Trane CAB-PRC001-EN manual Table PD-2. Free Discharge Motor, Group

Page 19

Performance

Hot Water

Data

Coils

 

 

 

 

 

 

Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C) T. All performance measured on high speed tap, zero ESP, and a throwaway filter.

Table PD-2. Free Discharge Motor, Group 1

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

240

(113)

15.9 (4.7)

0.14

1.06

(0.07)

4.8 (14.4)

60

95

65

 

3H

230 ( 108)

19.6 (5.7)

0.18

1.31(0.08)

10.5 (31.4)

60

95

65

 

4H

210 (99)

20.1 (6.0)

0.18

1.34

(0.08)

2.8 (8.4)

60

95

65

3

2H

318

(150)

21.0 (6.2)

0.19

1.40

(0.09)

8.8 (26.3)

70

80

83

 

3H

314

(148)

25.6 (7.5)

0.23

1.70

(0.11)

3.8 (11.3)

85

89

101

 

4H

284

(134)

27.1 (7.9)

0.25

1.81

(0.11)

5.3 (15.7)

85

89

101

4

2H

388

(183)

25.6 (7.5)

0.23

1.71

(0.11)

3.2 (9.5)

95

96

104

 

3H

374

(177)

31.8 (9.3)

0.29

2.12

(0.13)

6.4 (19.0)

100

107

106

 

4H

350

(165)

34.2

(10.0)

0.31

2.28

(0.14)

9.1 (27.3)

100

107

106

6

2H

611

(289)

40.6

(11.9)

0.37

2.70

(0.17)

8.9 (26.5)

110

154

165

 

3H

608

(287)

49.7

(14.6)

0.45

3.31

(0.21)

4.2 (12.6)

125

130

124

 

4H

565

(267)

53.8

(15.8)

0.49

3.59

(0.23)

5.7 (17.0)

125

130

124

8

2H

790

(373)

50.9

(14.9)

0.46

3.39

(0.21)

4.0 (11.9)

135

150

159

 

3H

731

(345)

61.6

(18.1)

0.56

4.11

(0.26)

6.9 (20.7)

120

123

133

 

4H

688

(325)

66.8

(19.6)

0.61

4.45

(0.28)

9.4 (28.1)

120

123

133

10

2H

980

(463)

64.8

(19.0)

0.59

4.32

(0.27)

6.8 (20.4)

205

250

269

 

3H

992

(468)

83.3

(24.4)

0.76

5.55

(0.35)

13.4 (40.2)

225

237

230

 

4H

930

(439)

90.1

(26.4)

0.82

6.00

(0.38)

18.3 (54.8)

225

237

230

12

2H

1110 (524)

75.0

(22.0)

0.68

4.99

(0.32)

9.6 (28.6)

230

246

263

 

3H

1082 (511)

91.5

(26.8)

0.83

6.10

(0.38)

10.5 (31.4)

220

230

239

 

4H

1010 (477)

99.3

(28.5)

0.90

6.48

(0.42)

7.3 (21.8)

220

230

239

Table PD-3. Free Discharge Motor, Group 2

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

211

(100)

14.5 (4.3)

0.13

0.97

(0.06)

4.1 (12.3)

60

95

65

 

3H

201 (95)

17.7 (5.2)

0.16

1.18

(0.07)

8.8 (26.2)

60

95

65

 

4H

188 (89)

18.3 (5.4)

0.17

1.22

(0.08)

2.4 (7.1)

60

95

65

3

2H

280

(132)

19.2 (5.6)

0.17

1.28

(0.08)

7.5 (22.4)

70

80

83

 

3H

277

(131)

23.3 (6.8)

0.21

1.55

(0.10)

3.2 (9.5)

85

89

101

 

4H

256

(121)

24.8 (7.3)

0.23

1.65

(0.10)

4.5 (13.4)

85

89

101

4

2H

349

(165)

23.8 (7.0)

0.22

1.58

(0.10)

2.8 (8.3)

95

96

104

 

3H

338

(159)

29.4 (8.6)

