Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

E 105

Device communication problem − No other devices on RS BUS (Commu-

Equipment is unable to communicate. Indicates

 

nication

numerous message errors. In most cases errors are

 

system).

related to electrical noise. Make sure high voltage

 

 

power is separated from RSBus. Check for mis−

 

 

wired and/or loose connections between the stat,

 

 

indoor unit and outdoor unit. Check for a high volt-

 

 

age source of noise close to the system. Fault

 

 

clears after communication is restored.

 

 

 

E 110

Low line voltage.

Line Voltage Low (Voltage lower than nameplate

 

 

rating). Check power line voltage and correct. Alarm

 

 

clears 5 seconds after fault recovered.

 

 

 

E 111

Line voltage polarity reversed.

Reverse line power voltage wiring. System resumes

 

 

normal operation 5 seconds after fault recovered.

 

 

 

E 112

Ground not detected

System shuts down. Provide proper earth ground.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 113

High line voltage.

Line Voltage High (Voltage higher than nameplate

 

 

rating). Provide power voltage within proper range.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 114

Line voltage frequency out−of−range.

No 60 Hertz Power. Check voltage and line power

 

 

frequency. Correct voltage and frequency problems.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 115

Low 24V − Control will restart if the error recovers.

24−Volt Power Low (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for additional power−rob-

 

 

bing equipment connected to system. May require

 

 

installation of larger VA transformer to be installed in

 

 

furnace / air handler. Clears after fault recovered.

 

 

 

E 116

High 24V.

24 Volt Power High (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for proper line voltage

 

 

(120V, 240V, etc.) to equipment. Clears when con-

 

 

trol senses proper voltage.

 

 

 

E 117

Poor ground detected (Warning only)

Provide proper grounding for unit. Check for proper

 

 

earth ground to the system. Warning only will clear

 

 

30 seconds after fault recovered.

 

 

 

E 120

Unresponsive device. Communication only.

Usually caused by delay in outdoor unit responding

 

 

to indoor unit poling. Recycle power. Check all wir-

 

 

ing connections. Cleared after unresponsive device

 

 

responds to any inquiry.

 

 

 

E 124

Active communicating thermostat signal missing for more than 3 min-

Equipment lost communication with the thermostat.

 

utes.

Check four wiring connections, ohm wires and cycle

 

 

power at the thermostat. Alert stops all services and

 

 

waits for heartbeat message from thermostat (sub-

 

 

net controller). Cleared after valid thermostat (sub-

 

 

net controller) message is received.

 

 

 

E 125

Control failed self−check, internal error, failed hardware. Will restart if

Hardware problem on the control. Cycle power on

 

error

control. Replace if problem prevents service and is

 

recovers. Integrated control not communicating. Covers hardware errors

persistent. Critical alert. Cleared 300 seconds after

 

(flame sense circuit faults, pin shorts, etc.).

fault recovered.

 

 

 

E 126

Control internal communication problem.

Hardware problem on the control. Cycle power on

 

 

control. Replace if problem prevents service and is

 

 

persistent. Cleared 300 seconds after fault recov-

 

 

ered.

 

 

 

Page 49

Image 49
Contents Table of Contents Installation Instructions SL280DFVTOP View Unit Dimensions − inches mmParts Arrangement SL280DFV Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside NON−COMBUSTIBLE Floor Opening Size Downflow InstallationSL280DFV Unit Setting EquipmentCooling Coil Properly Plenum Sized Floor OpeningFilters Venting Duct SystemTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Carbon Monoxide Poisoning Hazard Gas PipingGas Pipe Capacity − ft3/hr m3/hr MAKE−UP BOX ElectricalNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch 120V Connections System WiringApplications 24V Humidifier ConnectionsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated Control−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling GAS Valve Shown in on Position Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure SettingsHeating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatElectrical SHOCK, Fire Or Explosion Hazard ServiceSL280DFV BURNER, Combustion AIR Inducer Assembly Page Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Volt power−up of the furnace control, Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.