Louisville Tin and Stove W501F W252F, W506, W502F W255F, W351F, W355F, W505F W256F, W356F Figure a

Page 6

WARNING: Do not bypass the blocked flue switch. To do so could expose the consumer to property damage, personal injury or possible death.

 

More than 10’

Height above any

 

roof surface

FIGURE A

1 0 ’

within 10’

 

 

horizontally

Ridge

2’ Min.

 

 

3’ Min.

10’ or Less

Chimney

 

 

 

2’ Min.

 

 

ROUGH-IN INSTRUCTIONS NOTE: Maximum wall thickness for a dual wall (W501, W502, W505, W506) installation is 5-3/8”.

STEP 1. Attach the base plate (purchased with the vent pipe) to the header plate using two No. 8 sheet-metal screws through the pre-punched holes. The heater may not vent properly without a base plate to anchor and seal the vent system. See Figure C.

Ridge

3’ Min.

Chimney

Man. Reset

 

Blocked

 

Flue Switch

 

Draft

Reset

Button

 

Installation of B-W Gas Vent for one story buildings or for first floor of multi- story buildings

Ceiling plate spacers to center B-W gas vent in stud space - nail securely at both ends

Plate cut away for full width of stud space to provide ventilation

Studs on 16 inch centers

Sheet metal screw base plate to header

Use manufacturer’s method of fastening pipe to base plate

 

Diverter

Switch/

Relief

Gas

Opening

Control

Combustion

Wire

 

Chamber

 

 

FIGURE B

FIGURE B-1

Header plate of vented wall furnace (also acts as firestop)

FIGURE C

STEP 2. Cut out an opening between the studs of 14-3/8” x 66-1/2” above the floor plate. Embed the rear flange of the channel on top of header into either the drywall or the plastered wall. This provides part of the required fire stop. Square up and nail the header in place with the top front of header located 65-3/4” above floor plate. (See arrow on right side of header and Figure 1, 5A and 5B on Page 7).

STEP 3. Rough in ½” gas supply on center line of left stud either 4” above top of floor plate or 4” to right of left stud through floor plate. See Figure 1 located on Page 7.

Page 6

Image 6
Contents GAS This Unit is not to be Installed in Mobile HomesNatural What to do if YOU Smell GASSpecifications ContentsReadcarefullybefore Installingunit IntroductionSafety Rules Natural GASCombustion and Ventilation AIR ALL Combustion AIR from Outdoors Through Ventilated AtticVenting Square Hole BTU Size =Figure a ROUGH-IN Dimensions ROUGH-IN InstructionsInstallation Vent Burner ShelfWall Wiring Instructions Gravity Wall FurnaceNAT ThermostatWhat to do if YOU Smell GAS PilotModel W251F, W252F / W351F, W352F / W501F, W502F Pilot Adjustment Pilot Flame AdjustmentBurner Flame Adjustment Stainless Steel Burner Maintenance InstructionsModel WFF81-COPTIONAL FAN KIT StepWhite Black White Motor Green Ground Wire Black FAN SwitchTrouble Shooting Chart for qualified serviceman Main Burner Symptom Possible Causes Corrective ActionTrouble Shooting Chart Automatic Pilot & Valve Do not Bypass the Blocked Flue SwitchPossible Causes Corrective Action Gravity Wall Furnace List Prices - June Burner Assembly / Single Wall FurnaceBurner Assembly Single Wall FurnaceTWO Required August Part Description PriceIf YOU CAN’T Light IT Your GAS Control and Pilot Light SystemTampering is Dangerous DON’T Fight ITLimited Warranty Table a