Trane CAB-PRC001-EN Table PD-5. High Static Motor, Group, Table PD-6. High Static Motor, Group

Page 21

Performance

Hot Water

Data

Coils

 

 

 

 

 

 

Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C) T. All performance measured on high speed tap, zero ESP, and a throwaway filter.

Table PD-5. High Static Motor, Group 1

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

 

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

287

(135)

17.9 (5.3)

0.16

1.19

(0.08)

6.0 (17.8)

145

145

145

 

3H

282

(133)

22.9 (6.7)

0.21

1.52

(0.10)

13.8 (41.2)

145

145

145

 

4H

260

(123)

23.9 (7.0)

0.22

1.59

(0.10)

3.8 (11.5)

145

145

145

3

2H

365

(172)

23.0 (6.7)

0.21

1.53

(0.10)

10.3 (30.8)

140

140

140

 

3H

343

(162)

27.3 (8.0)

0.25

1.82

(0.11)

4.3 (12.8)

145

140

135

 

4H

318

(150)

29.7 (8.7)

0.27

1.98

(0.12)

6.2 (18.6)

145

140

135

4

2H

396

(187)

26.0 (7.6)

0.24

1.73

(0.11)

3.3 (9.8)

170

180

170

 

3H

484

(228)

38.6

(11.3)

0.35

2.57

(0.16)

9.1 (27.0)

210

210

210

 

4H

453

(214)

42.2

(12.4)

0.38

2.81

(0.18)

13.4

(39.9)

210

210

210

6

2H

668

(315)

43.1

(12.6)

0.39

2.87

(0.18)

9.9 (29.5)

245

240

240

 

3H

780

(368)

59.5

(17.4)

0.54

3.96

(0.25)

5.9 (17.7)

320

320

320

 

4H

725

(342)

65.6

(19.2)

0.60

4.37

(0.28)

8.2 (24.6)

320

320

320

8

2H

907

(428)

55.7

(16.3)

0.51

3.71

(0.23)

4.7 (14.2)

320

320

320

 

3H

886

(418)

71.2

(20.9)

0.65

4.74

(0.30)

9.1 (27.1)

320

320

320

 

4H

835

(394)

78.3

(22.9)

0.71

5.22

(0.33)

12.7

(37.8)

320

320

320

10

2H

1117 (527)

70.8

(20.7)

0.65

4.71

(0.30)

8.1 (24.1)

415

420

410

 

3H

1230 (580)

97.6

(28.6)

0.89

6.50

(0.41)

18.1

(54.0)

530

530

530

 

4H

1152 (544)

107.1

(31.4)

0.97

7.13

(0.45)

25.3

(75.6)

530

530

530

12

2H

1270 (600)

82.2

(24.1)

0.75

5.48

(0.35)

11.4

(34.0)

490

500

490

 

3H

1350 (637)

108.0

(31.6)

0.98

7.19

(0.45)

14.5

(43.2)

530

530

530

 

4H

1274 (601)

120.0

(35.2)

1.09

7.83

(0.51)

10.5

(31.4)

530

530

530

Table PD-6. High Static Motor, Group 2

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

Unit

 

CFM

TMBH

 

GPM

WPD

115V

230V

277V

Size

Coil

(L/s)

(TkW)

Q/ITD

(L/s)

(kPa)

Watt

Watt

Watt

2

2H

256

(121)

16.6 (4.9)

0.15

1.11

(0.07)

5.2 (15.5)

145

145

145

 

3H

250

(118)

20.9 (6.1)

0.19

1.39

(0.09)

11.8 (35.3)

145

145

145

 

4H

234

(111)

22.0 (6.5)

0.20

1.47

(0.09)

3.3 (9.9)

145

145

145

3

2H

330

(156)

21.5 (6.3)

0.20

1.43

(0.09)

9.2 (27.4)

140

140

140

 

3H

309

(146)

25.3 (7.4)

0.23

1.68

(0.11)

3.7 (11.1)

145

140

135

 

4H

290

(137)

27.6 (8.1)

0.25

1.84

(0.12)

5.4 (16.3)

145

140

135

4

2H

367

(173)

