Installation
SAFETY NOTICE: IF YOUR DEFIANT IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. TO REDUCE THE RISK OF FIRE, FOLLOW THE INSTALLATION INSTRUCTIONS. CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
Before you begin an installation, be sure that:
•Your stove and chimney connector will be far enough from combustible material to meet all clearance requirements.
•The floor protector is large enough and is con- structed properly to meet all requirements.
•You have all necessary permits from local authori- ties.
Your local building official is the final authority for approving your installation as safe and determining that it meets local and state codes.
The metal label permanently attached to the back of every Vermont Castings' stove indicates that the stove has been tested to current UL and ULC stan- dards, and gives the name of the testing laboratory. Clearance and installation information also is printed on the label. When the stove is installed according to the information both on the label and in this manual, local authorities usually will accept the label as evidence that the installation meets codes and can be approved.
However, codes vary in different areas. Before
starting the installation, review your plans with the local building authority. Your local dealer can provide any additional information needed.
For any unresolved installation issues, refer to the National Fire Protection Association’s publication ANSI/ NFPA 211 Standard for Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances. For Canada, the equivalent publication is CSA
IMPORTANT: FAILURE TO FOLLOW THESE INSTALLATION INSTRUCTIONS MAY RESULT IN A DANGEROUS SITUATION, INCLUDING A CHIMNEY OR HOUSE FIRE. FOLLOW ALL INSTRUCTIONS EXACTLY, AND DO NOT ALLOW MAKESHIFT COMPROMISES TO ENDANGER PROPERTY AND PERSONAL SAFETY.
Outside Air
In some modern,
When poor draft is caused by a low infiltration rate, opening a ground floor window on the windward side of the house and near the stove will usually alleviate the problem.
A better solution is to install a permanent outside air supply to the stove and/or room. In fact, bringing air for combustion from outside the home directly to the air inlet of the stove is required for new construction in some areas.
Pressure variations within the house do not affect a stove equipped with an outside air supply, and im- proved stove performance often results. An Outside Air Adaptor Kit for the Defiant is available from your local
Vermont Castings dealer.
Chimney Height
Altitude affects chimney performance. When using an 8" oval to 6" flue collar adapter on the Defiant, refer to Figure 1 for suggested chimney heights at various altitudes. Chimney height should be measured from the flue collar to the top of the chimney. The recommended minimum chimney height is 16 feet (5 meters).
| 30 |
|
|
|
|
|
|
| 25 |
|
|
|
|
|
|
Height | 20 |
|
|
|
|
|
|
| 15 |
|
|
|
|
|
|
| 0 | 2000 | 4000 | 6000 | 8000 | 10000 | 12000 |
ST491 |
|
| Altitude |
|
|
| |
|
|
|
|
|
|
Fig. 2 Chimney height requirements with 6” chimney and/or chimney connector.