Liebert Comprehensive Guide to Wiring and Connections for the AC4 Controller

Page 20

Wiring and Connections

3.2.3 Setting the Digital Output Jumpers

Digital output jumpers (four)

Each digital output has an associated jumper to define its operation when power is interrupted. This puts the AC4

in a fail-safe mode and ensures proper functioning when the board has no power.

The AC4 comes from the factory with all digital output jumpers in the OFF position (normally open). The jumper setting for each digital output can be changed to ON (nor- mally closed). The settings are shown in Table 5.

Table 5

Digital output jumper settings

 

 

 

Output status

Setting

(power loss)

OFF

Normally open

 

 

ON

Normally closed

 

 

To change the output jumper setting:

1. Find the respective loss-of-power jumper on the circuit board, as shown above. See Table 1 - Controller board components for more information.

2.Decide whether your configuration requires the jumper to be OFF or ON.

3.Set the jumper as needed:

Set the jumper to OFF by placing the loss-of-power jumper on the middle and top pins.

Set the jumper to ON by placing the black jumper on the middle and bottom pins.

3.3 Connecting Common Alarm Outputs

The common alarm relay, found in the top right corner of the AC4, permits the user to connect auxiliary notification equip- ment, such as lights, horns and sirens, to the AC4. To determine the proper wire size, see Table 4 - Wiring specifications.

There are two connectors for the common alarm output. However, the connectors are not individual relay outputs. The connectors should be treated as a double-pole, double-throw (DPDT) relay.

The common alarm relay is energized whenever an alarm occurs.

To connect an output:

Common alarm outputs

 

1.Turn OFF electrical power to the AC4.

2.If necessary, remove a conduit knockout to permit wire entry into the AC4 enclosure.

3.Bring the wire(s) into the AC4 enclosure through a conduit knockout or access slot.

4.Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.

5. Tighten the screw until it holds the wire snugly.

3.4RS232 Connector

The AC4’s Service Terminal Interface offers full con- figuration and monitoring capability via the RS232 port (see A.2 - Connecting to the Service Termi- nal Interface).

The RS232 port requires a null modem cable. Connect one end of the cable to the AC4’s RS232 port, shown at right, and the other end to the COM1 port of a lap- top computer or video terminal.

Serial interface connector (RS232/ EIA574)

14

Image 20
Contents AC4 MonitoringPage Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Methods of Viewing and Configuring the AC4 Available AlarmsData Logs IntroductionOperation LCD for configurationOutside Enclosure Overview Device RS232 Liebert Himod Typical ConfigurationDevice Liebert Challenger Controller Board Overview Controller board componentsConnector RS232 DIP switchLCD connector 24VAC powerOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Installation Considerations InstallationPacking Contents Unpacking and Preliminary InspectionMounting the Panel Surface-Mounting the AC4Required tools Flush-Mounting the AC4 Connect Power to the AC4 Electrical connections to panelWiring specifications Wiring SpecificationsWiring and Connections Connecting Digital Inputs and Outputs Connecting Liebert Environmental UnitsConnecting Digital Inputs Connecting Digital OutputsConnecting Common Alarm Outputs RS232 ConnectorSetting the Digital Output Jumpers Digital output jumper settingsOverview of Menus Guide to AC4 functionsLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options View Active Alarms Active AlarmsClearing Active Alarms Active AlarmsView Alarm Log Alarm LogAlarm log conditions Alarm LogView Event Log Event LogEvent log conditions Event LogView Input Status Input StatusViewing Additional Input Data Digital input statesView Output Status Output StatusViewing Additional Output Data Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entryLogin Screen System & Control menu Clear Alarms&Logs selectedSetup System menu Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Set Up Alarmable Inputs in Latched or Unlatched Mode Set Up Delay TimeDelay Time Latched / UnlatchedReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Setup System Setup Zones Set Up a ZoneMessage if too few devices entered Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedDefine Operating or Standby Mode Enable or Disable an Output Device in Alarm StatusConfigure Output for Loss of Power Fail-Safe Set ModeSetup System Setup System Info Change PasswordChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults System and Control Options Setup Operation Select Setup Operation Setup System MenuSetup Operation Menu Default settings operation featuresTurn Automatic Sequencing On or Off Activate / DeactivateSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalTurn Standby Testing On or Off Change Standby TestingSpecify Failed Standby Response Failed Standby responseSpecify Hold Delay Time Hold Delay TimeSetup Operation Menu Restart Delay TimeOverride Output Clear Alarms & Logs Clear Active AlarmsClear the Alarm Log Clear the Event LogAC4 Specifications SpecificationsAppendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Properties Setup Ascii SetupSettings tab Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htSilence Alarm and Backup Log Files Setup Menu OverviewView Status Overview Main Menu For sample screens, seeMain Menu View Status MenusMain Menu View Active Alarms View Active AlarmsView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Back Up Alarm Log File Backup Log Files Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Setup MenuLogin Menu Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateAuto Sequencing Setup OperationSetup Operation Auto Sequencing Standby Testing Setup Operation Standby TestingHold Delay Setup Operation Failed StandbySetup Operation Hold Delay Failed StandbyRestart Delay Setup Operation Restart DelayOverride Output Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Page Technical Support/Service Company Behind the ProductsLocations Asia 23F, Allied Kajima Bldg
Related manuals
Manual 4 pages 49.53 Kb

AC4 specifications

The Liebert AC4 is a highly advanced cooling solution designed for critical environments, such as data centers and telecommunications facilities. As data demands rise and IT equipment generates significant heat, an effective cooling system is paramount to maintaining optimal performance and reliability. The Liebert AC4 stands out in this space, offering a blend of efficiency, flexibility, and innovative technology.

One of the main features of the Liebert AC4 is its adaptability to various configurations and applications. It can be deployed in both hot aisle and cold aisle containment setups, making it versatile for different data center designs. This flexibility allows facilities to implement cooling strategies that align perfectly with their specific layouts and operational requirements.

The Liebert AC4 employs cutting-edge, variable-speed fans that enhance energy efficiency. These fans adjust their speed according to the cooling load, ensuring that the system operates at peak efficiency while significantly reducing energy consumption. This feature is essential in critical environments, where minimizing operational costs is often as important as maintaining optimal temperatures.

In addition to energy-efficient cooling, the Liebert AC4 integrates advanced monitoring and control technologies. With built-in intelligence and compatibility with the Liebert SiteScan monitoring system, users can ensure real-time visibility into their cooling operations. This monitoring capability enables data center managers to make informed decisions and swiftly address any cooling anomalies, minimizing the risk of overheating and downtime.

Furthermore, the system is designed to be easy to install and maintain, reducing downtime during setup and upkeep. The modular design allows for scalability, enabling organizations to expand their cooling capabilities as their needs grow.

The Liebert AC4 also features a robust construction that enhances reliability and durability, making it an ideal choice for environments where equipment uptime is critical. Its streamlined design not only optimizes airflow and cooling distribution but also contributes to aesthetic considerations in professional settings.

In conclusion, the Liebert AC4 combines efficiency, versatility, and advanced technologies to deliver a reliable cooling solution for modern data centers and critical facilities. Its variable-speed fans, flexible configurations, and advanced monitoring capabilities position it as a leader in the competitive field of cooling solutions, ensuring that critical equipment remains operational and efficient. Organizations looking to enhance their cooling strategies will find the Liebert AC4 to be an invaluable asset in today’s fast-paced digital landscape.