CLEARANCES TO COMBUSTIBLES
Floor protector must be 3/8” (10mm) thick minimum noncombustible material or equivalent, extending beneath heater and to the front/sides/rear as indicated in the ‘‘Floor Protection’ (See Figure 5).
Minimum clearances to Combustible Materials (in inches and millimeters)
|
| Chimney & |
|
|
|
|
|
|
Installation | Clearance | Connector | A | B | C | D | E | F |
Residential | Standard | Note 1 | 14" | 26" | 18" | 12" | 18" | 10" |
|
|
| (356) | (661) | (457) | (305) | (457) | (254) |
Residential/ | Reduced | Note 2 | 12" | 26" | 16" | 10" | 18" | 8" |
Mobile Home |
|
| (305) | (661) | (406) | (254) | (457) | (203) |
Alcove | Standard | Note 2 & 3 | 12" | 26" | N/A | 10" | 18" | 8" |
|
|
| (305) | (661) | N/A | (254) | (457) | (203) |
FIGURE 5. Clearance to Combustibles (UL AND ULC)
Note 1: 6" (152mm) diameter single wall, minimum 24 MSG black or blued steel connector pipe with a listed
Note 2: 6" (152mm) diameter double wall air cooled connector pipe with listed
Note 3: Alcove specifications: Maximum depth of al- cove shall be no more than 48" (1219mm). For addi- tional alcove information and clearances, refer to clearances to combustibles above.
NOTE: Unit is approved for use with listed double wall
When locating your stove consider safety, conve- nience, traffic flow, and the fact that the stove will need a chimney and chimney connector.
NFPA 211: Use a noncombustible material with 1” (25mm) ventilated air space to reduce clearances. However, this is not to exceed 50% of
NOTE: Must follow NFPA 211 spacing and materials to qualify. It is also subject to local jurisdiction.
AVOID FIRE: Maintain the designated clearances to combustibles. Insulation must not touch the chimney. You must maintain the designated air space clear- ance around the chimney. This space around a chim- ney is necessary to allow natural heat removal from the area. Insulation in this space will cause a heat buildup, which may ignite wood framing.
6