PERMANENTLY
SEALED FIREPLACE
OPENING
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile−lined must be lined with B1 vent or a listed insulated flexible metal vent. An exterior tile−lined chimney that is sealed and capped may be lined with a listed uninsulated flexible metal vent. If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting meth- od must be found.
Insulation for the flexible vent pipe must be an encapsu- lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 16.
Common Venting Using Metal−Lined Masonry Chimney
SEALED

Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector

NOTE− Refer to provided venting

tables for installations.

MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT

VENT

CONNECTOR

OTHER

APPLIANCE

INTERIOR TILE−LINED

MASONRY CHIMNEY

NOTE − the chimney must be properly sized per provided venting tables or lined with listed metal lining system.

PERMANENTLY

SEALED FIREPLACE

OPENING

FURNACE

FIGURE 15

DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran- ular insulating material

IMPORTANT

 

 

 

 

MAX. LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

−− SEE NOTE

 

 

 

 

 

 

 

 

 

 

BELOW.

 

 

 

 

 

 

5 ft. (1.5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN. LENGTH −− AS

 

 

 

 

 

EXTERIOR

 

minimum

 

 

 

 

 

 

 

 

SHORT AS PRACTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHIMNEY WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

METAL

 

 

 

 

 

 

 

 

 

 

 

LINER

VENT CONNECTOR

4 in. (102 mm) minimum

FURNACE

OTHER

APPLIANCE

NOTE 1 − Refer to the provided venting tables for installations.

FIGURE 16

SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac- cording to the provided venting tables and the vent pipe manufacturer’s instructions.

A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:

SThe chimney is currently serving at least one drafthood equipped appliance

SThe vent connectors and chimney are sized according to the provided venting tables.

If type B1 double-wall vent is used inside a chimney, no oth- er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as- sembly according to the terms of their respective listings and the vent manufacturer’s instructions.

When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting SL280DFV series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney.

Page 13

Image 13
Contents Table of Contents Installation Instructions SL280DFVTOP View Unit Dimensions − inches mmParts Arrangement SL280DFV Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside NON−COMBUSTIBLE Floor Opening Size Downflow InstallationSL280DFV Unit Setting EquipmentCooling Coil Properly Plenum Sized Floor OpeningFilters Venting Duct SystemTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Carbon Monoxide Poisoning Hazard Gas PipingGas Pipe Capacity − ft3/hr m3/hr MAKE−UP BOX ElectricalNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch 120V Connections System WiringApplications 24V Humidifier ConnectionsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated Control−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling GAS Valve Shown in on Position Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure SettingsHeating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatElectrical SHOCK, Fire Or Explosion Hazard ServiceSL280DFV BURNER, Combustion AIR Inducer Assembly Page Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Volt power−up of the furnace control, Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.