Lennox Hearth II-T C FS, II-T C INS operation manual Venting Requirements

Page 13

INSTALLATION

VENTING REQUIREMENTS

It is recommended that only an authorized dealer install your pellet stove. The specified installation requirements must be followed to ensure conformity with both the safety listing of the appliance and local building codes. All clearances, installation instructions and precautions specified by the vent manufacturer must be followed.

Selecting a Location (Freestanding Models) - Review the appliance clearance requirements before installing the venting system (see page 6). Position the appliance far enough away from walls to allow adequate room for servicing. Choose the appliance location with the least amount of interference with the house framing, plumbing, wiring, etc.

Preferred Vent Configuration - For the best perform- ance, we recommend a vent run design which runs verti- cally and terminates above the roofline. This design will allow natural draft to improve the flow of flue gases and will aid in combustion and stove performance.

Type of Pipe - This stove requires type “PL” vent pipe (pellet vent pipe, sometimes referred to as “L-Vent pellet vent”), listed to UL 641 or ULC S609. Connect the pellet vent pipe or the “tee” to the flue collar using a minimum of three screws and seal as specified in “Pipe / Liner Joint Requirements” on this page. Do not use class B gas chimney or single wall chimney as a substitute.

Size of Pipe - These pellet appliances are approved for use with the following vent sizes: 3” (75mm) standard, or 4” (100mm), see page 15 - for determining correct size vent). When 4” pipe is used: for horizontal vent installa- tions use a 3” (75mm) to 4” (100mm) adapter - available from vent manufacturer. For vertical installations use a 3” (75mm) to 4” (100mm) “tee” - available from vent manufacturer.

Note: If installation requires in excess of 11 feet (3 1/3 meter) of pipe, it is recommended that 4” (100 mm) pipe be used.

Offsets - In every installation, a single or double clean- out “tee” is recommended for every ninety-degree offset (this tee will help collect ash residue and will allow for routine cleaning without the need to disconnect sections of pipe). Note: Offsets and horizontal runs accumulate fly ash and soot which reduces the exhaust flow and per- formance of the stove.

Total Offsets in venting system should not exceed 270° total in direction change.

Horizontal Runs - The maximum total horizontal run must not exceed 10 feet (3.1 meters).

Horizontal run of pipe requires 1/4” (7 mm) rise per foot.

Pipe Clearances / Requirements - See pipe manufac- turers instructions for installation of venting components and clearances. Follow pipe manufacturers installation precautions for passing pipe through a combustible wall or ceiling (i.e. use an approved thimble). Note: Pellet vent pipe requires 3” (75mm) clearance from outside of pipe unless otherwise specified by vent manufacturer - all diameters: 3” (75mm) and 4” (100mm). A support bracket must be installed every 4’ (1.2m) of pellet vent pipe on the exterior wall of the house unless otherwise specified by vent manufacturer.

Pipe / Liner Joint Requirements - All pipe joints must be secured with a minimum of 3 screws. ALL horizontal joints must be sealed gas tight (air tight, sealed connec- tion). Use RTV high temperature silicone or Interam to provide a complete seal at the flue collar and on all joints.

Connection to Masonry Chimney through a Wall (Freestanding Models) - Be sure to verify the construc- tion of a masonry chimney, as it may have combustible framing.

Approved liner when relining Masonry or Factory Built Fireplaces is 2100HT (degree F.) liner listed to UL 1777 or ULC S635.

Connection to an Existing Class A Chimney (Free- standing Models) - A chimney adapter can be used to make the connection from 3” (75mm) or 4” (100mm) pel- let vent pipe (listed to UL 641 or ULC S609) to existing UL chimney system. Verify with the pipe manufacturer that your pipe brands will interconnect.

Horizontal-Vent Installations - On all horizontal-vent installations (short, horizontal runs with no vertical pipe); care should be taken when choosing a location for termi- nating the vent. It is not recommended to directly vent the exhaust on the prevailing wind side of the house. It is recommended that when an appliance is vented directly through a wall, a minimum of 8’ (2.5m) of vertical pipe should be installed to create some natural draft. This will reduce the possibility of smoke or odor entering the dwelling during appliance shutdown or loss of power.