0.27

1.96

(0.12)

5.5 (16.5)

100

107

106

 

4H

320

(151)

31.7 (9.3)

0.29

2.11

(0.13)

7.9 (23.7)

100

107

106

6

2H

544

(257)

37.4

(11.0)

0.34

2.49

(0.16)

7.6 (22.8)

110

154

165

 

3H

541

(255)

45.4

(13.3)

0.41

3.03

(0.19)

3.6 (10.6)

125

130

124

 

4H

510

(241)

49.4

(14.5)

0.45

3.29

(0.21)

4.8 (14.5)

125

130

124

8

2H

706

(331)

47.0

(13.8)

0.43

3.13

(0.20)

3.4 (10.2)

135

150

159

 

3H

659

(311)

56.8

(16.7)

0.52

3.79

(0.24)

5.9 (17.8)

120

123

133

 

4H

627

(296)

61.8

(18.1)

0.56

4.12

(0.26)

8.1 (24.3)

120

123

133

10

2H

879

(415)

60.0

(17.6)

0.55

4.00

(0.25)

5.9 (17.7)

205

250

269

 

3H

886

(420)

76.4

(22.4)

0.69

5.09

(0.32)

11.4 (34.1)

225

237

230

 

4H

840

(397)

82.8

(24.3)

0.75

5.52

(0.35)

15.7 (46.8)

225

237

230

12

2H

996

(470)

69.4

(20.3)

0.63

4.62

(0.29)

8.3 (24.7)

230

246

263

 

3H

976

(461)

84.3

(24.8)

0.77

5.62

(0.35)

9.0 (26.8)

220

230

239

 

4H

921

(435)

91.8

(26.4)

0.83

6.12

(0.39)

10.2 (30.5)

220

230

239

Note:

1.CFM = Cubic feet per minute

2.TMBH = Total capacity (MBH)

3.GPM = Gallons per minute

4.WPD = Water pressure drop (feet of water)

5.Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.

6.Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.

CAB-PRC001-EN

19

Image 19
Contents December Force-Flo Cabinet HeaterIt isn’t just a fan and a coil… Contents Features and Benefits Description ProcedureSelection Model NumberDigit 30 Control Type Digit 27 Main Control ValveDigit 28 Not Used Digit 29 Piping PackagesModel B Vertical Cabinet General Data ConfigurationsUnit Model a Vertical ConcealedModel C Horizontal Concealed Outlet Inlet Model D Horizontal CabinetFresh Air Outlet Model E Horizontal Recessed General Data Unit ConfigurationsModel F Vertical Wall Hung Cabinet Vertical Cabinet Slope Top Model HVertical Recessed Model JModel M Inverted Vertical Cabinet General DataModel N Inverted Vertical Recessed Table GD-2. Cabinet Heater Air Flow Table GD-1. Force-Flo Cabinet Heater General DataElectric Heat Electric HeatPiping Packages Factory-Installed Piping PackagesPiping Package Options General DataSelecting the Correct Modulating Valve Size Coils PerformanceHot Water DataTable PD-3. Free Discharge Motor, Group Table PD-2. Free Discharge Motor, GroupTable PD-4. Free Discharge Motor, Group Table PD-6. High Static Motor, Group Table PD-5. High Static Motor, GroupTable PD-9. Free Discharge Motor, Group Performance Steam DataCoilsTable PD-7. Free Discharge Motor, Group Table PD-8. Free Discharge Motor, GroupTable PD-11. High Static Motor, Group Table PD-10. High Static Motor, GroupTable PD-12. Steam Properties Tracer Controls Manual Fan Mode SwitchControls Control OptionsControls Operation SequenceSequence of Operation Table C-1. Controller Input/Output Summary General Controls InformationTable C-2. Controller Function Summary ZN.010 Zone SensorControls Options Zone Sensor OptionsControl Features Controls FeaturesZN.520 Additional Features Two-Position Control Valves End Device OptionsControl Valve Two-Position Fresh Air Damper Actuator Calculating MFS Electrical DataUnits with Electric Heat Calculating MCARPM Table ED-6. Two-Stage Electric Heat Digit 18 = U Table ED-8. Single Stage, Low kW Electric Heat Digit 18 = Table ED-7. Single-Stage, Max kW Electric Heat Digit 18 = NTable DW-1. Operating Weights lbs. kg Dimensions WeightsTable DW-2. Shipping Weights lbs. kg Concealed DimensionsVertical Concealed Unit Dimensions VerticalVertical Cabinet, Model B Vertical Cabinet Unit DimensionsHorizontal Horizontal Concealed Unit DimensionsHorizontal Concealed, Model C Cabinet Horizontal Cabinet Unit DimensionsHorizontal Cabinet, Model D Recessed Horizontal Recessed Unit DimensionsHorizontal Recessed, Model E Wall Hung Vertical Wall Hung Cabinet Unit DimensionsVertical Wall Hung Cabinet, Model F Vertical Recessed, Model H Vertical Recessed Unit DimensionsSlope Top Vertical Slope Top Unit DimensionsVertical Slope Top, Model J Inverted Vertical Inverted Vertical Cabinet Unit DimensionsInverted Vertical Cabinet, Model M Inverted Vertical Recessed, Model N Inverted Vertical Recessed Unit DimensionsHorizontal Units Inverted Units CoilConnections Coil Connections Vertical UnitsFresh Air Fresh Air Opening Dimensions, Horizontal UnitsOpening Fresh Air Opening Dimensions, Vertical Units Continuous Mortar Ribs TOP and Bottom Wall BoxProjection Panel Dimensions Dimensions Projection PanelProjection Panel Mechanical Specifications Manual Damper Electric Heat CoilFilters Fresh Air DamperMechanical Specifications Options Projection Panels False BacksRecessing Flanges Aluminum Wall BoxesManual Circuit Setter Piping Components Ball ValveAuto Circuit Setter Strainer Control ValveBalance Fitting UnionTrane Company Division of American Standard Inc