24.6 (7.2)

0.22

1.64

(0.10)

3.0 (8.9)

170

180

170

 

3H

440

(208)

36.0

(10.5)

0.33

2.40

(0.15)

8.0 (23.8)

210

210

210

 

4H

416

(196)

39.5

(11.6)

0.36

2.63

(0.17)

11.8

(35.3)

210

210

210

6

2H

610

(288)

40.5

(11.9)

0.37

2.70

(0.17)

8.8 (26.4)

245

240

240

 

3H

704

(332)

55.3

(16.2)

0.50

3.68

(0.23)

5.2 (15.4)

320

320

320

 

4H

662

(312)

61.1

(17.9)

0.56

4.07

(0.26)

7.2 (21.5)

320

320

320

8

2H

834

(394)

52.7

(15.5)

0.48

3.51

(0.22)

4.3 (12.7)

320

320

320

 

3H

815

(385)

66.9

(19.6)

0.61

4.46

(0.28)

8.1 (24.1)

320

320

320

 

4H

775

(366)

73.7

(21.6)

0.67

4.91

(0.31)

11.3

(33.8)

320

320

320

10

2H

1029 (486)

67.0

(19.6)

0.61

4.46

(0.28)

7.3 (21.8)

415

420

410

 

3H

1117 (527)

91.0

(26.7)

0.83

6.06

(0.38)

15.9

(47.4)

530

530

530

 

4H

1057 (499)

100.0

(29.3)

0.91

6.66

(0.42)

22.3

(66.6)

530

530

530

12

2H

1175 (554)

78.0

(22.8)

0.71

5.19

(0.33)

10.3

(30.8)

490

500

490

 

3H

1242 (586)

101.5

(29.8)

0.92

6.77

(0.43)

12.8

(38.4)

530

530

530

 

4H

1181 (557)

113.0

(33.1)

1.03

7.53

(0.47)

14.9

(44.6)

530

530

530

Note:

1.CFM = Cubic feet per minute

2.TMBH = Total capacity (MBH)

3.GPM = Gallons per minute

4.WPD = Water pressure drop (feet of water)

5.Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.

6.Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.

7.High static motors need the appropriate length of duct to prevent poor acoustical applications.

