FRESH AIR FOR COMBUSTION AND VENTILATION

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr

the space can support)

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. =

51.2 or 51,200 (maximum

Btu/Hr the space can support)

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

___________________ Btu/Hr

Gas water heater*

 

___________________ Btu/Hr

Gas furnace

 

 

___________________ Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Other gas appliances*

+ ___________________ Btu/Hr

Total

= ___________________ Btu/Hr

Example: Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

18,000

Btu/Hr

Total

=

 

 

Btu/Hr

58,000

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________

Btu/Hr (maximum the space can support)

_________________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

58,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

6

101823

Image 6
Contents OWNER’S OPERATION AND INSTALLATION MANUAL INFRARED VENT-FREEPROPANE/LP GAS HEATERINFORMATION CONTENTSSAFETY WARNINGSSAFETY INFORMATION WARNINGS ContinuedContinued IDENTIFICATION FEATURESPRODUCT LOCAL CODESVENTILATION FRESH AIRCOMBUSTION Section 5.3, Air for Combustion and VentilationFRESH AIR FOR COMBUSTION AND VENTILATION ContinuedDETERMINING FRESH-AIRFLOW FOR HEATER LOCATION VENTILATION AIR FRESH AIR FOR COMBUSTION AND VENTILATIONContinued Ventilation Air From Inside BuildingVentilated Outlet Attic Air FRESH AIR FOR COMBUSTION AND VENTILATIONContinued OutletINSTALLING TO WALLContinued INSTALLING TO WALL ContinuedTHERMOSTAT SENSING BULB TO WALL INSTALLINGINSTALLING HEATER TO WALL ContinuedMarking Screw Locations INSTALLING TO WALLContinued Attaching Mounting Bracket To WallContinued INSTALLING TO WALLInstalling Bottom Mounting Screws Placing Heater On Mounting BracketCONNECTING TO GASSUPPLY TO GAS CHECKINGCONNECTIONS SUPPLYTO GAS CONNECTINGPRESSURE TESTING HEATER GAS CONNECTIONS SUPPLYFOR YOUR SAFETY READ BEFORE LIGHTING OPERATING HEATERModels VP1600ITA and VP2200ITA Models VP1600ITA and VP2200ITA OPERATING HEATERLIGHTING INSTRUCTIONS ContinuedModels VP1600ITA and VP2200ITA HEATEROPERATING TO SELECT HEATING LEVELTHERMOSTAT OPERATION MANUAL LIGHTING PROCEDURETO TURN OFF GAS TO APPLIANCE OPERATING HEATERModels VP1600D OPERATINGand VP2600D FOR YOUR SAFETY READ BEFORE LIGHTINGModels VP1600D and VP2600D OPERATING HEATERContinued Models VP1600D and VP2600D OPERATING HEATERTO SELECT HEATING LEVEL ContinuedOPERATING HEATER INSPECTING BURNERMANUAL LIGHTING PROCEDURE TO TURN OFF GAS TO APPLIANCEINSPECTING BURNER ContinuedBURNER FLAME PATTERN TROUBLE CLEANINGMAINTENANCE SHOOTINGTROUBLE Cleaning and MainteCleaning and Mainte SHOOTINGsee Cleaning and TROUBLE- SHOOTINGsee Cleaning and see Cleaning andTROUBLE SERVICETECHNICAL SHOOTINGSERVICE PUBLICATIONS SERVICE HINTS SPECIFICATIONSPARTS REPLACEMENTACCESSORIES Parts Under WarrantyModel VP1600ITA ILLUSTRATEDBREAKDOWN PARTSPART PARTS LISTModel VP1600ITA NUMBERPARTS Model VP2200ITAILLUSTRATED BREAKDOWNPARTS LIST Model VP2200ITA098304-01 PARTS Model VP1600DILLUSTRATED BREAKDOWNPARTS LIST Model VP1600D098304-01 PARTS Model VP2600DILLUSTRATED BREAKDOWNPARTS LIST Model VP2600D098304-01 WARRANTY INFORMATION LIMITED WARRANTYVANGUARD VENT-FREEPROPANE/LP GAS HEATERS