FP FS338 14-1/2 368 mm FS339 18-3/8 467 mm 7100FP EPA Woodburning Fireplace Chimney ComponentsCatalog Description Catalog No FS340 16-3/4 425 mm15-3/4 Glass Size 12-3/50 w x 15 h 7100FP EPA Woodburning Fireplace Fireplace Diagram 17 13 1514 27 25 21247100FP EPA Woodburning Fireplace Service Parts Part DescriptionAlphabetical Order Accessories RIVNUT-REPAIRLifetime Warranty 7100FP EPA Woodburning Fireplace Warranty Policy7100FP EPA Certified Woodburning Fireplace Contact InformationDealer Telephone

7100FP-BK-B, 7100FP-GD-B, 7100FP-NL-B specifications

The Quadra-Fire 7100FP series, including the models 7100FP-BK-B, 7100FP-NL-B, and 7100FP-GD-B, represents an exceptional choice for homeowners seeking efficient and powerful heating solutions. These fireplaces are designed to provide warmth and ambiance while incorporating advanced technologies that enhance performance and ease of use.

One of the primary features of the 7100FP series is its large viewing area, which allows homeowners to enjoy the mesmerizing flames while increasing the aesthetic appeal of any living space. The generous size of the firebox ensures that it can accommodate sizable logs, providing longer burn times and requiring less frequent reloading. This feature is particularly beneficial for those who appreciate an extended, leisurely evening by the fire.

A hallmark of the Quadra-Fire brand is its innovative heating technology. The 7100FP models are equipped with the patented Quadra-Fire combustion system, which promotes a cleaner burn and maximizes heat output. This system utilizes secondary combustion technology that burns off excess gases and particulates, resulting in a more environmentally friendly fire that emits fewer emissions compared to traditional wood-burning fireplaces.

Additionally, the 7100FP series includes advanced airflow designs that facilitate efficient heat distribution throughout the room. The adjustable air control allows users to easily regulate the burn rate and heat output, ensuring optimal comfort at any time. With a variety of trim options available, including the sleek black, traditional natural, and modern gold finishes, homeowners have the flexibility to choose a model that complements their interior decor.

Moreover, the 7100FP series is designed with user convenience in mind. For easy cleaning and maintenance, they include a removable ash pan feature. A glass viewing window is treated with a special coating, preventing soot buildup and allowing for uninterrupted views of the flames.

In terms of safety, the 7100FP units are equipped with a tempered glass door that is designed to withstand high temperatures, ensuring that the fireplace is safe for family gatherings. Overall, the Quadra-Fire 7100FP-BK-B, 7100FP-NL-B, and 7100FP-GD-B models seamlessly combine style, efficiency, and comfort, making them a top choice for those seeking a modern solution to home heating. With innovative technology and a commitment to performance, these fireplaces enhance any home’s ambiance while providing reliable warmth.