Bryant 355M-40-5, 355M-40-4 IV. Multiventing and Vent Terminations, Condensate Drain General

Page 29

NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.

Roof terminationsÐLocate assembly through roof to ap- propriate height as shown in Fig. 32.

Sidewall terminationsÐLocate assembly through sidewall with rain shield positioned no more than 1-in. from wall as shown in Fig. 33.

5.Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.

6.Check required dimensions as shown in Fig. 32 or 33.

IV. MULTIVENTING AND VENT TERMINATIONS

When 2 or more 355MAV Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 355MAV furnaces. When 2 or more 355MAV furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 36, 37, 38, 39, or 40, but next vent termination must be at least 36 in. away from first 2 terminations. It is important that vent terminations be made as shown to avoid recirculation of flue gases. Dimension "A" in Fig. 36, 37, 38, 39, and 40 represents distance between pipes or rain shields, as touching or 2-in. maximum separation.

CONDENSATE DRAIN

I.GENERAL

Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications.

Condensate trap MUST be used for all applications.

An external trap is not required when connecting the field drain to this condensate trap.

The field drain connection (condensate trap or drain tube coupling) is sized for 1/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube connection.

Drain pipe and fittings must conform to ANSI standards and ASTM D1785 or D2846. CPVC or PVC cement and primer must conform to ASTM D2564 or F493. In Canada, use CSA or ULC certified schedule 40 CPVC or PVC drain pipe, fittings, and cement.

When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid conden- sate spillage, select a pump with an overflow switch.

Furnace condensate is mildly acidic, typically in the pH range of

3.2to 4.5. Due to corrosive nature of this condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.

II.APPLICATION

The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field- supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment's drain.

See Fig. 41 for example of possible field drain attachment using 1/2-in. CPVC or PVC tee for vent and A/C or humidifier drain connection.

32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED

A93058

CAUTION: Unit must not be installed, operated, and then turned and left off in an unoccupied structure during cold weather when temperature drops to 32°F or below unless drain trap and drain line have adequate freeze protection. See Service and Maintenance Procedures for winterizing procedure.

Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.

WARNING: Caution should be taken to prevent drain- ing where slippery conditions may cause personal inju- ries. Excessive condensate draining may cause saturated soil conditions which may result in damage to plants.

III.CONDENSATE DRAIN PROTECTION

Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120v and 40°F self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer's recommenda- tions.

1.Fold heat tape in half and wrap on itself 3 times.

2.Locate heat tape between sides of condensate trap back. (See Fig. 42.)

3.Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig. 42.)

4.Wrap field drain pipe with remaining heat tape, approxi- mately 1 wrap per ft.

5.When using field-supplied heat tape, follow heat tape manufacturer's instructions for all other installation guide- lines.

