Louisville Tin and Stove W251F, W506, W502F W255F Trouble Shooting Chart Automatic Pilot & Valve

Page 16

TROUBLE SHOOTING CHART - AUTOMATIC PILOT & VALVE

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

Burner won’t

1.

Pilot flame too large or too small.

1.

Re-adjust pilot flame using adjustment on

turn on

 

 

 

combination control valve.

 

2. Dirt in pilot orifice.

2.

Clean pilot orifice with air or solvent, do

 

 

 

 

not ream.

 

3.

Defective automatic pilot section in

3.

Replace entire combination control valve.

 

 

combination control valve.

 

 

 

4.

Defective thermocouple.

4.

Replace thermocouple.

 

5.

Defective combination control valve.

5.

Replace valve.

 

6.

Wall thermostat models - manual reset

6.

Reset switch, see Page 6 and blocked flue

 

 

blocked flue switch tripped.

 

section below.

 

 

 

 

 

TROUBLE SHOOTING CHART - BLOCKED FLUE SWITCH (FOR USE BY A QUALIFIED SERVICEMAN)

POSSIBLE CAUSES

 

CORRECTIVE ACTION

1.

Blockage in

A. Check vent pipe for blockage, such as bird nest, wasp nest, twigs, leaves, etc.

 

vent pipe

B. Check inside the bottom of the vent pipe to make sure the top of the draft diverter did not

 

 

 

rip the inner liner causing it to block part of the vent opening.

 

 

C. Check that no insulation from the header plate got caught on top of the draft diverter when

 

 

 

the heater was inserted into the wall.

 

 

D. Check that the vent cap is properly installed, not shoved too far down on the vent pipe.

2.

Burner is

A. Check the manifold pressure.

 

overfiring

B. Check the rate, NOTE: This appliance was orificed for elevations up to 2,000 feet. When

 

 

 

installed at higher elevations refer to orifice chart in controls section of instructions for

 

 

 

proper orifice size and re-orifice accordingly.

3.

Improper vent

3.

Correct vent system.

 

system

 

 

A. Vent too short

A. The vent should terminate a minimum of 12 feet above the floor. See Figure 2. Also, the

 

 

 

top of the vent must be at least 2 foot above any obstacle within a 10 foot radius, including

 

 

 

the roof. See Figure A.

B. Restriction in

B. All type “B” vents shall extend in a generally vertical direction with offsets not exceeding 45

 

vent system

 

degrees, except that a vent system having not more than one 60 degree offset may be allowed.

caused by offsets

 

Any angle greater than 45 degrees from the vertical is considered horizontal. The total

 

 

 

horizontal run of a vent plus the horizontal vent connector shall be not greater than 75 percent

 

 

 

of the vertical height of the vent.

 

 

 

Any offsets used should be as far above the drafthood as possible to allow a venting action to

 

 

 

begin before any restriction is encountered.

C. Incorrect vent pipe

C. Use listed BW type vent pipe. Do not use tansite or any other type of ceramic pipe for venting.

 

 

 

Do not use single wall pipe. When venting into a masonry chimney the chimney must be

 

 

 

properly lined and sized for this gas furnace. The use of type B or flexible chimney liner is

 

 

 

recommended.

4.

Incorrect header

4.

The header plate must be 65-3/4” above the floor plate. See rough-in instructions.

 

plate location

 

 

5.

Vent pipe not down

5.

Use a base plate (obtained from the vent pipe manufacturer) on top of our header plate.

 

on the header plate

 

This will lock the vent pipe down and prevent the draft diverter from shoving it up.

 

securely

 

 

6.

Loose connections

6.

Check the connection on both the switch and the gas valve. Tighten if necessary.

 

on the vent safety

 

 

 

wiring harness

 

 

 

 

 

 

DO NOT BYPASS THE BLOCKED FLUE SWITCH

To do so could expose the consumer to property damage, personal injury or possible death.

Page 16

Image 16
Contents This Unit is not to be Installed in Mobile Homes NaturalGAS What to do if YOU Smell GASContents Readcarefullybefore InstallingunitSpecifications IntroductionSafety Rules Natural GASCombustion and Ventilation AIR ALL Combustion AIR from Outdoors Through Ventilated AtticVenting Square Hole BTU Size =Figure a ROUGH-IN Dimensions ROUGH-IN InstructionsInstallation Vent Burner ShelfWiring Instructions Gravity Wall Furnace NATWall ThermostatWhat to do if YOU Smell GAS PilotModel W251F, W252F / W351F, W352F / W501F, W502F Pilot Flame Adjustment Burner Flame Adjustment Stainless Steel BurnerPilot Adjustment Maintenance InstructionsModel WFF81-COPTIONAL FAN KIT StepWhite Black White Motor Green Ground Wire Black FAN SwitchTrouble Shooting Chart for qualified serviceman Main Burner Symptom Possible Causes Corrective ActionDo not Bypass the Blocked Flue Switch Trouble Shooting Chart Automatic Pilot & ValvePossible Causes Corrective Action Burner Assembly / Single Wall Furnace Burner AssemblyGravity Wall Furnace List Prices - June Single Wall FurnaceTWO Required August Part Description PriceYour GAS Control and Pilot Light System Tampering is DangerousIf YOU CAN’T Light IT DON’T Fight ITLimited Warranty Table a