Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV High Altitude

Page 41

High Altitude

The manifold pressure, gas orifice and pressure switch may require adjustment or replacement to ensure proper operation at higher altitudes. Tables 24 through 27 shows

manifold pressure, pressures switch and gas conversion kits at all altitudes.

IMPORTANT

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

TABLE 24

Manifold Pressure Settings

 

 

 

 

Manifold

Manifold

Manifold

Supply Line

Unit

 

Orifice Size

Orifice Size

Pressure in.wg.

Pressure in.wg.

Pressure in.wg.

Pressure

Gas

7501 −

0−4500 ft.

4501−7500 ft.

7501 − 10,000 ft.2

in. w.g.

Input

0 − 7500 ft.

10,000 ft.1

 

 

 

 

 

 

 

 

 

Low

High

Low

High

Low

High

Min

Max

 

 

 

 

 

 

 

 

Fire

Fire

Fire

Fire

Fire

Fire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural

.063

.055

1.7

3.5

1.6

3.4

1.7

3.5

4.5

13.0

070

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

.063

.055

1.7

3.5

1.5

3.0

1.7

3.5

4.5

13.0

090

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

.063

.055

1.7

3.5

1.5

3.2

1.7

3.5

4.5

13.0

110

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

1This is the only permissible derate for these units.

2Natural gas high altitude orifice kit required.

3A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

NOTE − Units may be installed at altitudes up to 4500 ft. above sea level without modifications.

TABLE 25

High Altitude Pressure Switch Kits

 

 

High Altitude

 

Unit

 

Pressure Switch Kit

Input

 

 

 

0 − 4500 ft.

4501 − 7500 ft.

7501 − 10,000 ft.

 

 

 

 

 

070

No Change

No Change

73W36

 

 

 

 

090

No Change

69W56

73W36

 

 

 

 

110

No Change

69W56

73W35

 

 

 

 

TABLE 26

Honeywell Gas Valve Conversion Kits

 

High Altitude

 

 

LP/Propane

 

Natural Gas to

to

 

Natural Gas

 

LP/ Propane Kit

Natural Gas

Unit

Orifice Kit

 

 

Kit

Input

 

 

 

 

 

 

 

 

7501 −

0 − 7500 ft.

7501 −

0 − 7500 ft.

 

10,000 ft.

10,000 ft.

 

 

 

 

 

 

 

 

070

73W37

51W02

73W38

69W79

 

 

 

 

 

090

73W37

51W02

73W38

69W79

 

 

 

 

 

110

73W37

51W02

73W38

69W79

 

 

 

 

 

TABLE 27

White Rodgers Gas Valve Conversion Kits

 

High Altitude

 

 

LP/Propane

 

Natural Gas to

to

 

Natural Gas

 

LP/ Propane Kit

Natural Gas

Unit

Orifice Kit

 

 

Kit

Input

 

 

 

 

 

 

 

 

7501 −

0 − 7500 ft.

7501 −

0 − 7500 ft.

 

10,000 ft.

10,000 ft.

 

 

 

 

 

 

 

 

070

77W05

77W07

77W11

77W09

 

 

 

 

 

090

77W05

77W07

77W11

77W09

 

 

 

 

 

110

77W05

77W07

77W11

77W09

 

 

 

 

 

Page 41

Image 41
Contents Table of Contents Installation Instructions SL280DFVTOP View Unit Dimensions − inches mmParts Arrangement Shipping and Packing List Safety InformationSL280DFV Gas Furnace General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space NON−COMBUSTIBLE Floor Opening Size Downflow InstallationSL280DFV Unit Setting EquipmentCooling Coil Properly Plenum Sized Floor OpeningFilters Venting Duct SystemTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Carbon Monoxide Poisoning Hazard Gas PipingGas Pipe Capacity − ft3/hr m3/hr MAKE−UP BOX ElectricalNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch 120V Connections System WiringApplications 24V Humidifier ConnectionsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated Control−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling GAS Valve Shown in on Position Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure SettingsHeating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatElectrical SHOCK, Fire Or Explosion Hazard ServiceSL280DFV BURNER, Combustion AIR Inducer Assembly Page Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Volt power−up of the furnace control, Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.