Liebert AC4 Login Screen, System & Control menu Clear Alarms&Logs selected, Setup System menu

Page 33

System and Control Options

Figure 9 shows the main options available from the System & Control menu.

Figure 9 Menu overview - System and Control menu

Opening Screen

LIEBERT AC4

DD-MON-YY HR:MM:SS

VX.XXX.X

PRESS =STATUS/SETUP

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑↓ =NEXT

=SELECT

 

 

Login Screen

 

 

LOGIN

 

 

 

AAAA

 

 

 

↑↓ =SELECT =NEXT/END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System & Control menu

System & Control menu

Setup System selected

Override Output selected

System & Control menu Clear Alarms&Logs selected

>SETUP SYSTEM OVERRIDE OUTPUT CLEAR ALARMS & LOGS

Setup System menu

SETUP INPUTS

See

SETUP COMMON ALARM

Section

SETUP ZONES

7.2

SETUP OUTPUTS

 

SETUP SYSTEM INFO

 

SETUP OPERATION

 

 

 

SETUP SYSTEM

>OVERRIDE OUTPUT CLEAR ALARMS & LOGS

Select Output

OVERRIDE OUTPUT

>DEVICE_1 AUTO DEVICE_2 AUTO DEVICE_3 AUTO DEVICE_4 FORCE ON

See Section 7.9

SETUP SYSTEM

OVERRIDE OUTPUT

> CLEAR ALARMS & LOGS

Clear Alarms/Logs menu

CLEAR ACTIVE ALARMS

See

CLEAR ALARM LOG

Section

CLEAR EVENT LOG

7.10

 

 

 

 

 

 

 

 

 

 

Override Output

SELECT DEVICE_1

FORCE ON

Setup System options

 

 

 

 

 

 

 

 

 

 

 

 

CLEAR ACTIVE ALARMS

 

 

CLEAR ALARM LOG

ARE YOU SURE? N

 

 

ARE YOU SURE? N

 

 

 

 

 

 

 

 

 

 

 

 

CLEAR EVENT LOG

ARE YOU SURE? N

Setup Inputs

SELECT INPUT

>DEVICE_1 NO-AL-NLDEVICE_2 NO-AL-NL DEVICE_3 NO-AL-NL DEVICE_4 NO-EV-NL

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

LATCHED: N

DELAY: 00:01

See Section 7.3

Setup Common Alarm

RESET COMMON ALARM

See

WITH SILENCE? N

Section

 

7.4

 

 

Setup Zones

SETUP ZONES

ZONE 1 2

ZONE 2 2

#DEVICES IN ZONE ZONE 1 2

See Section 7.5

Setup Outputs

SELECT OUTPUT

>DEVICE_1 NO-OP-EDEVICE_2 NO-ST-E DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D

SETUP DEVICE_1

NORM OPEN/CLOSE: NO

MODE: OPERATING

IN ALARM: ENABLE

See Section 7.6

Setup System Info

CHANGE PASSWORD

SET DATE & TIME

SETUP SITE ID

FACTORY DEFAULTS

See Section 7.7

Setup Operation

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N

HOLD DELAY

:

10:00

RESTART

:

