\'ENTTNG PlOBLEMS
TROUBLE SHOOTING
Mostventingproblemsarecausedbyincorrect ventsizing,improperinstallation,or inadequate air supply.A preliminarycheck for a field problemmightinclude:
. Usinga draftmeterto determineif venting systemdraftmeetsmanufacturer'sspecifica- tions.
rCheckingthe vent sizing accordingto manufacturer'sspecifications,appliance input,andventingconfiguration.
rExaminingthe entireventingsystemfor faults such as disconnectedjoints or damagedventsections.
oMakingsureventandairopeningsarenot obstructed.
lf theseproceduresdo not revealthe source of the problem,troubleshootingmayinclude attentionto common venting problems discussedbelow.
FLUEGASSPILLAGE
Spillageoccurswhenflue gasescannotexit theventsystemandbackupintothedwelling.
Aprimarysymptomof appliancesequipped with a VentSafetyShutoffSystem(fluespill switch)is unexplainedapplianceshutoffs. Othersymptomsoffluegasspillageatthedraft hood include cendensationon walls and windowsand/ornoticeableodoursBut.spillage may also result in the releaseof carbon monoxide,a colourless,odourless,highlytoxic gas.A simplespillagetestcanbe conducted if spillageis suspected;seeownersmanual.
CAUSESOF SPILLAGEAND CORRECTIVEACTION
IncorrectVentSizing(H)
lf theventistoosmallortooshort,spillagemay occur.lf theventistoolarge,excessivedilution air may cool flue gasesand reducedraft, causingspillageThe.ventcapsizeshouldalso be checked.Checkmanufacturer'sinstruc- tions,applianceinputrating,andappropriate sizingtables.
Venting Condltion
Loosejointscanaffectdraftandcausespillage.
Obsfructions
Smallanimalsor birdsmaygetintoandblock the ventor drafthoodoutlet.Dust,lint,and foreignobjectsmayobstructairinletsRemove. obstructionsand cleanoPenings.
LateralRun (L)
Lengthyhorizontalor
the applianceto the vent.
Elbows
Toomanyelbowscauseexcessiverestriction of flowand mayresultin spillageUsually,.two 90 degreeturnscanbetoleratedin a properly sizedventingsystemMore.thantwo
Negativepressure in the Dwelling
An extremellytight house may not supply adequatecombustionandventingair.Useof mechanicalexhaustsuchas a dryerventor rangeventmayworsenthe problemAn. air exchangesystemmustbeinstalledInthedwell' ing to correctthis Problem.
Flue Gas Cooling
Venting exposed to extremelY cold temperaturesorventingofsinglewallconstruc- tion lose heat needed to maintaindraft;
massivemasonrychimneysabsorbneeded heat.lf the flue gasescool excessively,draft isreducedandspillagemayresultUse.proper materials,insulateandprotectproperly'reline
when necessary.
Down Drafts
tn certainwind conditionsand in certain relationshipswith nearby structuresand objects,high pressureconditionsrnayatfect
draftnegativelyRelocate. the ventcap, raise itsheighl,or usean approvedhighwindcap.