Bryant 355M-40-4, 355M-40-5 operating instructions Ðelectrical Data, III. Accessories, Amps Size

Page 20

TABLE 4ÐELECTRICAL DATA

UNIT

VOLTSÐ

OPERATING

MAXIMUM

UNIT

MINIMUM

MAXIMUM WIRE

MAXIMUM FUSE OR

HERTZÐ

VOLTAGE RANGE

UNIT

WIRE

SIZE

AMPACITY²

LENGTH (FT)³

CKT BKR AMPS**

PHASE

Maximum*

Minimum*

AMPS

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

042040

115Ð60Ð1

127

104

8.9

12.0

14

31

15

042060

115Ð60Ð1

127

104

8.9

12.0

14

31

15

042080

115Ð60Ð1

127

104

8.9

12.0

14

31

15

060080

115Ð60Ð1

127

104

13.8

17.9

12

32

20

060100

115Ð60Ð1

127

104

13.8

18.1

12

32

20

060120

115Ð60Ð1

127

104

11.6

15.3

12

37

20

 

 

 

 

 

 

 

 

 

* Permissible limits of voltage range at which unit will operate satisfactorily.

²Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier, etc.) full load amps.

³Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay fuse is recommended.

NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.

NOTE: For 2-speed applications, refer to Sequence of Operation section.

III.ACCESSORIES

1.Electronic Air Cleaner (EAC)

The control center EAC terminals are energized with 115v (1.5-amp maximum) during blower operation.

a.Two extension leads are connected to the control center EAC terminals to assist field installation of an EAC. (See Fig. 25.) To use these leads, proceed with the following:

(1.) Strip EAC power lead insulation approximately 1/4 in.

(2.) Insert stripped end into factory-supplied black lead's butt connector and crimp to secure.

(3.) Strip EAC neutral lead insulation approximately 1/4 in.

EAC-ELECTRONIC AIR CLEANER TERMINALS (115-VAC 1 AMP MAX)

(4.) Insert stripped end into factory-supplied white leads's butt connector and crimp to secure.

NOTE: If desired, cut butt connectors off factory leads and strip insulation approximately 1/4 in and use field-supplied wire nuts to connect.

b.An alternate method to attach EAC lead to control center is the following procedure:

(1.) Remove 2 screws securing the control box to furnace blower shelf.

(2.) Remove and discard 2 factory-supplied leads from control center EAC terminals.

(3.) Strip EAC power leads insulation approximately 1/8 in.

NOTE: The control center EAC terminals are sized for 12 gage maximum, solid or stranded wire.

(4.) Route EAC leads through right-hand wire grommet.

HOT SURFACE

IGNITOR CONNECTOR

115-V CONNECTORS

MAIN BLOWER CONTROL WIRE CONNECTOR

TRANSFORMER 24-V CONNECTORS

 

PRESSURE SWITCH

HUM

CONNECTOR

HUM-HUMIDIFIER

 

G

TERMINAL

 

R

(24-VAC 0.5 AMP MAX)

 

Y/Y2

24-V THERMOSTAT

W/W1

TERMINALS

 

COM 24V

 

W2

 

 

DEHUMIDIFIER (DH)

 

CONNECTOR

 