PAGE 13

www.PelletKing.com

Image 13
Contents Freestanding Insert Pellet Fired Stoves Installation and Operation ManualImportant Warnings Table of Contents Installation / Maintenance Standards Planning Your InstallationSelecting a Location Smoke DetectorsListed Material Floor Protection Advantage II-T C FSApproved Alternate Materials for Floor/Hearth Protection Minimum Clearances to Combustibles ClearancesAdvantage II-T C Masonry and Factory Built Fireplaces Model Advantage II-T C FS Pedestal Air Inlet Manufactured Mobile Home INSTAL- LationASH PAN Cover Assembly InstallationInstalling Pedestal to Body Removing Appliance from PalletCheck list Installation Check ListPrior to lighting your stove After you have begun operation of your stoveTop Surround Panel Rear View of Advantage II-T C FS Thermostat InstallationVenting Requirements Manufactured Mobile Home Chimney Height Requirements Vent TerminationInstallation Chart Determining Size of Pipe to InstallSample Installation Chart Pipe Selection ChartPipe Top View Illustration Advantage II-T C FS Corner Through the WallHorizontal Vent Through the Wall Existing Class a Chimney Vertical Vent Into a Masonry FlueVent Termination When Liner is Used Installation Advantage II-T C INSUSA & Canada Direct Connection / Posi- tive Flue Connection Important Notes Installing Advantage II-T C INSControl Board Operation Care and OperationControl Board Starting Your Pellet Stove PRE-LIGHTING InstructionsGeneral Operating Considerations Turning OFF Your Pellet StoveDamper In less air Damper OperationAutomatic Safety Features Damper Adjustment GuidelinePower Outage OverheatingUltraGrateTM FuelRoutine Cleaning Routine MaintenanceProper Disposal of Ashes UltraGrateTM ASH PAN Advantage II-T C FSHeat Exchanger Tubes ASH Trap and BafflesMinimum Frequency of 3 months to 1 year Door Rope GasketCreosote Removal Remove Window Wash Bracket Window WashOpening Side Panels Advantage II-T C FS Opening Side PanelsMotor Lubrication Small Area Paint TOUCH-UPSide View Illustration Specifications Advantage II-T C FSBack View Illustration Side View Front ViewComponent Definitions Wiring Diagram Troubleshooting Qualified Technicians Only Damper Adjustment Guidelines Troubleshooting Qualified Technicians Only Replacement Parts List Insert Only Parts Freestanding Only PartsMiscellaneous Parts Firebox PartsFirebrick Kit Replacement Part DiagramsPiece Set UltraGrate TM Kit Pressure Switch Kit Catalog # Model Description Stove Model Optional Accessories List and DiagramsGold Trivet Cat. # H0423 Surround Kits & Trim Kits Log Set Cat. #H0430Advantage II-T C Pellet Stove Safety Label Advantage II-T C EPA Label & Colorado Compliance Label Simple Operating Instructions Label Installation Tips Ownership Records Service and Maintenance LOGWest Taft Avenue Orange, CA

II-T C FS, II-T C INS specifications

The Lennox Hearth II-T C INS and II-T C FS are exemplary models in the world of modern heating solutions, designed for efficiency, comfort, and style. With innovative engineering and advanced technology, these units cater to the needs of contemporary homeowners seeking reliable and aesthetically pleasing heating options.

One of the main features of the Lennox Hearth II-T C INS and II-T C FS is their exceptional efficiency ratings. These models are designed to operate at high efficiency levels, reducing energy consumption while providing optimal warmth. This not only translates to lower utility bills but also represents a more sustainable choice for environmentally conscious consumers.

A standout characteristic of these products is their versatility in installation. The II-T C INS is an insert model, allowing it to be fitted into existing fireplaces easily. This makes it an ideal option for homeowners wanting to upgrade their current heating systems without extensive renovations. The II-T C FS, on the other hand, is a freestanding stove that adds a classic touch to any room, making it a perfect focal point while offering powerful heating capabilities.

Both models are equipped with advanced technology designed for seamless operation. The hot air circulation system ensures that warmth is evenly distributed throughout the space, eliminating cold spots and enhancing overall comfort. In addition, their adjustable thermostats allow users to set the desired temperature with ease, ensuring a consistent indoor environment.

The Lennox Hearth units are also designed with user convenience in mind. They come with easy-to-use controls and can often be integrated with smart home systems, offering the flexibility to monitor and adjust settings remotely. This modern approach to home heating makes it simple for users to maintain a cozy atmosphere, even on the coldest days.

Moreover, Lennox places a strong emphasis on safety. These heating models include features such as a glass door that remains cool to the touch and a built-in safety shut-off system, providing peace of mind for families.

In summary, the Lennox Hearth II-T C INS and II-T C FS models stand out for their efficiency, versatility, advanced technology, and safety features. With a focus on optimal performance and user convenience, these units represent a significant advancement in home heating, making them an attractive choice for those looking to enhance their living spaces while staying warm and comfortable.