TROUBLE SHOOTING CHART - AUTOMATIC PILOT & VALVE
SYMPTOM | POSSIBLE CAUSES | CORRECTIVE ACTION | ||
Burner won’t | 1. | Pilot flame too large or too small. | 1. | |
turn on |
|
|
| combination control valve. |
| 2. Dirt in pilot orifice. | 2. | Clean pilot orifice with air or solvent, do | |
|
|
|
| not ream. |
| 3. | Defective automatic pilot section in | 3. | Replace entire combination control valve. |
|
| combination control valve. |
|
|
| 4. | Defective thermocouple. | 4. | Replace thermocouple. |
| 5. | Defective combination control valve. | 5. | Replace valve. |
| 6. | Wall thermostat models - manual reset | 6. | Reset switch, see Page 6 and blocked flue |
|
| blocked flue switch tripped. |
| section below. |
|
|
|
|
|
TROUBLE SHOOTING CHART - BLOCKED FLUE SWITCH (FOR USE BY A QUALIFIED SERVICEMAN)
POSSIBLE CAUSES |
| CORRECTIVE ACTION | |
1. | Blockage in | A. Check vent pipe for blockage, such as bird nest, wasp nest, twigs, leaves, etc. | |
| vent pipe | B. Check inside the bottom of the vent pipe to make sure the top of the draft diverter did not | |
|
|
| rip the inner liner causing it to block part of the vent opening. |
|
| C. Check that no insulation from the header plate got caught on top of the draft diverter when | |
|
|
| the heater was inserted into the wall. |
|
| D. Check that the vent cap is properly installed, not shoved too far down on the vent pipe. | |
2. | Burner is | A. Check the manifold pressure. | |
| overfiring | B. Check the rate, NOTE: This appliance was orificed for elevations up to 2,000 feet. When | |
|
|
| installed at higher elevations refer to orifice chart in controls section of instructions for |
|
|
| proper orifice size and |
3. | Improper vent | 3. | Correct vent system. |
| system |
|
|
A. Vent too short | A. The vent should terminate a minimum of 12 feet above the floor. See Figure 2. Also, the | ||
|
|
| top of the vent must be at least 2 foot above any obstacle within a 10 foot radius, including |
|
|
| the roof. See Figure A. |
B. Restriction in | B. All type “B” vents shall extend in a generally vertical direction with offsets not exceeding 45 | ||
| vent system |
| degrees, except that a vent system having not more than one 60 degree offset may be allowed. |
caused by offsets |
| Any angle greater than 45 degrees from the vertical is considered horizontal. The total | |
|
|
| horizontal run of a vent plus the horizontal vent connector shall be not greater than 75 percent |
|
|
| of the vertical height of the vent. |
|
|
| Any offsets used should be as far above the drafthood as possible to allow a venting action to |
|
|
| begin before any restriction is encountered. |
C. Incorrect vent pipe | C. Use listed BW type vent pipe. Do not use tansite or any other type of ceramic pipe for venting. | ||
|
|
| Do not use single wall pipe. When venting into a masonry chimney the chimney must be |
|
|
| properly lined and sized for this gas furnace. The use of type B or flexible chimney liner is |
|
|
| recommended. |
4. | Incorrect header | 4. | The header plate must be |
| plate location |
|
|
5. | Vent pipe not down | 5. | Use a base plate (obtained from the vent pipe manufacturer) on top of our header plate. |
| on the header plate |
| This will lock the vent pipe down and prevent the draft diverter from shoving it up. |
| securely |
|
|
6. | Loose connections | 6. | Check the connection on both the switch and the gas valve. Tighten if necessary. |
| on the vent safety |
|
|
| wiring harness |
|
|
|
|
|
|
DO NOT BYPASS THE BLOCKED FLUE SWITCH
To do so could expose the consumer to property damage, personal injury or possible death.
Page 16