Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a
19. Replace main furnace door.
Step 4ÐCleaning Heat Exchangers
The following items should be performed by a qualified service technician.
PRIMARY HEAT EXCHANGERS
If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure: NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A
1.Turn off gas and electrical supplies to furnace.
2.Remove main furnace door.
3.Disconnect wires or connectors to rollout switch, gas valve, ignitor, and flame sensor.
Label all wires prior to disconnection when servicing con- trols. Wiring errors can cause improper and dangerous operation.
4.Disconnect
5.Remove the pressure switch tube from intake housing.
6.Remove screws attaching intake housing to burner box, and rotate intake housing away from burner box for removal.
7.Using backup wrench, disconnect gas supply pipe from gas valve.
8.Disconnect pressure tubing from gas valve.
9.Remove 2 screws attaching top filler panel and rotate upwards to gain access to screws attaching burner box to cell panel.
10.Remove screws attaching burner box to cell panel. (See Fig. 5.)
NOTE: Burner box cover, manifold, gas valve, and burner assembly should be removed as 1 assembly.
11.Clean heat exchanger openings with a vacuum and a soft brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products.
12. Reverse items 4 through 10 for reassembly.
The ground wire from the gas valve MUST be attached to the burner box attachment screw. Failure to attach this ground wire to an adequate casing ground will cause the furnace control to lock out.
NOTE: Be sure burner box gasket is installed between burner box and cell panel. If gasket is damaged, replace it.
PRIMARY HX
INLET OPENINGS
A93080
Fig. 6ÐCleaning Inlet Openings of Primary Heat
Exchangers
→NOTE: Inspect
RTV
PAM
A93087
Fig. 7ÐCombustion-Air Intake Housing Gasket
Repair
13.Refer to furnace wiring diagram and connect wires to rollout switch, gas valve, ignitor, and flame sensor.
14.Reconnect pressure switch tubes to gas valve and intake housing. Refer to tube routing label on main furnace door for proper tube location. Be sure tubes are not kinked. (See Fig. 8.)
15.Turn on gas and electrical supplies to furnace.
16.Check furnace operation through 2 complete heat operating cycles. Look through sight glass in burner enclosure to check burners. Burner flames should be clear blue, almost transpar- ent. (See Fig. 9.)
17.Check for gas leaks.
5