Vermont Casting 2550 installation instructions Stove Heat Shields, Wall Shields

Page 11

In general, the greatest clearance is required when you place a stove and its connector with no heat shields near a wall with no heat shield.

For example, when the Encore is installed parallel to the rear wall and no shields are used, it must be at least 31” (787 mm) from the wall behind it and at least 24” (610 mm) from walls on either side.

If the Encore is installed in a corner and no shields are used, the corners of the stove must be at least 24” (610 mm) from nearby walls.

The least clearance is required when both the stove and its connector, as well as the wall, have heat shields.

When shields are attached to the stove or chimney connector, they are mounted 1” - 2” (25-51 mm) away from the stove or connector surface on noncombustible spacers. Air flowing between the stove (and/or chimney connector) and nearby shields carries away heat. Do not block the air flow by filling this empty space with any insulating material.

The shiny shield surface facing the heat source must be left unpainted, enabling it to reflect heat back towards the stove or connector and away from the wall.

Clearances may be reduced only by means approved by the regulatory authority, and in accordance with the clearances listed in this manual.

Because of their restricted air flow and heat retention characteristics, specific construction requirements and special clearances apply to installations into alcoves. Refer to the diagrams on Page 10, and contact your Vermont Castings Dealer for details before beginning an alcove installation.

NOTE: ALCOVE INSTALLATION OF THE ENCORE IS NOT PERMITTED IN CANADA.

Stove Heat Shields

The Vermont Castings Encore Rear Heat Shield is one way to reduce the clearance to the rear wall. The rear heat shield can be installed on either rear- or top-vent- ing stoves. However, since the chimney connector also radiates heat toward the wall in top-venting instal- lations, you should use a chimney connector shield whenever you use the rear heat shield on top-venting stoves.

Clearance reductions with the rear heat shield apply only to the wall to the rear in parallel installations. Nei- ther the side clearance requirement nor the clearance requirement in corner installations may be reduced.

Encore Woodburning Stove

Wall Shields

One way to reduce clearances is with a wall shield constructed of 24 gauge or heavier sheet metal, or of another noncombustible material such as 1/2” (13 mm) insulation board or common brick “laid on flat,” with the 3¹⁄₂" (90 mm) side down.

Shields must be spaced out from the combustible surface 1" (25 mm) on noncombustible spacers, as in Figure 13. The spacers should not be directly behind the stove or chimney connector.

Air must be able to flow between the wall and the shield. At least 50% of the bottom 1" (25 mm) of the shield should be open and the shield must be open at the top. Use metal screening, as in Figure 14, to keep stray objects from falling behind the shield.

The shield for a top-exit stove must extend 10" (254 mm) above the top of the stove; for a rear exit configura- tion, the shield must be 36” (914 mm) high. The shield for the chimney connector must be 30” (762 mm) wide, centered behind the pipe; for installations that use an approved prefabricated chimney to pass through the ceil- ing, the chimney connector shield must stop 1” (25 mm) below the ceiling.

Air Flow

Metal

 

Screening

 

Wall Shield

 

Stud Wall

 

Framing

 

Noncombustible

 

Spacer and

Wall

Fasteners

Shield

 

 

Metal Lathe or

Drywall

Noncombustible

 

Spacers

Airflow

 

 

ST248

Fig. 14 Approved wall shield construction.

2000956

11

Image 11
Contents Encore Welcome Table of ContentsSpecifications Encore dimensionsChimney Height InstallationOutside Air Chimney Size What Kind of Chimney to UseMasonry Chimneys Prefabricated ChimneysSingle-wall Chimney Connectors Chimney Connector GuidelinesDouble-wall Chimney Connectors Above the Fireplace Securing the Single-wall Connector to a Masonry ChimneyFreestanding Installations Fireplace InstallationsWall Pass-Throughs Through the FireplaceAn approved wall pass-through for the United States Floor ProtectionReducing Clearances Safely with Shields Floor Protection for Fireplace InstallationsKeep the Stove a Safe Distance From Surrounding Materials Wall Shields Stove Heat ShieldsFireplace and Mantel Trim Shields Chimney Connector Heat ShieldsConstruction Requirements Alcove InstallationsUnprotected Surfaces Protected Surfaces Encore Clearance ChartEncore Clearance Diagrams Wall Shield Requirements for Common Installations Corner Parallel Installations Assembly Damper Directs Air Flow Within the Stove OperationEncore Controls Single Air Control Regulates Heat Output and Burn TimeEncore’s hinged griddle makes it easy to top-load wood Two Ways to Add FuelBurn Only High-Quality Wood Use the Air Control Settings That Work Best for YouInfrared Reflective Glass Panels For Clear Fire Viewing Andirons Help Protect the GlassHigh-Efficiency Wood Burning with Catalytic Combustion Encore Control SettingsStarting and Maintaining a Wood Fire Conditioning Your StoveAsh Disposal Refuel While the Embers Are Still HotIndoor / Outdoor location Draft ManagementSteel Chimney Creosote Flue SizingPipe & Chimney Layout Single ventingMaintenance Check the Operation Primary Air Shutter Installing the GlassAdjust the Damper as Needed Removing the GlassTighten the Damper Handle as Needed How to Adjust the Door LatchesCatalytic Element Inspection and Cleaning When to Suspect a Combustor ProblemRemove the lower fireback through the front door opening Inspecting the CombustorGasket Diameter ...And the Parts it Seals Replace the Stove Gaskets as NeededChimney System Creosote Adjust the Door If NecessaryAnnual Maintenance Permanent Encore GasketsAppendix Catalytic Combustor Encore Woodburning Stove Encore Woodburning Stove Shell Enamel Parts Encore Color Encore Woodburning Stove Encore Woodburning Stove Warranty CFM Corporation