Liebert AC4 Change Label Name of Input, Define Input as Normally Open or Normally Closed

Page 35

System and Control Options

7.3.1 Change Label (Name of Input)

Each input has a default label (Device_1, Device_2, etc.) that you may change to a more descriptive name for ease in recognizing alarms and events associated with the input. The label may consist of up to eight characters (see Table 12 for valid characters).

The device name assigned through this menu is also displayed for the corresponding output.

Table 14 Input and output labels

Label

 

Applies to:

Device_1

Input 1

 

Output 1

Device_2

Input 2

 

Output 2

Device_3

Input 3

 

Output 3

Device_3

Input 3

 

Output 3

If the input label is changed, the output will change also.

Setup Inputs Menu

SETUP DEVICE_1

> LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓ =NEXT

=SELECT

LATCHED: N

DELAY: 00:01

Change Label

CHANGE LABEL

DEVICE_1

↑↓ =SELECT =NEXT/END

From the Setup Inputs Menu, choose Label for the selected input—Label: Device_1 in the example at right—and press Enter .

To change the input’s label, which may consist of up to eight characters:

Use the arrows ↑↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

7.3.2Define Input as Normally Open or Normally Closed

Each input may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all input points is NO (Normally Open).

If you require an input to be a supervised point, define the input as Normally Closed (NC).

From the Setup Inputs Menu, choose Norm Open/Close, as shown at right, and press Enter .

• To change the normal state for this input, use the arrows ↑↓ to choose NO (Normally Open) or NC (Normally Closed), then press Enter .

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

> NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓ =NEXT

=SELECT

LATCHED: N

DELAY: 00:01

Normally Open / Closed

IS INPUT NORMALLY OPEN OR CLOSED? NO

↑↓ =NO/NC

=END

7.3.3Define Input as Alarmable or Event

Each input may be defined as Alarmable (AL) or as an Event (EV).

For an input defined as alarmable, a change in the status of the device triggers these actions: the LCD flashes, the audible horn sounds, a record is entered in the Alarm Log and the common alarm relay is energized.

For an input defined as an event, a change in the status of the device is recorded in the Event Log.

For both types (alarmable and event), user setup determines output control—whether the device that changed status is disabled or kept in operating mode and whether a standby device is set to operate.

By default, all inputs are set up as AL (Alarmable).

From the Setup Inputs Menu, choose Alarm/Event, as shown at right, and press Enter .

Setup Inputs Menu

SETUP DEVICE_1 LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

> ALARM/EVENT: AL

↑↓ =NEXT

=SELECT

LATCHED: N

DELAY: 00:01

Alarmable / Event

IS INPUT AN ALARM OR EVENT? AL

↑↓ =AL/EV

=END

To change the type of input, use the arrows ↑↓ to choose AL (Alarmable) or EV (Event), then press Enter .

29

Image 35
Contents Monitoring AC4Page Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Setup Menu Appendix a Service Terminal InterfaceFigures Introduction Methods of Viewing and Configuring the AC4Available Alarms Data LogsOperation LCD for configurationOutside Enclosure Overview Device RS232 Liebert Himod Typical ConfigurationDevice Liebert Challenger Controller board components Controller Board Overview24VAC power Connector RS232DIP switch LCD connectorOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Unpacking and Preliminary Inspection Installation ConsiderationsInstallation Packing ContentsMounting the Panel Surface-Mounting the AC4Required tools Flush-Mounting the AC4 Electrical connections to panel Connect Power to the AC4Wiring specifications Wiring SpecificationsWiring and Connections Connecting Digital Outputs Connecting Digital Inputs and OutputsConnecting Liebert Environmental Units Connecting Digital InputsDigital output jumper settings Connecting Common Alarm OutputsRS232 Connector Setting the Digital Output JumpersGuide to AC4 functions Overview of MenusLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options Active Alarms View Active AlarmsActive Alarms Clearing Active AlarmsAlarm Log View Alarm LogAlarm Log Alarm log conditionsEvent Log View Event LogEvent Log Event log conditionsDigital input states View Input StatusInput Status Viewing Additional Input DataDigital output states View Output StatusOutput Status Viewing Additional Output DataSilence Alarm Service Terminal Interface only Silence Alarm & Backup LOG Files Service Terminal InterfaceBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Valid characters for data entry Login Login System and Control OptionsClear Alarms/Logs menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Setup System menuSetup System Setup Inputs Setup System OverviewDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Latched / Unlatched Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Delay TimeReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Message if too many devices entered Setup System Setup ZonesSet Up a Zone Message if too few devices enteredDefine Output as Normally Open or Normally Closed Setup System Setup OutputsSet Mode Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Configure Output for Loss of Power Fail-SafeReset Password to the Factory Default Aaaa Setup System Setup System InfoChange Password Change the PasswordSet Date & Time Setup Site IDSetup Site ID Set Date & Time/Automatic Daylight Saving TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults System and Control Options Default settings operation features Setup OperationSelect Setup Operation Setup System Menu Setup Operation MenuSet Start Time Hour Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Interval & Start Time 1- to 99-Day IntervalFailed Standby response Turn Standby Testing On or OffChange Standby Testing Specify Failed Standby ResponseRestart Delay Time Specify Hold Delay TimeHold Delay Time Setup Operation MenuOverride Output Clear the Event Log Clear Alarms & LogsClear Active Alarms Clear the Alarm LogSpecifications AC4 SpecificationsComparison of Functions LCD and Service Terminal Interface Appendix a Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Ascii Setup button Properties SetupAscii Setup Settings tabClick on the file name for example, AC4.ht Connect to the Service Terminal InterfaceMain Menu For sample screens, see Silence Alarm and Backup Log FilesSetup Menu Overview View Status OverviewMain Menu View Status MenusMain Menu View Active Alarms View Active AlarmsView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSection A.5.1 Section A.5.2 Silence AlarmBack Up Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Backup Log Files Event Log FileLogin Setup MenuLogin Menu See Description Setup MenuSetup Menu Tips on Using the Service Terminal InterfaceSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Set Date & Time Setup Site IDBackup & Upload Configuration File Backup Factory Defaults Backup & Upload Configuration File UploadFirmware Update Firmware Update Service Terminal Interface onlyAuto Sequencing Setup OperationSetup Operation Auto Sequencing Setup Operation Standby Testing Standby TestingFailed Standby Hold DelaySetup Operation Failed Standby Setup Operation Hold DelaySetup Operation Restart Delay Restart DelayOverride Output Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Page Asia 23F, Allied Kajima Bldg Technical Support/ServiceCompany Behind the Products Locations