PLANNING YOUR INSTALLATION

FLOOR PROTECTION – Advantage II-T C FS

(For USA and Can- ada) This appliance requires 3/8" (10 mm) minimum non- combustible floor protection designed for solid fuel burning appliances having a thermal conductivity of k = .84 BTU in/ft or equivalent. If the floor protection is to be stone, tile, brick, etc., it must be mor- tared or grouted to form a continuous non-combustible sur-

face (See Using Alternate Material As Floor Protector below). If a chimney connector extends horizontally over the floor, protection must cover the floor under the connector and at least 2" (51 mm) to either side. The floor protector must fully cover the area beneath the appliance and extend 6” to the front, 6” to the sides, and up to 6” from the back (see illustra- tion above and following note).

*Note: When installed at clearances less than 6”, the floor protection is only required to extend to the wall.

FLOOR PROTECTION / HEARTH EXTENSION USING AL- TERNATE MATERIAL AS FLOOR PROTECTOR (also see Floor Protection above for freestanding models and Hearth Requirements, page 8 for the insert model)

The hearth pad or alternate material used as a floor/hearth protector must be constructed of a durable noncombustible material having an equal or better thermal conductivity value (lower k value) of k = .84 BTU / IN FT2 HR °F or a thermal resistance that equals or exceeds r = 1.19 HR °F FT2 IN/BTU with a minimum thickness of 3/8”. With these values, determine the minimum thickness of the alternate material required using the formula(s) and the table shown here (see chart - Approved Alternate Materials for Floor/Hearth Protection).

Note: Any noncombustible material having a minimum thickness of 3/8” (10 mm) whose k value is less than .84 or whose r value is more than 1.19 is acceptable. If the alternate material used has a higher k value or lower r value will require a greater thickness of the material used. In some cases, if the k value is less or the r value higher, a thinner material may be used.

Methods of determining floor protection equivalents:

To determine the thickness required for the alternate material when either the k value or r value is known, use either the k formula or r formula:

Example: DurockCement is to be used for the floor protec- tion. How thick must this material be? The following formulas give the means of determining minimum thickness required.

TM = minimum thickness required for alternate material kM = k value per inch of alternate material

TL = minimum thickness of listed material rM = r value per inch of alternate material

Using the k formula:

Minimum

 

k-value (per Inch)

 

Specified min.

thickness of

=

of alternate material

x

thickness

alternate

 

k-value (per inch)

 

of listed

material

 

of listed material

 

material

TM (inches) = kM x TL

.84

TM (inches) = 1.92 x .375 (3/8”)

.84

Answer using k: 2.29 x 0.375” = 0.858 = ~7/8”

7/8” thickness (minimum) DurockCement will be required. Using the r formula:

TM (inches) = 1.19 x TL rM

TM (inches) = 1.19 x 375 (3/8”)

.52

Answer using r: 2.29 x 0. 375” = 0.858 = ~7/8”

7/8” thickness (minimum) DurockCement will be required.

At times it is important to know what combination of materials are acceptable for use as floor protection. The “R values” are used to determine acceptable combinations of materials because “R val- ues” are additive where r and k values are not.

“R value” = 1 = r x thickness of material used k

Example: Given that the required “R value” for a suitable floor pro- tector used must be equal to or greater than “R” = r x TL = 1.19 x

.375” = .45.

Listed Material

 

Thermal Values

Specified

 

 

 

Minimum

 

 

 

Thickness

 

k (per inch)

r (per inch)

TL

Listed Material

.84

1.19

3/8” (.375)

Approved Alternate Materials for

Floor/Hearth Protection (**)

Alternative

Thermal Values

* Minimum

Materials

 

 

Thickness

 

k (per inch)

r (per inch)

 

TM

Kaowool M Board

.47

2.13

* 3/8”

Micore 160

.35

2.86

* 3/8”

Micore 300

.46

2.18

* 3/8”

DurockCement

1.92

.52

7/8”

Hardibacker

1.95

.51

7/8”

Hardibacker 500

2.30

.44

1

1/8”

Cultered Stone

2.82

.35

1

5/8”

Hearthstone

 

 

 

 

Wonderboard

3.23

0.31

1

1/2”

Face brick

9.00

0.11

4

1/8”

Common brick

5.00

0.20

2

1/4”

Cement mortar

5.00

0.20

2

1/4”

Ceramic tile

12.5

.08

5 5/8”

Marble

~20.0

~.05

 

9”

 

 

 

Note: To convert inches to millimeters divide by .03937.

*After minimum thickness is calculated, the thickness can be no less than 3/8” (.375” / 10mm).

(**)If the floor protector to be used is a noncombustible material and is NOT listed on the chart above, the manufacturer of the material must provide either the listed k-value per inch or r-value per inch and the minimum acceptable thickness will need to be calculated per instruc- tions on this page.