CAB-PRC001-EN

21

Image 21
Contents December Force-Flo Cabinet HeaterIt isn’t just a fan and a coil… Contents Features and Benefits Selection ProcedureModel Number DescriptionDigit 28 Not Used Digit 27 Main Control ValveDigit 29 Piping Packages Digit 30 Control TypeUnit General Data ConfigurationsModel a Vertical Concealed Model B Vertical CabinetModel C Horizontal Concealed Model D Horizontal Cabinet Outlet InletFresh Air Outlet General Data Unit Configurations Model E Horizontal RecessedModel F Vertical Wall Hung Cabinet Vertical Recessed Model HModel J Vertical Cabinet Slope TopGeneral Data Model M Inverted Vertical CabinetModel N Inverted Vertical Recessed Table GD-2. Cabinet Heater Air Flow Table GD-1. Force-Flo Cabinet Heater General DataElectric Heat Electric HeatPiping Packages Factory-Installed Piping PackagesPiping Package Options General DataSelecting the Correct Modulating Valve Size Hot Water PerformanceData CoilsTable PD-3. Free Discharge Motor, Group Table PD-2. Free Discharge Motor, GroupTable PD-4. Free Discharge Motor, Group Table PD-6. High Static Motor, Group Table PD-5. High Static Motor, GroupTable PD-7. Free Discharge Motor, Group Performance Steam DataCoilsTable PD-8. Free Discharge Motor, Group Table PD-9. Free Discharge Motor, GroupTable PD-10. High Static Motor, Group Table PD-11. High Static Motor, GroupTable PD-12. Steam Properties Controls Manual Fan Mode SwitchControl Options Tracer ControlsSequence Controls OperationSequence of Operation General Controls Information Table C-1. Controller Input/Output SummaryTable C-2. Controller Function Summary Controls Options Zone SensorZone Sensor Options ZN.010Controls Features Control FeaturesZN.520 Additional Features End Device Options Two-Position Control ValvesControl Valve Two-Position Fresh Air Damper Actuator Units with Electric Heat Electrical DataCalculating MCA Calculating MFSRPM Table ED-6. Two-Stage Electric Heat Digit 18 = U Table ED-8. Single Stage, Low kW Electric Heat Digit 18 = Table ED-7. Single-Stage, Max kW Electric Heat Digit 18 = NDimensions Weights Table DW-1. Operating Weights lbs. kgTable DW-2. Shipping Weights lbs. kg Vertical Concealed Unit Dimensions DimensionsVertical ConcealedVertical Cabinet, Model B Vertical Cabinet Unit DimensionsHorizontal Concealed Unit Dimensions HorizontalHorizontal Concealed, Model C Horizontal Cabinet Unit Dimensions CabinetHorizontal Cabinet, Model D Horizontal Recessed Unit Dimensions RecessedHorizontal Recessed, Model E Vertical Wall Hung Cabinet Unit Dimensions Wall HungVertical Wall Hung Cabinet, Model F Vertical Recessed, Model H Vertical Recessed Unit DimensionsVertical Slope Top Unit Dimensions Slope TopVertical Slope Top, Model J Inverted Vertical Cabinet Unit Dimensions Inverted VerticalInverted Vertical Cabinet, Model M Inverted Vertical Recessed, Model N Inverted Vertical Recessed Unit DimensionsConnections CoilCoil Connections Vertical Units Horizontal Units Inverted UnitsFresh Air Opening Dimensions, Horizontal Units Fresh AirOpening Fresh Air Opening Dimensions, Vertical Units Continuous Mortar Ribs TOP and Bottom Wall BoxDimensions Projection Panel Projection Panel DimensionsProjection Panel Mechanical Specifications Filters Electric Heat CoilFresh Air Damper Manual DamperMechanical Specifications Options Recessing Flanges False BacksAluminum Wall Boxes Projection PanelsPiping Components Ball Valve Manual Circuit SetterAuto Circuit Setter Balance Fitting Control ValveUnion StrainerTrane Company Division of American Standard Inc

CAB-PRC001-EN specifications

The Trane CAB-PRC001-EN is an advanced control system designed to enhance the efficiency and performance of commercial heating, ventilation, and air conditioning (HVAC) systems. This building automation system plays a crucial role in optimizing indoor climate conditions while maximizing energy savings.

One of the standout features of the CAB-PRC001-EN is its capability for real-time monitoring and control. The system integrates seamlessly with various HVAC components, allowing users to adjust settings, schedules, and operational modes from a centralized interface. This flexibility ensures that building managers can respond promptly to changes in occupancy or external weather conditions, optimizing comfort while minimizing energy consumption.

The CAB-PRC001-EN employs a robust set of advanced technologies aimed at enhancing system reliability. Utilizing adaptive control algorithms, it intelligently balances heating and cooling loads across different zones, ensuring a consistent temperature environment throughout the building. The system can quickly adapt to variable load conditions, improving energy efficiency and reducing wear on equipment.

Another defining characteristic is its commitment to user-friendly operation. The intuitive interface utilizes a clear graphical display, making navigation straightforward for users of all skill levels. Furthermore, the system can be accessed remotely through web-enabled devices, providing convenience and flexibility for building managers who are often on the move.

Integration capabilities are another hallmark of the CAB-PRC001-EN. It is designed to work with a multitude of third-party devices and protocols, enabling a comprehensive building management solution. This compatibility allows for smooth communication between different systems, including lighting, security, and fire safety systems, fostering an environment of enhanced operational efficiency.

In addition, the CAB-PRC001-EN supports advanced analytics and reporting features. Users can generate detailed reports on energy usage, system performance, and maintenance needs, enabling informed decision-making that can lead to further energy savings and improved system longevity.

In summary, the Trane CAB-PRC001-EN control system is a cutting-edge solution designed for commercial buildings, offering a combination of real-time monitoring, advanced control technologies, user-friendly interfaces, seamless integration capabilities, and powerful analytics. This makes it an ideal choice for any organization looking to enhance their HVAC operations while promoting sustainability and energy efficiency.