Liebert AC4 user manual Turn Standby Testing On or Off, Specify Failed Standby Response

Page 50

System and Control Options

7.8.2Turn Standby Testing On or Off

Standby testing permits scheduling an automatic operational check of devices in Standby mode.

When this feature is activated (ON), the AC4 tests all devices in Standby mode by putting each device in operating mode for a designated time. You may specify the time of day the testing begins, the dura- tion of the test and the interval between tests. Standby testing is OFF (deactivated) by default.

To change the standby testing settings:

• From the Setup System Operation Menu, use the arrows ↑↓ to choose Standby Testing, then press Enter .

• In the Change Standby Testing screen, press Enter to edit Standby Testing, then use the arrows ↑↓ to choose ON to activate or OFF to deactivate the standby testing feature. Press Enter .

Select the desired interval for how frequently the testing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.

• For each digit, use the arrows ↑↓ to choose a number from 0 to 9, then press Enter to advance to the next digit.

When finished, press Enter to configure the time of day.

Specify the time of day the test should begin in the At 00:00 field. The format is HH:MM for hours and minutes.

Use the arrows ↑↓ to choose from available entries for hours (00-23), then press Enter to advance to minutes.

Setup Operation Menu

AUTO SEQUENCING OFF

> STANDBY TESTING OFF FAILED STANDBY N ↑↓ =NEXT =SELECT

HOLD DELAY

:

10:00

RESTART

:

00:06

Change Standby Testing

>STANDBY TESTING ON EVERY 03 DAYS

AT 00:00 FOR 10 MIN

↑↓ =NEXT

=EDIT

Use the arrows ↑↓ to select minutes (00-59).

When finished, press Enter again.

Specify the duration of the test in minutes—the length of time the standby units will be turned

On—in the For 10 Min field. Use the arrows ↑↓ to choose a number from 0 to 59 minutes. The default is 10 minutes.

When finished, press Enter .

7.8.3Specify Failed Standby Response

The AC4’s Failed Standby feature determines what happens when an operating device fails and a standby device then becomes an operating unit. A subsequent alarm in the newly operating unit (previously the standby device) results in either restarting the previously operating device that was alarmed or not. This feature specifies whether each device remains in its current state or returns to its previous state of operation.

When this feature is activated (Y), each device returns to its previous state, as Table 19 shows: the newly enabled Standby device is dis- abled and the previously operating device is returned to Operating mode. The default setting is N (deactivated), meaning that each device remains in its current state: the Standby device remains enabled and the previously operating unit remains disabled.

Table 19 Failed Standby response

Failed Standby

Previous Standby Device

Previously Operating

Setting

(alarm after being enabled)

Device

 

 

 

Activated (Y)

Disabled

Returned to Operating mode

 

 

 

Deactivated (N)

Remains enabled

Remains disabled

 

 

 

To change the Failed Standby settings:

• From the Setup System Operation Menu, use the arrows ↑↓ to choose Failed Standby, then press Enter .

• In the Change Failed Standby screen, press use the arrows ↑↓ to choose Y to activate or N to deactivate the feature.

• Press Enter .

Setup Operation Menu

AUTO SEQUENCING OFF STANDBY TESTING OFF

> FAILED STANDBY

N

 

 

↑↓ =NEXT

=SELECT

 

 

 

 

 

 

 

HOLD DELAY

: 10:00

 

 

RESTART

 

: 00:06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change Failed Standby

 

> FAILED STANDBY

N

 

 

↑↓ =NEXT

 

=END

 

 

 

 

 

 

 

 

