Vermont Castings Defiant

What Kind of Chimney to Use

You must connect the Defiant to a code-approved masonry chimney with a flue liner, to a relined masonry chimney that meets local codes, or to a prefabricated metal chimney that complies with the requirements for Type HT chimneys in the Standard for Chimneys, Factory-Built, Residential Type and Building Heating Appliance, UL 103. Fig. 2 illustrates the two types. The chimney and chimney connector must be in good condition and kept clean.

If you use an existing masonry chimney, it must be inspected to ensure it is in a safe condition before the stove is installed. Your local professional chimney sweep, building inspector, or fire department official will be able to inspect the chimney or provide a referral to someone who can. See 'Chimney and Fireplace Hazards, in the appendix, for particulars.

A prefabricated double-

wall insulated chimney

A tile-lined masonry chimney

ST241

Fig. 2 Approved chimney types.

The chimney must extend at least 3' (900 mm) above the highest point where it passes through or past a roof, and at least 2' (600 mm) higher than any part of a building within 10' (3 m) horizontally. (Fig. 3)

For proper draft and good performance, any chimney used with a Defiant should extend at least 16 feet (5 m) above the flue collar of the stove.

 

0 TO 10'

 

 

2' Min.

0 TO 10'

 

3'

 

Min.

 

 

 

2' Min.3'

 

 

Min.

 

Reference

 

 

Point

AC617

 

 

Fig. 3

The 2’-3’10’ Chimney Rule.

 

6

 

 

Masonry Chimneys

An inspection of the chimney must confirm that it has a lining. Do not use an unlined chimney. The chimney must have no cracks, loose mortar, other signs of deterioration, or blockage. Repair any defects before using the chimney with your stove.

Seal any unused openings in an existing masonry chimney with masonry to the thickness of the chimney wall, and repair the chimney liner. Openings sealed with pie plates or wallpaper are a hazard and must be sealed with mortar or refractory cement. In a chimney fire, flames and smoke may be forced out of these unused thimbles.

The chimney should be thoroughly cleaned before use.

Anewly-built masonry chimney must conform to the standards of your local building code or, in the absence of a local code, to a recognized national code. Masonry chimneys must be lined, either with code- approved masonry or pre-cast refractory tiles, stainless steel pipe, or a code-approved, “poured-in-place” liner. The chimney’s clean-out door must seal tightly. A loose or leaky clean-out door can weaken chimney draft to the stove, causing performance problems.

Prefabricated Chimneys

A prefabricated metal chimney must be one tested and listed for use with solid-fuel burning appliances to the High-Temperature (H.T.) Chimney Standard UL-103- 1985 (2100° F.) for the United States, and High Temperature (650˚C) Standard ULC S-629 for Canada.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

Chimney Size

The Defiant is approved for venting into a masonry chimney with a nominal flue size of 8" x 8" (200 x 200

mm)or 8" x 12" (200 x 300 mm), and into a round flue with nominal flue size of 8" (200 mm). A Defiant with a 6" (150 mm) flue collar adapter is approved for venting into a masonry chimney with a nominal flue size of 8" X 8" (200 X 200 mm), and into a round flue with nominal flue size of 6" (150 mm).

NOTE: When installed with a 6" flue collar

adapter, the Defiant may not be operated with the front doors open.

Whatever the flue collar size, a Defiant may be vented into larger chimneys as well. However, chim- neys with liners larger than 8" x 12" (200 x 300 mm) may experience rapid cooling of smoke and reduction in draft, especially if the chimneys are located outside the home. These large chimneys may need to be insulated or have their flues relined for proper stove performance.

Image 6
Contents Defiant Welcome Save These Instructions for Future ReferenceTable of Contents Story of the DefiantSpecifications Defiant, ModelInstallation Outside AirChimney Height Prefabricated Chimneys What Kind of Chimney to UseMasonry Chimneys Chimney SizeChimney Connector Guidelines Single-wall Chimney ConnectorsFireplace Installations Securing the Single-wall Connector to a Masonry ChimneyFreestanding Installations Above the FireplaceThrough the Fireplace Wall pass-ThroughsFloor Protection for Fireplace Installation Floor ProtectionKeep the Stove a Safe Distance from Surrounding Materials Safe Ways to Reduce ClearancesWall Shields Defiant Clearance Chart Stove Clearance Unprotected Surfaces Protected SurfacesDefiant Clearance Diagrams Unprotected Surfaces Protected SurfacesRear heat shield installed on the Defiant Stove Stove Heat ShieldsDistance from the Center of the Flue Collar to the Wall Defiant With Rear Heat Shield onlyAssembly Assemble the Removable Insert Handle OperationDefiant Controls Single Air Control Regulates Heat Output and Burn TimeTwo Ways to Add Fuel Damper Directs Air Flow Within the StoveBurn Only High-Quality Wood Infra-Red Reflective Glass Panels For Clear Fire ViewingAndirons Help Protect the Glass Surface Thermometer is a Valuable Guide to OperationUse the Air Control Settings that Work Best for You Defiant Control SettingsHigh-Efficiency Wood Burning With Catalytic Combustion Conditioning Your Stove Starting and Maintaining a Wood FireRefuel While the Embers Are Still Hot Add larger pieces of wood as the fire begins to burnAsh Disposal Indoor/Outdoor Location Masonry ChimneySteel Chimney Flue SizingCreosote Draft TestingSingle Venting FuelNegative Pressure ConclusionMaintenance Keep Your Stove Looking New Working Its BestCheck the Operation Primary Air Shutter Adjust the Damper as NeededHow to Adjust the Door Latches Tighten the Damper Handle as NeededRemoving and Cleaning the Combustor Inspection and CleaningWhen To Suspect a Combustor Problem Catalytic ElementRemove the bricks and the brick retainer Replace the Stove Gaskets as Needed Chimney System Annual MaintenanceAdjust the Door Latch If Necessary Permanent Defiant GasketsFlame Impingement BlockageMasking and Poisoning OverfiringAppendix Chimney and Fireplace Hazards For a fireplaceDefiant Woodburning Stove Defiant Warranty Vermont Castings Majestic Products Company