Liebert AC4 user manual View Output Status, Viewing Additional Output Data, Digital output states

Page 28

View Status Options

5.5View Output Status

The Output Status option allows you to view the current status of all four outputs.

To view the Output Status:

• From the Main Menu, use the arrows ↑↓ to choose View Status, then press Enter ↵.

• From the View Status Menu, use the arrows ↑↓ to choose View Output Status, then press Enter .

5.5.1Output Status

The Output Status screen displays the status of each digital output.

Main Menu

>VIEW STATUS SYSTEM AND CONTROL

↑↓ =NEXT

=SELECT

View Status Menu

VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS

> VIEW OUTPUT STATUS

The following details appear for digital outputs:

the name of the output (for example, DEVICE_1)

the current status (ALARM)—values are updated constantly while being viewed

There are eight possible states for a digital output, as shown in Table 11.

Table 11 Digital output states

State

Description

OPERATING

Device operating, or ON

STANDBY

Device in standby mode

ALARM

Device in alarm

FORCE ON

Device forced ON by operator

FORCE OFF

Device forced OFF by operator

HW FORCE ON

Device forced ON by hardware switch

PENDING

Pending delay timer

NOT USED

Device not used

Viewing Additional Output Data

Output Status

OUTPUT / STATUS

> DEVICE_1

ALARM

DEVICE_2

OPERATING

DEVICE_3

OPERATING

DEVICE_4

OPERATING

All output data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

To view all outputs, use the arrows ↑↓ .

To return to the previous screen, press the ESC key.

22

Image 28
Contents AC4 MonitoringPage Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Methods of Viewing and Configuring the AC4 Available AlarmsData Logs IntroductionOutside Enclosure Overview LCD for configurationOperation Device Liebert Challenger Typical ConfigurationDevice RS232 Liebert Himod Controller Board Overview Controller board componentsConnector RS232 DIP switchLCD connector 24VAC powerLED indicators summary LED IndicatorsOutput LEDs Status LEDs Input LEDs Typical Sequence Installation Considerations InstallationPacking Contents Unpacking and Preliminary InspectionRequired tools Surface-Mounting the AC4Mounting the Panel Flush-Mounting the AC4 Connect Power to the AC4 Electrical connections to panelWiring and Connections Wiring SpecificationsWiring specifications Connecting Digital Inputs and Outputs Connecting Liebert Environmental UnitsConnecting Digital Inputs Connecting Digital OutputsConnecting Common Alarm Outputs RS232 ConnectorSetting the Digital Output Jumpers Digital output jumper settingsOverview of Menus Guide to AC4 functionsMain Menu Overview Opening Screen OverviewLCD Menu Overview View Status Options View Active Alarms Active AlarmsClearing Active Alarms Active Alarms View Alarm Log Alarm Log Alarm log conditions Alarm LogView Event Log Event LogEvent log conditions Event LogView Input Status Input StatusViewing Additional Input Data Digital input statesView Output Status Output StatusViewing Additional Output Data Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface Login LoginSystem and Control Options Valid characters for data entryLogin Screen System & Control menu Clear Alarms&Logs selectedSetup System menu Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsChange Label Name of Input Define Input as Alarmable or EventDefine Input as Normally Open or Normally Closed Set Up Alarmable Inputs in Latched or Unlatched Mode Set Up Delay TimeDelay Time Latched / UnlatchedChange to Reset Y or Not Reset N Setup System Setup Common AlarmReset Common Alarm Setup System Setup Zones Set Up a ZoneMessage if too few devices entered Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedDefine Operating or Standby Mode Enable or Disable an Output Device in Alarm StatusConfigure Output for Loss of Power Fail-Safe Set ModeSetup System Setup System Info Change PasswordChange the Password Reset Password to the Factory Default AaaaSetup Site ID Setup Site IDSet Date & Time/Automatic Daylight Saving Time Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Factory Defaults Factory DefaultsFirmware Update Service Terminal Interface only System and Control Options Setup Operation Select Setup Operation Setup System MenuSetup Operation Menu Default settings operation featuresTurn Automatic Sequencing On or Off Activate / DeactivateSet Interval & Start Time 1- to 99-Day Interval Set Start Time Hour IntervalTurn Standby Testing On or Off Change Standby TestingSpecify Failed Standby Response Failed Standby responseSpecify Hold Delay Time Hold Delay TimeSetup Operation Menu Restart Delay TimeOverride Output Clear Alarms & Logs Clear Active AlarmsClear the Alarm Log Clear the Event LogAC4 Specifications SpecificationsAppendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Create a Connection COM1 Port SetupSpecify COM Port Connection Properties Setup Ascii SetupSettings tab Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htSilence Alarm and Backup Log Files Setup Menu OverviewView Status Overview Main Menu For sample screens, seeMain Menu View Status MenusMain Menu View Active Alarms View Active AlarmsView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Back Up Alarm Log File Backup Log Files Alarm Log FileBackup Log Files Event Log File Back Up Event Log FileLogin Menu Setup MenuLogin Setup Menu Setup MenuTips on Using the Service Terminal Interface See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsSetup System Info Setup System InfoChange Password Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateSetup Operation Auto Sequencing Setup OperationAuto Sequencing Standby Testing Setup Operation Standby TestingHold Delay Setup Operation Failed StandbySetup Operation Hold Delay Failed StandbyRestart Delay Setup Operation Restart DelayOverride Output Override OutputClear Alarms & Logs Clear Active Alarms Clear Alarms & LogsClear Alarms & Logs Clear the Alarm Log Clear Alarms & Logs Clear the Event Log Page Technical Support/Service Company Behind the ProductsLocations Asia 23F, Allied Kajima Bldg