SERVICE
If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.
LED CODE | STATUS |
CONTINUOUS OFF - | Check for 115VAC at L1 and L2, and 24VAC at |
CONTINUOUS ON - | |
Control has 24V power. |
RAPID FLASHING - Line voltage (115V) polarity reversed. If twinned, refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11NO PREVIOUS CODE - Stored status codes are erased when power
(115V or 24V) to control is interrupted or 48 hours after each fault is cleared.
12BLOWER ON AFTER POWER UP (115V or 24V) - Blower runs for 90 seconds, if unit is powered up during a call for heat
13LIMIT OR FLAME
14IGNITION LOCKOUT - Control will
21GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - |
22ABNORMAL
Check for: | - Leaky gas valve |
23PRESSURE SWITCH (ES) DID NOT OPEN Check for:
- Obstructed pressure tubing. - Defective pressure switch (stuck closed).
24SECONDARY VOLTAGE FUSE IS OPEN
Check for: - Short circuit in secondary voltage (24V) wiring.
31 PRESSURE, DRAFT SAFEGUARD,
VENT SHUTOFF (when used) SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry.
Check for: | - Inadequate Combustion air supply. |
-Proper vent sizing and condensate pitch or sag
-Low inducer voltage.
-Vent restriction or high winds.
-Disconnected or obstructed pressure tubing
-Defective inducer motor or start capacitor.
-Defective pressure switch or connections. If it opens after trial for ignition period, blower will come on for 90 second recycle delay.
33LIMIT OR FLAME
-Dirty filter or restricted duct system.
-Loose blower wheel.
-Defective switch or connections.
-Inadequate Combustion air supply (Flame
-Open Flame
34IGNITION PROVING FAILURE - Control will try three more times before a lockout #14 occurs. If flame signal lost after trial for ignition period, blower will come on for 90 second recycle delay. Check for:
-Oxide buildup on flame sensor (clean with fine steel wool).
-Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
-Gas valve defective or gas valve turned off.
-Defective Hot Surface Ignitor
-Manual valve
-Low inlet gas pressure.
-Green wire MUST be connected to furnace sheet metal.
-Inadequate flame carryover or rough ignition.
COMPONENT TEST
To initiate the component test sequence,shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower
9 | 6 | 3 |
8 | 5 | 2 |
7 | 4 | 1 |
STATUS | TEST |
→
HUM Com W | Y | R | G |
24V |
|
|
|
A99107
Fig. 16ÐService Label
13