Lennox International Inc SL280DFV, DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE Non−Communicating

Page 22

2 − Holes are on both sides of the furnace cabinet to facili- tate wiring.

3 − Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

4 − Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.

5 − Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wir- ing diagrams shown in table 13 and figure 24. Use 18−gauge wire or larger that is suitable for Class II ra- ting for thermostat connections.

6 − Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70). A green ground wire is provided in the field make−up box.

NOTE − The SL280DFV furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

7 − One line voltageade terminal is provided on the furnace integrated control. Any electronic air cleaner or other accessory rated up to one amp can be connected to this terminal with the neutral leg of the cir- cuit being connected to the one of the provided neutral terminals. See figure 25 for control configuration. This terminal is energized when the indoor blower is operat- ing.

8 − An unpowered, normally open (dry) set of contacts with a 1/4" spade terminal

er connections and may be connected to 24V or 120V. Any humidifier rated up to one amp can be connected to these terminals. In 120V humidifier applications the neutral leg of the circuit can be connected to one of the provided neutral terminals. This terminal is energized in the heating mode.

9 − Install the room thermostat according to the instruc- tions provided with the thermostat. See table 13 for field wiring connections in varying applications. If the furnace is being matched with a heat pump, refer to the instruction packaged with the dual fuel thermostat.

Thermostat Selection

CAUTION

Field wiring for both communicating and non−com- municating applications is illustrated in diagrams, which begin on Page 23.

Non−Communicating

In non−communicating applications the SL280DFV is de- signed to operate in a SINGLE−STAGE mode or TWO− STAGE mode using a conventional thermostat.

For optimal performance in non−communicating applica- tions, Lennox recommends use of a ComfortSense® 7000 high quality electronic digital thermostat or any other with adjustable settings for 1st stage / 2nd stage on / off differen- tials and adjustable stage timers.

Lennox recommends the following two−stage thermostat settings:

First heat stage differential set to 1/2 to 1 degree F; second heat stage differential set to 1/2 or 1 degree F; second heat stage upstage timer disabled, or set to maximum (1 hr mini- mum).

Communicating

In communicating applications the icomfort Touch® ther- mostat must be used. Refer to the instructions provided with the thermostat for installation, set−up and operation. In communicating system all unused thermostat wire in the wire bundle needs to be terminated inside and out. The ex- tra wires can terminate on the ’C" terminal of the icomfortt communication terminal strip. (RSBus). Using an addition- al wire come off "C" terminal and wire nut all the extra wires together. Termination on the outdoor control must match the indoor control.

Indoor Blower Speeds

Non−Communicating

1 − When the thermostat is set to AN ON," the indoor blower will run continuously at a field selectable per- centage of the second−stage cooling speed when there is no cooling or heating demand. The factory default setting is 38% of cool speed.

2 − When the SL280DFV is running in the heating mode, the indoor blower will run on the heating speed desig- nated by the positions of DIP switches 11, 12 and 13. First stage heating will run at 91% heat speed.

3 − When there is a cooling demand, the indoor blower will run on the cooling speed designated by the positions of DIP switches 5 and 6. First stage cooling will run at 70% cool speed.

Communicating

NOTE − When the SL280DFV is used with icomfort Touch® thermostat, proper indoor blower speed selec- tions are made by the communicating thermostat.

1 − When the thermostat is set to AN ON," the indoor blower will run at setting determined during system configuration.

2 − When there is a heating demand the fan will run on heating speeds for firing rate.

3 − When there is a cooling demand, the fan will run on the first stage and second stage cooling speed set using the icomfort Touch® thermostat in the installer setup mode. The factory default is based upon 400 CFM a ton.

Page 22

Image 22
Contents Installation Instructions SL280DFV Table of ContentsUnit Dimensions − inches mm TOP ViewParts Arrangement SL280DFV Gas Furnace Safety InformationShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Downflow Installation NON−COMBUSTIBLE Floor Opening SizeCooling Coil Setting EquipmentSL280DFV Unit Properly Plenum Sized Floor OpeningFilters Duct System VentingTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Gas Piping Carbon Monoxide Poisoning HazardGas Pipe Capacity − ft3/hr m3/hr Electrical MAKE−UP BOXNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch Applications System Wiring120V Connections 24V Humidifier ConnectionsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram Integrated Control + = Data High Connection − = Data LOW Connection−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling Unit Start−Up GAS Valve Shown in on PositionGas Pressure Adjustment Proper CombustionManifold Pressure Settings High AltitudeOther Unit Adjustments Heating Sequence of OperationHeating Operation with TWO−STAGE Thermostat SECService Electrical SHOCK, Fire Or Explosion HazardSL280DFV BURNER, Combustion AIR Inducer Assembly Page Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Program Unit Capacity/Size Mode Volt power−up of the furnace control,Troubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.