3-AMP FUSE

CONTINUOUS FAN (CF) SETUP

SWITCHES

COMMUNICATION

CONNECTOR

STATUS AND DIAGNOSTIC LED LIGHTS

AIR CONDITIONING

(A/C) SETUP SWITCH SETUP SWITCHES (SW) AND BLOWER OFF DELAY SETUP

SWITCHES

MODEL PLUG

A93062

Fig. 25ÐControl Center

Ð20Ð

Image 20
Contents Ð1Ð ÐMultipoise OrientationsUnit Size DimensionsÐ2Ð Safety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance To Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð III. Downflow Applications Condensate Trap LocationCondensate Trap Tubing Ð7ÐÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Condensate Trap Tubing ÐHorizontal Right Tube Configuration Location GeneralII. LOW-FIRE only Installation III. Furnace Location Relative to Cooling EquipmentIV. Hazardous Locations Installation Leveling Legs if DesiredII. Installation in Upflow or Downflow Applications Width Ðopening DimensionsFurnace Plenum Opening Floor Opening Casing III. Installation in Horizontal Applications ÐDuct FlangesIV. Filter Arrangement Ðfilter InformationBottom Closure Panel → ÐBottom Filter ArrangementWiring VI. GAS PipingÐmaximum Capacity of Pipe Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Size III. AccessoriesÐelectrical Data Direct Venting Removal of Existing Furnaces from Common Vent SystemsNgpic II. COMBUSTION-AIR and Vent PipingÐCOMBUSTION-AIR and Vent Pipe Termination Clearances Combustion-Air and Vent Pipe DiameterLocation Clearance FT Or doors which can be opened or Combustion-air openingExample Combustion-Air and Vent Pipe AttachmentÐmaximum Allowable Pipe Length FT 2001 to3001 to 4001 to 5000³Ðmaximum Allowable Pipe Length FT 6001 to 7000³7001 to 8000³ 8001 to 9000³III. Concentric Vent and COMBUSTION-AIR COMBUSTION-AIR Intake Housing Plug FittingTermination KIT Installation ÐRoof Termination Preferred Extended Exposed Sidewall Pipes Two-Pipe Termination KitConcentric Vent/Air Termination Kit 042040 042060 042080 060080 060100 060120IV. Multiventing and Vent Terminations Condensate Drain GeneralII. Application III. Condensate Drain ProtectionÐConcentric Vent and Combustion-Air Roof SELF-TEST Mode II. Heating ModeSequence of Operation HSIIV. Emergency Heat Mode Cooling ModeVI. Heat Pump Mode III. Heating Modeðtwo StageÐWiring Schematic for 2-Speed Cooling Applications VII. Continuous FAN ModeIX. Bypass Humidifier Mode Dehumidification ModeXI. Zone Mode START-UP Procedures GeneralÐair Conditioning A/C Airflow Setup Switch Position Ðcontinuous FAN CF Airflow Setup Switch PositionSetup Switches SW III. Prime Condensate Trap with WaterÐsetup Switch Description Ðblower OFF Delay Setup Switch PositionAdjustments IV. Purge GAS LinesSet Gas Input Rate → ÐRedundant Automatic Gas ValveBTU/CU FT Only 4001875 1.5 50007001 775 1.58000 825Ðaltitude Derate Multiplier for U.S.A CanadaSume the Orifice SIZE. Always Check and Verify Altitude Derate Multiplier Factor for U.S.ASet Temperature Rise Check Safety Controls Check Primary Limit ControlÐgas Rate CU FT/HR Set Thermostat Heat AnticipatorII. Check Pressure Switches ChecklistChecklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Combustion and Vent Piping

355M-40-4, 355M-40-5 specifications

The Bryant 355M-40-5 and 355M-40-4 are innovative CNC cylindrical grinders designed to meet the demands of precision machining in various industrial applications. These machines stand out due to their robust construction, advanced technology, and versatile functionalities, which are critical for achieving high-quality grinding results.

One of the main features of the Bryant 355M-40-5 and 355M-40-4 is their precision grinding capability. With high spindle speeds and excellent rigidity, these grinders are engineered to deliver superior surface finishes even on complex geometries. The machines are equipped with advanced dressing systems that ensure consistent wheel profiles, enhancing performance and reducing cycle times.

The Bryant 355M-40-5 differentiates itself through its multi-axis capability, allowing for the grinding of intricate shapes and features without the need for extensive setup changes. Operators can easily program complex grinding sequences through the user-friendly interface, which supports both manual and automated operations. This flexibility is crucial in manufacturing environments that require quick turnaround times and adaptability to various workpieces.

Meanwhile, the Bryant 355M-40-4 focuses on efficiency and productivity, featuring a streamlined design that optimizes workflow. The machine is fitted with high-precision linear guides and ball screws, ensuring smooth and accurate movements during the grinding process. This results in minimal wear and tear, thereby extending the machine's lifespan and maintaining accuracy over time.

Key technologies incorporated into both models include state-of-the-art control systems that enable real-time monitoring and feedback during operations. This feature allows operators to make on-the-fly adjustments to optimize grinding parameters, leading to improved performance and reduced scrap rates. Additionally, the integration of automation solutions, such as robotic loading systems, enhances productivity by minimizing downtime and labor costs.

The Bryant 355M-40-5 and 355M-40-4 are built with durability in mind, utilizing high-strength materials that resist deformation and wear. Their thermal stability ensures consistent performance even under varying operating conditions, making them a reliable choice for high-volume production.

In summary, the Bryant 355M-40-5 and 355M-40-4 models are exemplary CNC cylindrical grinders that combine precision, efficiency, and advanced technology. Their features make them suitable for a wide range of grinding applications, from tool manufacturing to automotive components, ensuring that they remain competitive in the ever-evolving landscape of manufacturing technology.