PAGE 5

www.PelletKing.com

Image 5
Contents Freestanding Insert Pellet Fired Stoves Installation and Operation ManualImportant Warnings Table of Contents Installation / Maintenance Standards Planning Your InstallationSelecting a Location Smoke DetectorsApproved Alternate Materials for Floor/Hearth Protection Floor Protection Advantage II-T C FSListed Material Advantage II-T C ClearancesMinimum Clearances to Combustibles Masonry and Factory Built Fireplaces Model Advantage II-T C FS Pedestal Air Inlet Manufactured Mobile Home INSTAL- LationASH PAN Cover Assembly InstallationInstalling Pedestal to Body Removing Appliance from PalletCheck list Installation Check ListPrior to lighting your stove After you have begun operation of your stoveTop Surround Panel Rear View of Advantage II-T C FS Thermostat InstallationVenting Requirements Manufactured Mobile Home Chimney Height Requirements Vent TerminationInstallation Chart Determining Size of Pipe to InstallSample Installation Chart Pipe Selection ChartPipe Horizontal Vent Through the Wall Advantage II-T C FS Corner Through the WallTop View Illustration Existing Class a Chimney Vertical Vent Into a Masonry FlueUSA & Canada Direct Connection / Posi- tive Flue Connection Installation Advantage II-T C INSVent Termination When Liner is Used Important Notes Installing Advantage II-T C INSControl Board Care and OperationControl Board Operation Starting Your Pellet Stove PRE-LIGHTING InstructionsGeneral Operating Considerations Turning OFF Your Pellet StoveDamper In less air Damper OperationAutomatic Safety Features Damper Adjustment GuidelinePower Outage OverheatingUltraGrateTM FuelRoutine Cleaning Routine MaintenanceProper Disposal of Ashes UltraGrateTM ASH PAN Advantage II-T C FSHeat Exchanger Tubes ASH Trap and BafflesCreosote Removal Door Rope GasketMinimum Frequency of 3 months to 1 year Remove Window Wash Bracket Window WashOpening Side Panels Advantage II-T C FS Opening Side PanelsMotor Lubrication Small Area Paint TOUCH-UPBack View Illustration Specifications Advantage II-T C FSSide View Illustration Side View Front ViewComponent Definitions Wiring Diagram Troubleshooting Qualified Technicians Only Damper Adjustment Guidelines Troubleshooting Qualified Technicians Only Replacement Parts List Insert Only Parts Freestanding Only PartsMiscellaneous Parts Firebox PartsPiece Set UltraGrate TM Kit Replacement Part DiagramsFirebrick Kit Pressure Switch Kit Catalog # Model Description Stove Model Optional Accessories List and DiagramsGold Trivet Cat. # H0423 Surround Kits & Trim Kits Log Set Cat. #H0430Advantage II-T C Pellet Stove Safety Label Advantage II-T C EPA Label & Colorado Compliance Label Simple Operating Instructions Label Installation Tips Ownership Records Service and Maintenance LOGWest Taft Avenue Orange, CA

II-T C FS, II-T C INS specifications

The Lennox Hearth II-T C INS and II-T C FS are exemplary models in the world of modern heating solutions, designed for efficiency, comfort, and style. With innovative engineering and advanced technology, these units cater to the needs of contemporary homeowners seeking reliable and aesthetically pleasing heating options.

One of the main features of the Lennox Hearth II-T C INS and II-T C FS is their exceptional efficiency ratings. These models are designed to operate at high efficiency levels, reducing energy consumption while providing optimal warmth. This not only translates to lower utility bills but also represents a more sustainable choice for environmentally conscious consumers.

A standout characteristic of these products is their versatility in installation. The II-T C INS is an insert model, allowing it to be fitted into existing fireplaces easily. This makes it an ideal option for homeowners wanting to upgrade their current heating systems without extensive renovations. The II-T C FS, on the other hand, is a freestanding stove that adds a classic touch to any room, making it a perfect focal point while offering powerful heating capabilities.

Both models are equipped with advanced technology designed for seamless operation. The hot air circulation system ensures that warmth is evenly distributed throughout the space, eliminating cold spots and enhancing overall comfort. In addition, their adjustable thermostats allow users to set the desired temperature with ease, ensuring a consistent indoor environment.

The Lennox Hearth units are also designed with user convenience in mind. They come with easy-to-use controls and can often be integrated with smart home systems, offering the flexibility to monitor and adjust settings remotely. This modern approach to home heating makes it simple for users to maintain a cozy atmosphere, even on the coldest days.

Moreover, Lennox places a strong emphasis on safety. These heating models include features such as a glass door that remains cool to the touch and a built-in safety shut-off system, providing peace of mind for families.

In summary, the Lennox Hearth II-T C INS and II-T C FS models stand out for their efficiency, versatility, advanced technology, and safety features. With a focus on optimal performance and user convenience, these units represent a significant advancement in home heating, making them an attractive choice for those looking to enhance their living spaces while staying warm and comfortable.