Vermont Casting 2550 installation instructions Installation, Outside Air, Chimney Height

Page 4

Encore Woodburning Stove

Installation

SAFETY NOTICE: IF YOUR ENCORE IS NOT PROP- ERLY INSTALLED, A HOUSE FIRE MAY RESULT. TO REDUCE THE RISK OF FIRE, FOLLOW THE INSTALLATION INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRIC- TIONS AND INSTALLATION INSPECTION REQUIRE- MENTS IN YOUR AREA.

Before you begin an installation, be sure that:

Your stove and chimney connector will be far enough from combustible materials to meet all clearance requirements.

The floor protector is large enough and is con- structed properly to meet all requirements.

You have all necessary permits from local au- thorities.

Your local building official is the final authority for ap- proving your installation as safe and determining that it meets local and state codes.

The metal label permanently attached to the back of every Vermont Castings’ stove indicates the stove has been tested to current UL and ULC standards, and gives the name of the testing laboratory. Clearance and installation information also is printed on the label. When the stove is installed according to the information both on the label and in this manual, local authorities in most cases will accept the label as evidence that the installation meets codes and can be approved.

However, codes vary in different areas. Before starting the installation, review your plans with the local building authority. Your local dealer can provide any additional information needed.

For any unresolved installation issues, refer to the National Fire Protection Association’s publication ANSI/NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances. For Canada, the equivalent publication is CSA CAN-B365 Installation Code for Solid Fuel Burning Appliances and Equipment. These standards are the basis for many national codes. They are nationally recognized and are accepted by most local authorities. Your local dealer or your local building official may have a copy of these regulations.

IMPORTANT: FAILURE TO FOLLOW THESE IN- STALLATION INSTRUCTIONS MAY RESULT IN A DANGEROUS SITUATION, INCLUDING A CHIMNEY OR HOUSE FIRE. FOLLOW ALL INSTRUCTIONS EXACTLY, AND DO NOT ALLOW MAKESHIFT COM- PROMISES TO ENDANGER PROPERTY AND PER- SONAL SAFETY.

Outside Air

In some modern, super-insulated homes, there is inadequate air for combustion because of insufficient air infiltration into the building. Such air enters a home through unsealed cracks and openings. Exhaust fans for kitchen or bath can compete with the stove for avail- able air and compound the problem.

When poor draft is caused by a low infiltration rate, opening a ground floor window on the windward side of the house and in the vicinity of the stove will usually alleviate the problem.

Another solution is to install a permanent outside air supply to the stove and/or room. In fact, bringing air for combustion from outside the home directly to the air inlet of the stove is required for new construction in some areas.

Pressure variations within the house do not affect a stove equipped with an outside air supply, and im- proved stove performance often results. An Outside Air Adapter Kit for the Encore is available from your local Vermont Castings dealer.

Chimney Height

Altitude affects chimney performance. When using a 6” flue collar on the Encore, refer to Figure 2 for sug- gested chimney heights at various altitudes. Chimney height should be measured from the flue collar to the top of the chimney. The recommended minimum chim- ney height is 16’ (4.9m).

 

30

Height

25

20

 

15

0 2000 4000 6000 8000 10000 12000

ST491Altitude

Fig. 2 Chimney height requirements for Encore when equipped with a 6” chimney.

4

2000956

Image 4
Contents Encore Table of Contents WelcomeEncore dimensions SpecificationsOutside Air InstallationChimney Height What Kind of Chimney to Use Masonry ChimneysPrefabricated Chimneys Chimney SizeDouble-wall Chimney Connectors Chimney Connector GuidelinesSingle-wall Chimney Connectors Securing the Single-wall Connector to a Masonry Chimney Freestanding InstallationsFireplace Installations Above the FireplaceThrough the Fireplace Wall Pass-ThroughsFloor Protection An approved wall pass-through for the United StatesKeep the Stove a Safe Distance From Surrounding Materials Floor Protection for Fireplace InstallationsReducing Clearances Safely with Shields Stove Heat Shields Wall ShieldsChimney Connector Heat Shields Fireplace and Mantel Trim ShieldsAlcove Installations Construction RequirementsEncore Clearance Chart Unprotected Surfaces Protected SurfacesEncore Clearance Diagrams Wall Shield Requirements for Common Installations Corner Parallel Installations Assembly Operation Encore ControlsSingle Air Control Regulates Heat Output and Burn Time Damper Directs Air Flow Within the StoveTwo Ways to Add Fuel Encore’s hinged griddle makes it easy to top-load woodUse the Air Control Settings That Work Best for You Infrared Reflective Glass Panels For Clear Fire ViewingAndirons Help Protect the Glass Burn Only High-Quality WoodEncore Control Settings High-Efficiency Wood Burning with Catalytic CombustionConditioning Your Stove Starting and Maintaining a Wood FireRefuel While the Embers Are Still Hot Ash DisposalSteel Chimney Draft ManagementIndoor / Outdoor location Flue Sizing Pipe & Chimney LayoutSingle venting CreosoteMaintenance Installing the Glass Adjust the Damper as NeededRemoving the Glass Check the Operation Primary Air ShutterHow to Adjust the Door Latches Catalytic Element Inspection and CleaningWhen to Suspect a Combustor Problem Tighten the Damper Handle as NeededInspecting the Combustor Remove the lower fireback through the front door openingReplace the Stove Gaskets as Needed Gasket Diameter ...And the Parts it SealsAdjust the Door If Necessary Annual MaintenancePermanent Encore Gaskets Chimney System CreosoteAppendix Catalytic Combustor Encore Woodburning Stove Encore Woodburning Stove Shell Enamel Parts Encore Color Encore Woodburning Stove Encore Woodburning Stove Warranty CFM Corporation