Ð29Ð

Image 29
Contents ÐMultipoise Orientations Ð1ÐUnit Size DimensionsÐ2Ð Electrostatic Discharge ESD Precautions Safety ConsiderationsMinimum Inches Clearance To Combustible Construction → ÐClearances to CombustiblesApplications General IntroductionII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Ð5ÐCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð Condensate Trap Location III. Downflow ApplicationsCondensate Trap Tubing Ð7ÐIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Condensate Trap Tubing Location General ÐHorizontal Right Tube ConfigurationIII. Furnace Location Relative to Cooling Equipment II. LOW-FIRE only InstallationIV. Hazardous Locations Installation Leveling Legs if DesiredII. Installation in Upflow or Downflow Applications Width Ðopening DimensionsFurnace Plenum Opening Floor Opening Casing ÐDuct Flanges III. Installation in Horizontal ApplicationsÐfilter Information IV. Filter ArrangementBottom Closure Panel → ÐBottom Filter ArrangementVI. GAS Piping WiringÐmaximum Capacity of Pipe Electrical ConnectionsII -V Wiring → ÐHeating and Cooling Application Wiring DiagramÐWiring Diagram Amps Size III. AccessoriesÐelectrical Data Removal of Existing Furnaces from Common Vent Systems Direct VentingNgpic II. COMBUSTION-AIR and Vent PipingCombustion-Air and Vent Pipe Diameter ÐCOMBUSTION-AIR and Vent Pipe Termination ClearancesLocation Clearance FT Or doors which can be opened or Combustion-air openingCombustion-Air and Vent Pipe Attachment Example2001 to Ðmaximum Allowable Pipe Length FT3001 to 4001 to 5000³6001 to 7000³ Ðmaximum Allowable Pipe Length FT7001 to 8000³ 8001 to 9000³III. Concentric Vent and COMBUSTION-AIR COMBUSTION-AIR Intake Housing Plug FittingTermination KIT Installation ÐRoof Termination Preferred Two-Pipe Termination Kit Extended Exposed Sidewall PipesConcentric Vent/Air Termination Kit 042040 042060 042080 060080 060100 060120Condensate Drain General IV. Multiventing and Vent TerminationsII. Application III. Condensate Drain ProtectionÐConcentric Vent and Combustion-Air Roof II. Heating Mode SELF-TEST ModeSequence of Operation HSICooling Mode IV. Emergency Heat ModeVI. Heat Pump Mode III. Heating Modeðtwo StageVII. Continuous FAN Mode ÐWiring Schematic for 2-Speed Cooling ApplicationsDehumidification Mode IX. Bypass Humidifier ModeXI. Zone Mode START-UP Procedures GeneralÐcontinuous FAN CF Airflow Setup Switch Position Ðair Conditioning A/C Airflow Setup Switch PositionSetup Switches SW III. Prime Condensate Trap with WaterÐblower OFF Delay Setup Switch Position Ðsetup Switch DescriptionIV. Purge GAS Lines AdjustmentsSet Gas Input Rate → ÐRedundant Automatic Gas ValveBTU/CU FT 4001 Only875 1.5 5000775 1.5 70018000 825Canada Ðaltitude Derate Multiplier for U.S.ASume the Orifice SIZE. Always Check and Verify Altitude Derate Multiplier Factor for U.S.ACheck Safety Controls Check Primary Limit Control Set Temperature RiseÐgas Rate CU FT/HR Set Thermostat Heat AnticipatorChecklist II. Check Pressure SwitchesCHECKLISTÐSTART-UP ChecklistðinstallationLoad Calculation Combustion and Vent Piping

355M-40-4, 355M-40-5 specifications

The Bryant 355M-40-5 and 355M-40-4 are innovative CNC cylindrical grinders designed to meet the demands of precision machining in various industrial applications. These machines stand out due to their robust construction, advanced technology, and versatile functionalities, which are critical for achieving high-quality grinding results.

One of the main features of the Bryant 355M-40-5 and 355M-40-4 is their precision grinding capability. With high spindle speeds and excellent rigidity, these grinders are engineered to deliver superior surface finishes even on complex geometries. The machines are equipped with advanced dressing systems that ensure consistent wheel profiles, enhancing performance and reducing cycle times.

The Bryant 355M-40-5 differentiates itself through its multi-axis capability, allowing for the grinding of intricate shapes and features without the need for extensive setup changes. Operators can easily program complex grinding sequences through the user-friendly interface, which supports both manual and automated operations. This flexibility is crucial in manufacturing environments that require quick turnaround times and adaptability to various workpieces.

Meanwhile, the Bryant 355M-40-4 focuses on efficiency and productivity, featuring a streamlined design that optimizes workflow. The machine is fitted with high-precision linear guides and ball screws, ensuring smooth and accurate movements during the grinding process. This results in minimal wear and tear, thereby extending the machine's lifespan and maintaining accuracy over time.

Key technologies incorporated into both models include state-of-the-art control systems that enable real-time monitoring and feedback during operations. This feature allows operators to make on-the-fly adjustments to optimize grinding parameters, leading to improved performance and reduced scrap rates. Additionally, the integration of automation solutions, such as robotic loading systems, enhances productivity by minimizing downtime and labor costs.

The Bryant 355M-40-5 and 355M-40-4 are built with durability in mind, utilizing high-strength materials that resist deformation and wear. Their thermal stability ensures consistent performance even under varying operating conditions, making them a reliable choice for high-volume production.

In summary, the Bryant 355M-40-5 and 355M-40-4 models are exemplary CNC cylindrical grinders that combine precision, efficiency, and advanced technology. Their features make them suitable for a wide range of grinding applications, from tool manufacturing to automotive components, ensuring that they remain competitive in the ever-evolving landscape of manufacturing technology.