00:06

See Section 7.8

Setup System Info options

Change Password

CHANGE PASSWORD

AAAA

See Section 7.7.1

Set Date & Time

SET DATE & TIME DAYLIGHT SVG TIME: Y

18-MAY-02 10:56:30

See Section 7.7.2

Setup Site ID

SETUP SITE ID

See Section 7.7.3

Factory Defaults

RESTORE ALL DEFAULTS ARE YOU SURE? N

See Section 7.7.5

27

Image 33
Contents Monitoring AC4Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Available Alarms Methods of Viewing and Configuring the AC4Data Logs IntroductionLCD for configuration Outside Enclosure OverviewOperation Typical Configuration Device Liebert ChallengerDevice RS232 Liebert Himod Controller board components Controller Board OverviewDIP switch Connector RS232LCD connector 24VAC powerLED Indicators LED indicators summaryOutput LEDs Status LEDs Input LEDs Typical Sequence Installation Installation ConsiderationsPacking Contents Unpacking and Preliminary InspectionSurface-Mounting the AC4 Required toolsMounting the Panel Flush-Mounting the AC4 Electrical connections to panel Connect Power to the AC4Wiring Specifications Wiring and ConnectionsWiring specifications Connecting Liebert Environmental Units Connecting Digital Inputs and OutputsConnecting Digital Inputs Connecting Digital OutputsRS232 Connector Connecting Common Alarm OutputsSetting the Digital Output Jumpers Digital output jumper settingsGuide to AC4 functions Overview of MenusOpening Screen Overview Main Menu OverviewLCD Menu Overview View Status Options Active Alarms View Active AlarmsClearing Active Alarms Active AlarmsAlarm Log View Alarm LogAlarm log conditions Alarm LogEvent Log View Event LogEvent log conditions Event LogInput Status View Input StatusViewing Additional Input Data Digital input statesOutput Status View Output StatusViewing Additional Output Data Digital output statesSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entrySystem & Control menu Clear Alarms&Logs selected Login ScreenSetup System menu Clear Alarms/Logs menuSetup System Setup Inputs Setup System OverviewDefine Input as Alarmable or Event Change Label Name of InputDefine Input as Normally Open or Normally Closed Set Up Delay Time Set Up Alarmable Inputs in Latched or Unlatched ModeDelay Time Latched / UnlatchedSetup System Setup Common Alarm Change to Reset Y or Not Reset NReset Common Alarm Set Up a Zone Setup System Setup ZonesMessage if too few devices entered Message if too many devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsEnable or Disable an Output Device in Alarm Status Define Operating or Standby ModeConfigure Output for Loss of Power Fail-Safe Set ModeChange Password Setup System Setup System InfoChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only System and Control Options Select Setup Operation Setup System Menu Setup OperationSetup Operation Menu Default settings operation featuresActivate / Deactivate Turn Automatic Sequencing On or OffSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalChange Standby Testing Turn Standby Testing On or OffSpecify Failed Standby Response Failed Standby responseHold Delay Time Specify Hold Delay TimeSetup Operation Menu Restart Delay TimeOverride Output Clear Active Alarms Clear Alarms & LogsClear the Alarm Log Clear the Event LogSpecifications AC4 SpecificationsComparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface COM1 Port Setup Create a ConnectionSpecify COM Port Connection Ascii Setup Properties SetupSettings tab Ascii Setup buttonClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceSetup Menu Overview Silence Alarm and Backup Log FilesView Status Overview Main Menu For sample screens, seeView Status Menus Main MenuMain Menu View Active Alarms View Active AlarmsView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBackup Log Files Alarm Log File Back Up Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileSetup Menu Login MenuLogin Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlySetup Operation Setup Operation Auto SequencingAuto Sequencing Setup Operation Standby Testing Standby TestingSetup Operation Failed Standby Hold DelaySetup Operation Hold Delay Failed StandbySetup Operation Restart Delay Restart DelayOverride Output Override OutputClear Alarms & Logs Clear Alarms & Logs Clear Active AlarmsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Page Company Behind the Products Technical Support/ServiceLocations Asia 23F, Allied Kajima Bldg
Related manuals
Manual 4 pages 49.53 Kb

AC4 specifications

The Liebert AC4 is a highly advanced cooling solution designed for critical environments, such as data centers and telecommunications facilities. As data demands rise and IT equipment generates significant heat, an effective cooling system is paramount to maintaining optimal performance and reliability. The Liebert AC4 stands out in this space, offering a blend of efficiency, flexibility, and innovative technology.

One of the main features of the Liebert AC4 is its adaptability to various configurations and applications. It can be deployed in both hot aisle and cold aisle containment setups, making it versatile for different data center designs. This flexibility allows facilities to implement cooling strategies that align perfectly with their specific layouts and operational requirements.

The Liebert AC4 employs cutting-edge, variable-speed fans that enhance energy efficiency. These fans adjust their speed according to the cooling load, ensuring that the system operates at peak efficiency while significantly reducing energy consumption. This feature is essential in critical environments, where minimizing operational costs is often as important as maintaining optimal temperatures.

In addition to energy-efficient cooling, the Liebert AC4 integrates advanced monitoring and control technologies. With built-in intelligence and compatibility with the Liebert SiteScan monitoring system, users can ensure real-time visibility into their cooling operations. This monitoring capability enables data center managers to make informed decisions and swiftly address any cooling anomalies, minimizing the risk of overheating and downtime.

Furthermore, the system is designed to be easy to install and maintain, reducing downtime during setup and upkeep. The modular design allows for scalability, enabling organizations to expand their cooling capabilities as their needs grow.

The Liebert AC4 also features a robust construction that enhances reliability and durability, making it an ideal choice for environments where equipment uptime is critical. Its streamlined design not only optimizes airflow and cooling distribution but also contributes to aesthetic considerations in professional settings.

In conclusion, the Liebert AC4 combines efficiency, versatility, and advanced technologies to deliver a reliable cooling solution for modern data centers and critical facilities. Its variable-speed fans, flexible configurations, and advanced monitoring capabilities position it as a leader in the competitive field of cooling solutions, ensuring that critical equipment remains operational and efficient. Organizations looking to enhance their cooling strategies will find the Liebert AC4 to be an invaluable asset in today’s fast-paced digital landscape.