Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV Gas Piping

Page 19

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a venting system commonly run with separate gas ap- pliances, the venting system is likely to be too large to properly vent the remaining attached appliances.

Conduct the following test while each appliance is operat- ing and the other appliances (which are not operating) re- main connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re- quirements section.

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon mon- oxide poisoning or death.

The following steps shall be followed for each ap- pliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1 − Seal any unused openings in the common venting sys- tem.

2 − Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3 − Close all building doors and windows and all doors be- tween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dry- ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper- ate at maximum speed. Do not operate a summer ex- haust fan. Close fireplace dampers.

4 − Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.

5 − After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.

6 − After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp- ers, and any other gas−burning appliances to their pre- vious mode of operation.

7 − If a venting problem is found during any of the preced- ing tests, the common venting system must be modi- fied to correct the problem.

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan- dards of the National Fuel Gas Code ANSI Z223.1.

Gas Piping

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

Gas Supply

1 − This unit is shipped standard for left or right side instal- lation of gas piping. Connect the gas supply to the pip- ing assembly.

2 − When connecting the gas supply piping, consider fac- tors such as length of run, number of fittings, and fur- nace rating to avoid excessive pressure drop. Table 11 lists recommended pipe sizes for typical applications.

3 − The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.

4 − The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the fur- nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang- ers or straps. Install a drip leg inside vertical pipe runs to the unit.

5 − A 1/8" N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See figures 26 and 27.

6 − In some localities, codes may require the installation of a manual main shut-off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro- leum gases.

Page 19

Image 19
Contents Table of Contents Installation Instructions SL280DFVTOP View Unit Dimensions − inches mmParts Arrangement SL280DFV Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside NON−COMBUSTIBLE Floor Opening Size Downflow InstallationProperly Plenum Sized Floor Opening Setting EquipmentSL280DFV Unit Cooling CoilFilters Venting Duct SystemTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Carbon Monoxide Poisoning Hazard Gas PipingGas Pipe Capacity − ft3/hr m3/hr MAKE−UP BOX ElectricalNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch 24V Humidifier Connections System Wiring120V Connections ApplicationsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated Control−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling GAS Valve Shown in on Position Unit Start−UpProper Combustion Gas Pressure AdjustmentHigh Altitude Manifold Pressure SettingsHeating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatElectrical SHOCK, Fire Or Explosion Hazard ServiceSL280DFV BURNER, Combustion AIR Inducer Assembly Page Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Volt power−up of the furnace control, Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.