Vanguard Heating VN12, VN6A Pressure Testing Heater GAS Connections, Manual Shutoff Valve

Page 11

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 11).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 12). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING HEATER GAS CONNECTIONS

1.Open manual shutoff valve (see Figure 11).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 12). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see OPERATING HEATER, pages 12 through 15). Check the rest of the internal joints for leaks.

7.Turn off heater (see TO TURN OFF GAS TO APPLIANCE, page 15).

8.Replace front panel.

Open

Manual

Shutoff

Valve

Closed

Figure 11 - Manual Shutoff Valve

Control Valve Location

Gas Meter

Manual

Shutoff

Valve

Figure 12 - Checking Gas Joints

11

Image 11
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualContents Safety Information Safety Information Piezo Ignition System Local Codes Unpacking Product FeaturesSafety Device Product IdentificationLocating Heater Installation ItemsCheck GAS Type Marking Screw Locations Installing Heater to WallCeiling FloorFolding Anchor Installing Two Mounting ScrewsPlacing Heater On Mounting Screws Connecting to GAS Supply Checking GAS Connections Pressure Testing GAS Supply Piping SystemManual Shutoff Valve Pressure Testing Heater GAS ConnectionsLighting Instructions For Your Safety Read Before LightingOperating Heater Pilot Burner Patterns To Select Heating LevelPilot Flame Pattern Manual Lighting ProcedureInspecting Burner To Turn OFF GAS to ApplianceCabinet Cleaning and MaintenanceBurner Flame Pattern ODS/PILOT and Burner OrificeObserved Possible Problem Cause Remedy Trouble ShootingCleaning Observed Possible Problem Cause Remedy VN12 Technical ServiceIng statement at TopValve GA5010 Parts Under WarrantyParts Not Under Warranty Manual ShutoffVN6A Parts ListVN12 Illustrated Parts BreakdownLimited Warranty Vanguard VENT-FREE Residential GAS Heaters Warranty Information