VENTILATION AIR

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

WARNING

WARNING ICON

G 001

If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide adequate combus- tion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING

WARNING ICON

G 001

 

 

Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

12"

Figure 2 - Ventilation Air from Inside Building

Continued

101823

7

Image 7
Contents INFRARED VENT-FREEPROPANE/LP GAS HEATER OWNER’S OPERATION AND INSTALLATION MANUALWARNINGS CONTENTSSAFETY INFORMATIONWARNINGS Continued SAFETY INFORMATIONContinued LOCAL CODES FEATURESPRODUCT IDENTIFICATIONSection 5.3, Air for Combustion and Ventilation FRESH AIRCOMBUSTION VENTILATIONContinued FRESH AIR FOR COMBUSTION AND VENTILATIONDETERMINING FRESH-AIRFLOW FOR HEATER LOCATION Ventilation Air From Inside Building FRESH AIR FOR COMBUSTION AND VENTILATIONContinued VENTILATION AIROutlet FRESH AIR FOR COMBUSTION AND VENTILATIONContinued Ventilated Outlet Attic AirTO WALL INSTALLINGContinued Continued INSTALLING TO WALLTHERMOSTAT SENSING BULB Continued INSTALLINGINSTALLING HEATER TO WALL TO WALLAttaching Mounting Bracket To Wall INSTALLING TO WALLContinued Marking Screw LocationsPlacing Heater On Mounting Bracket INSTALLING TO WALLInstalling Bottom Mounting Screws ContinuedTO GAS CONNECTINGSUPPLY SUPPLY CHECKINGCONNECTIONS TO GASSUPPLY CONNECTINGPRESSURE TESTING HEATER GAS CONNECTIONS TO GASOPERATING HEATER FOR YOUR SAFETY READ BEFORE LIGHTINGModels VP1600ITA and VP2200ITA Continued OPERATING HEATERLIGHTING INSTRUCTIONS Models VP1600ITA and VP2200ITATO SELECT HEATING LEVEL HEATEROPERATING Models VP1600ITA and VP2200ITAOPERATING HEATER MANUAL LIGHTING PROCEDURETO TURN OFF GAS TO APPLIANCE THERMOSTAT OPERATIONFOR YOUR SAFETY READ BEFORE LIGHTING OPERATINGand VP2600D Models VP1600DOPERATING HEATER Models VP1600D and VP2600DContinued Continued OPERATING HEATERTO SELECT HEATING LEVEL Models VP1600D and VP2600DTO TURN OFF GAS TO APPLIANCE INSPECTING BURNERMANUAL LIGHTING PROCEDURE OPERATING HEATERContinued INSPECTING BURNERBURNER FLAME PATTERN SHOOTING CLEANINGMAINTENANCE TROUBLESHOOTING Cleaning and MainteCleaning and Mainte TROUBLEsee Cleaning and TROUBLE- SHOOTINGsee Cleaning and see Cleaning andSHOOTING SERVICETECHNICAL TROUBLESPECIFICATIONS SERVICE PUBLICATIONS SERVICE HINTSParts Under Warranty REPLACEMENTACCESSORIES PARTSPARTS ILLUSTRATEDBREAKDOWN Model VP1600ITANUMBER PARTS LISTModel VP1600ITA PARTBREAKDOWN Model VP2200ITAILLUSTRATED PARTSModel VP2200ITA PARTS LIST098304-01 BREAKDOWN Model VP1600DILLUSTRATED PARTSModel VP1600D PARTS LIST098304-01 BREAKDOWN Model VP2600DILLUSTRATED PARTSModel VP2600D PARTS LIST098304-01 LIMITED WARRANTY WARRANTY INFORMATIONVANGUARD VENT-FREEPROPANE/LP GAS HEATERS