Carrier 58MSA instruction manual ÐWinterizing

Page 10

32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED

A93058

If this furnace is installed in an unconditioned space where the ambient temperatures may be 32°F or lower, freeze protection measures must be taken.

1.Check for signs of physical damage to heat tape such as nicks, cuts, abrasions, gnawing by animals, etc.

2.Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape.

3. Check that heat tape power supply circuit is on.

Step 10ÐWinterizing

Freezing condensate left in the furnace will damage the equipment.

If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32°F or below, winterize as follows:

1.Turn off electrical supply to furnace.

2.Remove main furnace door.

3.Disconnect drain tube from inducer housing. (See Fig. 13.)

4.Insert funnel in drain tube and pour antifreeze, propylene glycol (RV, swimming pool antifreeze, or equivalent) into furnace until it is visible at point where condensate enters open drain. (See Fig. 14.)

5.Reconnect drain tube to inducer housing.

6.Replace main furnace door.

Do not use ethylene glycol (Prestone II antifreeze/coolant or equivalent automotive type). Failure of plastic components will occur.

10

Image 10
Contents Service and Maintenance Instructions → ÐMultipoise Furnace in Upflow Orienta- tionÐMultipoise Orientations ÐCleaning and/or Replacing Air Filter ÐBlower Motor and Wheel MaintenanceÐCleaning Burners ÐSpeed SelectorÐCleaning Inlet Openings of Primary Heat Exchangers ÐCleaning Heat Exchangers→ ÐFurnace Pressure and Drain Tubing Diagram ÐFlushing Collector Box and Drainage SystemÐGasket on Collector Box ÐServicing Hot Surface IgnitorÐElectrical Controls and Wiring → ÐField WiringÐTroubleshooting ÐControl Center ÐChecking Heat Tape Operation If ApplicableÐWinterizing A99118 A99119 → ÐWiring Diagram Schematic DiagramService → Troubleshooting Guide A99123 Service Training