CHIMNEY INSTALLATION

Your unit should be place on a non-combustible floor or 3/8" thick fireproof millboard or equivalent which ex- tends at least 8" from the sides and rear and extends 24" from the front. Leave a minimum clearance of 36" in front of your unit. This is for safe, easy loading and cleaning of your unit.

Also be sure to allow enough room at the rear of the Woodchuck for installation of the circulating blower and filter box.

If using your unit as an add-on, 6" minimum clearance is required from your present furnace.

One very important step in locating your wood/coal fur- nace is how much distance you will be from your new or existing chimney. The unit should be installed as close to the chimney as possible with a minimum of elbows (no more than 2) and no more than 6 feet horizontally with ½" rise per foot.

CHIMNEY INSTALLATION

It is extremely important that your Woodchuck furnace be installed into a CLASS A CHIMNEY ONLY. These chimneys consist of a flue-lined masonry chimney or an approved Class A All Fuel factory built metal type. Any other installation constitutes a fire hazard, as wood and coal burning units have stack temperatures as much as 300° to 1000° and may also deposit creosote

which can ignite and cause severe damage to any chimney. MAKE SURE YOUR WOODCHUCK IS IN-

STALLED INTO A PROPER CHIMNEY.

For maximum safety and efficiency never install the Woodchuck furnace into the same chimney serving an- other appliance.

A typical chimney checklist of requirements is depicted on figure 8.

The Model 526 furnace is equipped with a 6" flue collar having 28 sq. in. of exhaust area. Models 2900 and 4000 have an 8" flue collar having 50 sq. in. of exhaust area. When connecting the furnace to the chimney maintain a chimney flue section giving these minimum areas or larger but not exceeding twice this area. Some common sizes that are acceptable are 8" round, 10" round, or 8"x12" rectangular. All Woodchuck furnaces must be in- stalled into a chimney developing a minimum of .04 W.C. to a maximum of .06 W.C. inches of draft. To maintain this range of draft, a barometric damper should be in- stalled (see pgs. 18-20) on each unit when the draft from the chimney is capable of exceeding .06 W.C. inches of draft.

Insufficient draft can contribute to smoke spillage when the loading door is opened and to rapid creosote accu- mulation. Excessive draft can cause high flue gas tem- perature, loss of overall efficiency and effect the degree of control the operator can exert on the unit.

10’ MIN.

 

3’ MIN.

2’ MIN.

2’ MIN.

 

APPROVED

CHIMNEY

APPROVED CHIMNEY

6" OR 7" PIPE FOR MODEL 526

8" PIPE FOR MODELS 2900/4000

STOVE PIPE

DAMPER

DAMPER

SIDE VIEW

FRONT VIEW

FIGURE 9 CHIMNEY/ROOF CLEARANCE

TYPICAL STOVE PIPE INSTALLATION

17

Image 18
Contents Phone 715/654-5132 Fax 715/654-5513 INSTRUCTION AND PARTS BOOK FORMODELS 07/97Page INTRODUCTION TRANSPORTATION DAMAGESTABLE OF CONTENTS DANGER FURNACE SAFETYDANGER DANGERDISCLAIMER NOTICE SPECIFICATIONSMODEL MODELEFFICIENCY GENERAL INFORMATIONHIGH QUALITY CONSTRUCTION COMFORTADDITION COMFORT AND SAVING FIGURE FIGURECOMMON SENSE OPERATION PROCEDURE IN THE EVENT OF POWER FAILUREOPERATION IF YOU HAVE CHIMNEY FIRESTARTUP OPERATING YOUR WOODCHUCK FURNACEBURNING WOOD IN YOUR WOOD- CHUCK FIGURE 5 WOODCHUCK CONTROLSASH REMOVAL HELPFUL HINTSRECHARGING BURNING COAL IN YOUR WOOD- CHUCKSTARTING A COAL FIRE BANKINGMAINTENANCE OPTIONAL CATALYTIC COMBUSTOR FOR MODELS 2900/4000ASH REMOVAL SOLUTION TROUBLE SHOOTINGPROBLEM POSSIBLE CAUSEPOSSIBLE CAUSE PROBLEMSOLUTION 9. Excessive amounts ofGENERAL REQUIREMENTS INSTALLATIONPLACEMENT AND MINIMUM CLEAR ANCES FIGURE 7 LOCATING THE WOODCHUCKFIGURE 8 TYPICAL CHIMNEY CHECKLIST CHIMNEY INSTALLATION TYPICAL STOVE PIPE INSTALLATIONFIGURE 9 CHIMNEY/ROOF CLEARANCE INSTALLATION OF A BAROMETRIC DRAFT INSTALLING YOUR WOODCHUCKSTOVE PIPE INSTALLATION DAMPERS IN STOVE PIPESAIR DUCT INSTALLATION ADD-ONINSTALLATIONSFIGURE 12 PARALLEL ADD-ONINSTALLATION WOODCHUCK FINAL ASSEMBLYOPTIONAL SHAKER GRATE INSTALLATION FOR MODEL FIGURE 13 CENTRAL ADD-ONINSTALLATIONINSTALL SHAKER GRATE HANDLE MODEL 2900 ONLY FIGURE 14 POOR INSTALLATIONSFIGURE 15 INSTALL SHAKER GRATE HANDLE INSTALL FIREBRICK FIGURE 16 INSTALL OPTIONAL SHAKER GRATE FOR MODELFIGURE 17 INSTALL FIREBRICK FIGURE 19 INSTALL MANUAL DRAFT-MODEL526 ASSEMBLE MANUAL DRAFT MODEL 526 ONLYINSTALL CIRCULATING BLOWER INSTALL FILTER BOXFIGURE 21 INSTALL CIRCULATING BLOWER AND FILTER ELECTRICAL HOOKUP FIGUREFIGURE 22 ELECTRICAL WIRING DIAGRAM KEY NO. PART NO REPAIR PARTSBASIC UNIT FOR MODEL DESCRIPTIONDESCRIPTION BASIC UNIT FOR MODELKEY NO. PART NO KEY NO. PART NODESCRIPTION BASIC UNIT FOR MODELKEY NO. PART NO KEY NO. PART NOFILTER BOX OPTIONAL SHAKER GRATE FOR MODELSHAKER GRATE FOR MODELS 2900/4000 2900/4000CIRCULATING BLOWER COMFORT CONTROL DESCRIPTIONKEY NO. PART NO. DESCRIPTION PERSONAL DATA INFORMATION FOR FUTURE REFERENCE Page LIMITED WARRANTY