44

Image 50
Contents AC4 MonitoringPage Table of Contents Setup System Setup Common Alarm 7.5 Setup System Setup Zones Appendix a Service Terminal Interface Setup MenuFigures Data Logs Methods of Viewing and Configuring the AC4Available Alarms IntroductionOperation LCD for configurationOutside Enclosure Overview Device RS232 Liebert Himod Typical ConfigurationDevice Liebert Challenger Controller Board Overview Controller board componentsLCD connector Connector RS232DIP switch 24VAC powerOutput LEDs Status LEDs Input LEDs LED IndicatorsLED indicators summary Typical Sequence Packing Contents Installation ConsiderationsInstallation Unpacking and Preliminary InspectionMounting the Panel Surface-Mounting the AC4Required tools Flush-Mounting the AC4 Connect Power to the AC4 Electrical connections to panelWiring specifications Wiring SpecificationsWiring and Connections Connecting Digital Inputs Connecting Digital Inputs and OutputsConnecting Liebert Environmental Units Connecting Digital OutputsSetting the Digital Output Jumpers Connecting Common Alarm OutputsRS232 Connector Digital output jumper settingsOverview of Menus Guide to AC4 functionsLCD Menu Overview Opening Screen OverviewMain Menu Overview View Status Options Clearing Active Alarms View Active AlarmsActive Alarms Active AlarmsAlarm log conditions View Alarm LogAlarm Log Alarm LogEvent log conditions View Event LogEvent Log Event LogViewing Additional Input Data View Input StatusInput Status Digital input statesViewing Additional Output Data View Output StatusOutput Status Digital output statesSilence Alarm & Backup LOG Files Service Terminal Interface Silence Alarm Service Terminal Interface onlyBack Up Log Files Service Terminal Interface only Silence Alarm & Backup Log Files Service Terminal Interface System and Control Options LoginLogin Valid characters for data entrySetup System menu Login ScreenSystem & Control menu Clear Alarms&Logs selected Clear Alarms/Logs menuSetup System Overview Setup System Setup InputsDefine Input as Normally Open or Normally Closed Define Input as Alarmable or EventChange Label Name of Input Delay Time Set Up Alarmable Inputs in Latched or Unlatched ModeSet Up Delay Time Latched / UnlatchedReset Common Alarm Setup System Setup Common AlarmChange to Reset Y or Not Reset N Message if too few devices entered Setup System Setup ZonesSet Up a Zone Message if too many devices enteredSetup System Setup Outputs Define Output as Normally Open or Normally ClosedConfigure Output for Loss of Power Fail-Safe Define Operating or Standby ModeEnable or Disable an Output Device in Alarm Status Set ModeChange the Password Setup System Setup System InfoChange Password Reset Password to the Factory Default AaaaSet Date & Time/Automatic Daylight Saving Time Setup Site IDSetup Site ID Set Date & TimeBackup and Upload Configuration File Back Up the Configuration File Upload the Configuration File Firmware Update Service Terminal Interface only Factory DefaultsFactory Defaults System and Control Options Setup Operation Menu Setup OperationSelect Setup Operation Setup System Menu Default settings operation featuresSet Interval & Start Time 1- to 99-Day Interval Turn Automatic Sequencing On or OffActivate / Deactivate Set Start Time Hour IntervalSpecify Failed Standby Response Turn Standby Testing On or OffChange Standby Testing Failed Standby responseSetup Operation Menu Specify Hold Delay TimeHold Delay Time Restart Delay TimeOverride Output Clear the Alarm Log Clear Alarms & LogsClear Active Alarms Clear the Event LogAC4 Specifications SpecificationsAppendix a Service Terminal Interface Comparison of Functions LCD and Service Terminal InterfaceConnecting to the Service Terminal Interface Specify COM Port Connection COM1 Port SetupCreate a Connection Settings tab Properties SetupAscii Setup Ascii Setup buttonConnect to the Service Terminal Interface Click on the file name for example, AC4.htView Status Overview Silence Alarm and Backup Log FilesSetup Menu Overview Main Menu For sample screens, seeMain Menu View Status MenusMain Menu View Active Alarms View Active AlarmsView Alarm Log View Alarm LogView Event Log View Event LogView Input Status View Input StatusView Output Status View Output StatusSilence Alarm Section A.5.1 Section A.5.2Backup Log Files Event Log File Back Up Alarm Log FileBackup Log Files Alarm Log File Back Up Event Log FileLogin Setup MenuLogin Menu Tips on Using the Service Terminal Interface Setup MenuSetup Menu See DescriptionSetup Inputs Setup InputsSetup Common Alarm Setup Common AlarmSetup Zones Setup ZonesSetup Outputs Setup OutputsChange Password Setup System InfoSetup System Info Setup Site ID Set Date & TimeBackup & Upload Configuration File Backup Backup & Upload Configuration File Upload Factory DefaultsFirmware Update Service Terminal Interface only Firmware UpdateAuto Sequencing Setup OperationSetup Operation Auto Sequencing Standby Testing Setup Operation Standby TestingSetup Operation Hold Delay Hold DelaySetup Operation Failed Standby Failed StandbyRestart Delay Setup Operation Restart DelayOverride Output Override OutputClear Alarms & Logs Clear the Alarm Log Clear Alarms & LogsClear Alarms & Logs Clear Active Alarms Clear Alarms & Logs Clear the Event Log Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg