Lennox International Inc SL280DFV installation instructions Duct System, Venting

Page 12

Duct System

Use industry-approved standards (such as those pub- lished by Air Conditioning Contractors of America or Ameri- can Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.

NOTE − Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.8 inches w.c. Higher external static pressures may cause erratic lim- it operation.

Ensure that you have made a seal between the supply air plenum and the furnace and between the furnace and the return air plenum.

Return Air Plenum

Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed. When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pres- sure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be dis- tributed throughout the house by the furnace duct sys- tem.

Venting

A 4−inch diameter flue transition is factory-installed on all models. Modifying or removing the flue transition will cause the unit to operate unsafely and will void the unit certification. The vent connector does not require insula- tion.

The SL280DFV series units are classified as fan−assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1). A fan−assisted Category I furnace is an ap- pliance equipped with an integral mechanical means to ei- ther draw or force combustion products through the com- bustion chamber and/or heat exchanger.

NOTE − Use these instructions as a guide. They do not su- persede local codes. This furnace must be vented accord- ing to all local codes, these installation instructions, and the provided venting tables in these instructions

The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper ap- plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab- sence of local codes, the NFGC serves as the defining doc- ument.

Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.

IMPORTANT

Once the venting system is installed, attach the connected Vent" warning sticker to a visible area of the plenum near the vent pipe. The warning sticker is provided in the bag assembly. Order kit 66W04 for additional stickers.

WARNING

Asphyxiation hazard. The exhaust vent for this fur- nace must be securely connected to the furnace flue transition at all times.

VENT CONNECTION

“DISCONNECTED VENT”

 

WARNING

 

STICKER

FLUE TRANSITION

 

COLLAR

 

FIGURE 14

Use self−drilling sheet metal screws or a mechanical fas- tener to firmly secure the vent pipe to the round collar of the flue transition. If self−drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self−drilling screw through the front and one through each side of the vent pipe and collar. See figure 14.

Masonry chimneys used to vent Category I central fur- naces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 15 and 16 for com- mon venting.

Page 12

Image 12
Contents Installation Instructions SL280DFV Table of ContentsUnit Dimensions − inches mm TOP ViewParts Arrangement Safety Information SL280DFV Gas FurnaceShipping and Packing List Use of Furnace as Construction Heater GeneralCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from Inside Equipment in Confined Space ALL AIR from Outside Equipment in Confined SpaceEquipment Confined Space ALL AIR from Outside Downflow Installation NON−COMBUSTIBLE Floor Opening SizeSetting Equipment SL280DFV UnitCooling Coil Properly Plenum Sized Floor OpeningFilters Duct System VentingTables for installations −1/2 MIN MAX 126 FAN + FAN FAN + NAT 168 Gas Piping Carbon Monoxide Poisoning HazardGas Pipe Capacity − ft3/hr m3/hr Electrical MAKE−UP BOXNon−Communicating Icomfortt Integrated Control Outdoor Unit Icomfort Touch System Wiring 120V ConnectionsApplications 24V Humidifier ConnectionsSL280 Field Wiring Applications With Conventional Thermostat OFF Single Stage Thermostat w Dual fuel capa Bilities SL280DFV Schematic Wiring Diagram Typical SL280DFV Field Wiring Diagram Integrated Control + = Data High Connection − = Data LOW Connection−10% approx OFF On−Board Links Blower Data 1400 Operating System Demand System Response Sequence VAC Room Thermostat Calls for First Stage Cooling Unit Start−Up GAS Valve Shown in on PositionGas Pressure Adjustment Proper CombustionManifold Pressure Settings High AltitudeOther Unit Adjustments Heating Sequence of OperationHeating Operation with TWO−STAGE Thermostat SECService Electrical SHOCK, Fire Or Explosion HazardSL280DFV BURNER, Combustion AIR Inducer Assembly Page Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesEquipment is unable to communicate. Indicates Reconfigure the system. Replace control if heating Low pressure switch failed open To flame failure Limiters to protect the motor from damage caused Sor run cycle, or after power reset Program Unit Capacity/Size Mode Volt power−up of the furnace control,Troubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN
Related manuals
Manual 6 pages 24.8 Kb

DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV specifications

Lennox International Inc has made a significant mark in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. One of its standout products is the SL280DFV model, a high-efficiency gas furnace designed to meet the needs of modern homes.

The SL280DFV boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 80%. This rating indicates that the furnace converts 80% of the fuel it consumes into usable heat, making it a cost-effective choice for homeowners. The high efficiency not only reduces energy bills but also lessens the environmental impact by minimizing greenhouse gas emissions.

One of the key features of the SL280DFV is its two-stage gas valve operation. This technology allows the furnace to operate at two levels of heating output: low stage for milder days and high stage for extremely cold temperatures. This adaptability enhances comfort by maintaining more consistent indoor temperatures while also saving energy when full power is unnecessary.

Another innovative aspect of the SL280DFV is its variable-speed blower motor. This smart technology enables the furnace to adjust airflow based on the heating needs of a home, which promotes quiet operation and improved temperature consistency throughout living spaces.

The SL280DFV is equipped with a durable heat exchanger that is designed to withstand the rigors of daily use, contributing to the unit’s longevity. Additionally, the furnace features a smart ignition system that ensures reliable start-ups, so homeowners can depend on it through the coldest winter nights.

Safety is also a priority in the design of the SL280DFV. It includes various safety features such as a built-in flame sensor and advanced venting system, designed to avert hazardous situations and ensure optimal operation.

Furthermore, Lennox offers convenient installation and maintenance support, making the SL280DFV not only an efficient heating solution but also a practical choice for homeowners. With its blend of advanced technology, high efficiency, and reliability, the Lennox SL280DFV is an appealing option for those looking to upgrade their home’s heating system, promising comfort and peace of mind for many winters to come.