CAB-PRC001-EN specifications

The Trane CAB-PRC001-EN is an advanced control system designed to enhance the efficiency and performance of commercial heating, ventilation, and air conditioning (HVAC) systems. This building automation system plays a crucial role in optimizing indoor climate conditions while maximizing energy savings.

One of the standout features of the CAB-PRC001-EN is its capability for real-time monitoring and control. The system integrates seamlessly with various HVAC components, allowing users to adjust settings, schedules, and operational modes from a centralized interface. This flexibility ensures that building managers can respond promptly to changes in occupancy or external weather conditions, optimizing comfort while minimizing energy consumption.

The CAB-PRC001-EN employs a robust set of advanced technologies aimed at enhancing system reliability. Utilizing adaptive control algorithms, it intelligently balances heating and cooling loads across different zones, ensuring a consistent temperature environment throughout the building. The system can quickly adapt to variable load conditions, improving energy efficiency and reducing wear on equipment.

Another defining characteristic is its commitment to user-friendly operation. The intuitive interface utilizes a clear graphical display, making navigation straightforward for users of all skill levels. Furthermore, the system can be accessed remotely through web-enabled devices, providing convenience and flexibility for building managers who are often on the move.

Integration capabilities are another hallmark of the CAB-PRC001-EN. It is designed to work with a multitude of third-party devices and protocols, enabling a comprehensive building management solution. This compatibility allows for smooth communication between different systems, including lighting, security, and fire safety systems, fostering an environment of enhanced operational efficiency.

In addition, the CAB-PRC001-EN supports advanced analytics and reporting features. Users can generate detailed reports on energy usage, system performance, and maintenance needs, enabling informed decision-making that can lead to further energy savings and improved system longevity.

In summary, the Trane CAB-PRC001-EN control system is a cutting-edge solution designed for commercial buildings, offering a combination of real-time monitoring, advanced control technologies, user-friendly interfaces, seamless integration capabilities, and powerful analytics. This makes it an ideal choice for any organization looking to enhance their HVAC operations while promoting sustainability and energy efficiency.