Monessen Hearth NB18, NB24 operating instructions Special Requirements

Page 37

SPECIAL REQUIREMENTS CONTINUED

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

81D0107

37

Image 37
Contents Read and Save These Instructions Model NB18, NB24What to do if YOU Smell GAS Contents Installer Important Safety InformationOwner Massachussetts Residents only Getting Started What YOU will Need for InstallationMake Sure YOU have Received ALL Parts Product Features and Specifications Codes General Installation InformationAdequate Combustion and Ventilation AIR BTU / Hr = Model Fireplace and Hearth DimensionsHeight of Restriction Minimum Depth of Fireplace/Firebox Placement in a Fireplace with a Restrictive BarrierSidewall and Ceiling Clearances Clearances and Height RequirementsClearances and Height Requirements Measuring Heat Resistant Material for Mantel Minimum Mantel Clearance with No Hood -NB18 Mum of 10 at a minimum of 28 above the opening Minimum Clearance above Combustible Flooring Floor ClearanceBefore Fully Installing the Unit Installing Vented ApplicationsBefore Installing the Appliance Damper Stop InstallationAssembly Procedure Installing Vented ApplicationsPlacing and Securing Appliance Flexible Tube Manual Shutoff Gas Supply Inlet Valve Connecting the GASMillivolt Valve Control Figure Checking GAS PressureConnecting Optional Wall Switch or Thermostat Electrical Wiring MillivoltATE Checking System Operation Connecting Remote ReceiverComplete Millivolt System Check Placing Rock Wool LOG PlacementPlacing Log #3 Cast Iron Grate Installation EMBER, GRATE, and Rock InstallationPlacing Flickering Embers Placing the Decorative RockChecking the Pilot Flame Flame AppearanceMillivolt Control and Thermostat Control Operating Instructions Checking the Burner FlameWhat to do if YOU Smell GAS Operating InstructionsTo Turn OFF GAS to Heater Cleaning and Servicing Operating Instructions and Cleaning and ServicingObserved Problem Possible Cause Remedy TroubleshootingODS/pilot lights, but flame Burner Assembly Replacement PartsAccessories Sold Separately Replacement Parts ListDescription Qty BO18-R BO18-F BO24-R BO24-F BO30-R BO30-F Berkley OAK Refractory LogsCarbon Monoxide Detector Requirements Special Requirements 81D0107 81D0107 Five Year Warranty Lifetime WarrantyBasic Warranty