Bryant 355M-40-4, 355M-40-5 Ð8Ð, IV. Horizontal Left SUPPLY-AIR Discharge Applications

Page 8

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

d.Use inducer housing drain tube (violet label and factory- supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.

e.Connect inducer housing drain connection to condensate trap.

(1.)

Condensate Trap Located on Left Side of Casing

 

(a.)

Determine appropriate length and cut.

 

(b.)

Connect tube to condensate trap.

 

(c.)

Clamp tube to prevent any condensate leakage.

(2.)

Condensate Trap Located on Right Side of Casing

(a.)

Route inducer housing drain tube (violet label)

 

 

directly from inducer housing drain to conden-

 

 

sate trap as shown in Fig. 8.

 

(b.)

Determine appropriate length and cut.

 

(c.)

Connect tube to condensate trap.

 

(d.)

Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

Refer to Pressure Switch Tubing section for connection procedure.

C.Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D.Pressure Switch Tubing

One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be dis- connected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZON- TAL RIGHT applications.

NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Relocate tubes as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

2.Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connec- tion by splicing to small diameter tube (factory-supplied in loose parts bag).

3.Connect collector box pressure tube (green label) to pres- sure switch connection labeled COLLECTOR BOX.

4.Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory-supplied in loose parts bag).

5.Route this extended tube (pink label) to condensate trap relief port connection.

6.Determine appropriate length, cut, and connect tube.

7.Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda- tions and procedures.

Ð8Ð

IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.

CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.

NOTE: The auxiliary junction box (J-box) MUST be relocated to opposite side of furnace casing. (See Fig. 9.) See Electrical Connection section for J-box relocation.

A.Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 9.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 9.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

B.Condensate Trap Tubing

NOTE: See Fig. 9 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.

b.Connect large diameter drain tube and clamp (factory- supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.

c.Route extended tube (blue label) to condensate trap and cut to appropriate length.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to conden- sate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Extend collector box tube (green label) which was previously connected to condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).

Image 8
Contents Ð1Ð ÐMultipoise OrientationsUnit Size DimensionsÐ2Ð Safety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance To Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð III. Downflow Applications Condensate Trap LocationCondensate Trap Tubing Ð7ÐÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsÐ9Ð Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications ÐAttic Location and Working Platform Condensate Trap Tubing ÐHorizontal Right Tube Configuration Location GeneralII. LOW-FIRE only Installation III. Furnace Location Relative to Cooling EquipmentIV. Hazardous Locations Installation Leveling Legs if DesiredII. Installation in Upflow or Downflow Applications Width Ðopening DimensionsFurnace Plenum Opening Floor Opening Casing III. Installation in Horizontal Applications ÐDuct FlangesIV. Filter Arrangement Ðfilter InformationBottom Closure Panel → ÐBottom Filter ArrangementWiring VI. GAS PipingÐmaximum Capacity of Pipe Electrical Connections→ ÐHeating and Cooling Application Wiring Diagram II -V WiringÐWiring Diagram Amps Size III. AccessoriesÐelectrical Data Direct Venting Removal of Existing Furnaces from Common Vent SystemsNgpic II. COMBUSTION-AIR and Vent PipingÐCOMBUSTION-AIR and Vent Pipe Termination Clearances Combustion-Air and Vent Pipe DiameterLocation Clearance FT Or doors which can be opened or Combustion-air openingExample Combustion-Air and Vent Pipe AttachmentÐmaximum Allowable Pipe Length FT 2001 to3001 to 4001 to 5000³Ðmaximum Allowable Pipe Length FT 6001 to 7000³7001 to 8000³ 8001 to 9000³III. Concentric Vent and COMBUSTION-AIR COMBUSTION-AIR Intake Housing Plug FittingTermination KIT Installation ÐRoof Termination Preferred Extended Exposed Sidewall Pipes Two-Pipe Termination KitConcentric Vent/Air Termination Kit 042040 042060 042080 060080 060100 060120IV. Multiventing and Vent Terminations Condensate Drain GeneralII. Application III. Condensate Drain ProtectionÐConcentric Vent and Combustion-Air Roof SELF-TEST Mode II. Heating ModeSequence of Operation HSIIV. Emergency Heat Mode Cooling ModeVI. Heat Pump Mode III. Heating Modeðtwo StageÐWiring Schematic for 2-Speed Cooling Applications VII. Continuous FAN ModeIX. Bypass Humidifier Mode Dehumidification ModeXI. Zone Mode START-UP Procedures GeneralÐair Conditioning A/C Airflow Setup Switch Position Ðcontinuous FAN CF Airflow Setup Switch PositionSetup Switches SW III. Prime Condensate Trap with WaterÐsetup Switch Description Ðblower OFF Delay Setup Switch PositionAdjustments IV. Purge GAS LinesSet Gas Input Rate → ÐRedundant Automatic Gas ValveBTU/CU FT Only 4001875 1.5 50007001 775 1.58000 825Ðaltitude Derate Multiplier for U.S.A CanadaSume the Orifice SIZE. Always Check and Verify Altitude Derate Multiplier Factor for U.S.ASet Temperature Rise Check Safety Controls Check Primary Limit ControlÐgas Rate CU FT/HR Set Thermostat Heat AnticipatorII. Check Pressure Switches ChecklistChecklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Combustion and Vent Piping

355M-40-4, 355M-40-5 specifications

The Bryant 355M-40-5 and 355M-40-4 are innovative CNC cylindrical grinders designed to meet the demands of precision machining in various industrial applications. These machines stand out due to their robust construction, advanced technology, and versatile functionalities, which are critical for achieving high-quality grinding results.

One of the main features of the Bryant 355M-40-5 and 355M-40-4 is their precision grinding capability. With high spindle speeds and excellent rigidity, these grinders are engineered to deliver superior surface finishes even on complex geometries. The machines are equipped with advanced dressing systems that ensure consistent wheel profiles, enhancing performance and reducing cycle times.

The Bryant 355M-40-5 differentiates itself through its multi-axis capability, allowing for the grinding of intricate shapes and features without the need for extensive setup changes. Operators can easily program complex grinding sequences through the user-friendly interface, which supports both manual and automated operations. This flexibility is crucial in manufacturing environments that require quick turnaround times and adaptability to various workpieces.

Meanwhile, the Bryant 355M-40-4 focuses on efficiency and productivity, featuring a streamlined design that optimizes workflow. The machine is fitted with high-precision linear guides and ball screws, ensuring smooth and accurate movements during the grinding process. This results in minimal wear and tear, thereby extending the machine's lifespan and maintaining accuracy over time.

Key technologies incorporated into both models include state-of-the-art control systems that enable real-time monitoring and feedback during operations. This feature allows operators to make on-the-fly adjustments to optimize grinding parameters, leading to improved performance and reduced scrap rates. Additionally, the integration of automation solutions, such as robotic loading systems, enhances productivity by minimizing downtime and labor costs.

The Bryant 355M-40-5 and 355M-40-4 are built with durability in mind, utilizing high-strength materials that resist deformation and wear. Their thermal stability ensures consistent performance even under varying operating conditions, making them a reliable choice for high-volume production.

In summary, the Bryant 355M-40-5 and 355M-40-4 models are exemplary CNC cylindrical grinders that combine precision, efficiency, and advanced technology. Their features make them suitable for a wide range of grinding applications, from tool manufacturing to automotive components, ensuring that they remain competitive in the ever-evolving landscape of manufacturing technology.