Encore Woodburning Stove
•The fireplace damper must be sealed to prevent room air from escaping up the flue. However, it must be possible to
Chimney | * | |
Connector Shields | ||
| * | |
* Check | Mantel | |
These Clear- | ||
| ||
ances |
| |
| Seal this off | |
ST244 |
|
Fig. 8 In this installation, the chimney connector is attached to the chimney above the fireplace opening.
Through the Fireplace
If your fireplace opening height is at least 26¹⁄₂" (675 mm), you may install an Encore through the opening using a “positive connection” kit, available from your local dealer. These positive connection kits ensure a tight fit between the stove flue collar and the chimney flue. (Fig. 9)
Fireplace installations, whether connected to the flue above or through the fireplace opening, have special clearance requirements to adjacent trim and the mantel. You’ll find the required safe clearances for Encore fire- place installations on Page 12.
Floor protection requirements also apply to fireplace installations. This information is on Page 10.
Wall Pass-Throughs
Whenever possible, design your installation so the con- nector does not pass through a combustible wall. If you are considering a wall
Also, check with the chimney connector manufacturer for any specific requirements.
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall
Flexible Connector
Mantel Shield
Fireplace Adapter
Kit “Positive Con- nection”
ST245
Fig. 9 In this installation, the chimney connector enters the firepalce opening and then connects to the chimney.
In the United States, the National Fire Protection As- sociation (NFPA) has established guidelines for passing chimney connectors through combustible walls. Many building code inspectors follow these guidelines when approving installations.
Figure 10 shows one NFPA-recommended method. All combustible material in the wall is cut away from the single-wall connector to provide the required 12” (305mm) clearance. Any material used to close up the opening must be noncombustible.
Three other methods are also approved by the NFPA:
•Using a section of double-wall chimney with a 9” (229 mm) clearance to combustibles.
•Placing a section of chimney connector inside a ventilated thimble, which in turn is separated from combustibles by 6” (152 mm) of fiberglass insulating material.
•Placing a section of chimney connector inside a section of 9” (230 mm) diameter, solid-insulated, facto- ry-built chimney, with 2” (51 mm) of air space between the chimney section and combustibles.
In Canada, The Canadian Standards Association has established different guidelines. Figure 10 shows one method, in which all combustible material in the wall is cut away to provide the required 18” (457 mm) clear- ance for the connector. The resulting space must re- main empty. A flush-mounted sheet metal cover may be used on one side only. If covers must be used on both sides, each cover must be mounted on noncombustible spacers at least 1” (25 mm) clear of the wall.
8 | 2000956 |