Lennox Hearth LA41CF, LA41TCF Calculating Minimum Thickness if Multiple Materials are Used

Page 17

Answer - The minimum required thickness of the Micore 160 is .417”, therefore round up to nearest standard thickness available which is 1/2”.

Listed Material

 

k (per inch)

r (per inch)

Listed Min.Thickness

 

 

 

 

Listed Material

.84

1.19

1"

 

KL

rL

TL

** Approved Alternate Materials for Floor/Hearth Protection

 

 

 

AlternativeMaterials

Thermal Values

MinimumThickness

 

 

 

(rounded to nearest 1/8 inch)

 

 

 

 

 

k (per inch)

r (per inch)

Min. Thickness

 

KM

rM

TM

Kaowool M Board

.47

2.13

.56" (1/2")

 

 

 

 

Micore 160™

.35

2.86

.42" (3/8")

U.S. Gypsum

 

 

 

 

 

 

 

Micore 300™

.46

2.17

.55" (1/2")

U.S. Gypsum

 

 

 

 

 

 

 

Durock™ Cement Board

1.92

.52

2.29" (2-1/4")

U.S. Gypsum

 

 

 

 

 

 

 

Hardibacker™

1.95

.513

2.32" (2-3/8")

Hardibacker 500™

2.30

.435

2.74" (2-3/4")

Cultered Stone Hearth-

2.82

.355

3.36" (3-3/8")

stone™

 

 

 

 

 

 

 

Wonderboard

3.23

.31

3.85" (3-7/8")

 

 

 

 

Super Firetemp M

.61

1.64

.73" (3/4")

Johns-Manville

 

 

 

 

 

 

 

Super Firetemp L

.54

1.85

.64" (5/8")

Johns-Manville

 

 

 

 

 

 

 

Face brick

9.00

.111

10.71" (10-3/4")

Common brick

5.00

.20

5.95" (6")

Cement mortar

5.00

.20

5.95" (6")

 

 

 

 

Ceramic tile

12.5

.08

14.88" (14-7/8")

 

 

 

 

Marble

11

.09

13.10" (13-1/8")

 

 

 

 

Table 1

 

 

 

**If the hearth extension material(s) that is intended to be used is NOT listed on Table 1, the material can still be used if the material(s) is noncombustible. However, the manufacturer of the material must provide either the listed k- value per inch or r-value per inch with listed thickness so that the minimum thickness required for the hearth can be calculated (per instructions on this Page and/or as specified in the NFI Certification manuals).

Note: Also see NFI (National Fireplace Institute) Certification Manuals showing other acceptable calculation methods and acceptable alternate materials which can be used.

Calculating Minimum Thickness if Multiple Materials are Used

At times it is important to know what combination of materials are acceptable for use as floor protection. The “R values” are used to determine acceptable combinations of materials because “R values” are additive where r and k values are not.

“R value” = 1/k = “r” x thickness of material used

Example: Given that the required “R value” for a suitable floor protector used must be equal to or greater than:

“R” = rL x TL = 1.19 x 1” = 1.19.”

If it is desired to elevate a marble hearth ex- tension to a level of 5” or more above the floor surface. What combination of noncombus- tible materials can be used to accomplish this?

If common brick is used so that the 3 1/2” dimension is the height, “R” for the common brick becomes:

brick

“R”M = rM x TS = 0.20 x 3 1/2" = .70

Using 1/2” of mortar to set the brick, “R” for the mortar is calculated as follows:

mortar

“R”M = rM x TS = 0.20 x 1/2" = .10

Next, a 3/4" marble slab set in 1/2" mortar cov- ers the brick, “R” for the marble and mortar becomes:

marble

“R”M = rM x TS = 0.05 x 3/4" = .038

mortar

“R”M = rM x TS = 0.20 x 1/2" = .10

The sum of all “R values” is: .70 + .10 +. 038 + .10 = .938

This would NOT be an acceptable combination of material for the hearth extension since the total calculated “R value” of the materials used is under the required “R value” of 1.19. An additional layer of insulating materials must be used.

Note: Also see NFI Certification Manuals for expanded explanation on calculating “R val- ues” when multiple materials are used.

17

Image 17
Contents WH Report No. J20017261-231 Retain These Instructions For Future ReferenceWood Burning Fireplaces P/N 504,217M REV. E 04/2007 Table of Contents Precautions Typical InstallationIntroduction Clearances and Height RequirementsChimney Height Assembly OutlineChase Enclosure Before You StartPRE-INSTALLATION Notes Assembly StepsInstalling the Fireplace ClearancesBlocking Metal Safety Strips Fireplace SpecificationsFront Left SideFraming Specifications 8d Nail Or Equivalent Installing the Chimney SystemChimney 30 Offset Through Floor Or Ceiling 12 to 12/12 Roof Pitch Model Flat to 6/12FTF8-S4 Stabilizer FTF10 Chimney Do Not Seal Flashing Spacers FTF10 FlashingUsing a FTF10-CT1 Chase Termination Using a FTF10-CTDT Chase TerminationUsing a FTF10-CT2 Chase Termination TEN Foot Rule SummaryOffset Calculations Multiple TerminationsSpecial Offset Instructions FTF10 Vertical Elevation Chart Installing Offsets FTF10 Offset Elevation ChartOptional Equipment Considerations Cold Climate Insulation Glass DoorsFireplace Finishes Mantels and TrimUsing the k formula Minimum Hearth Extension DimensionsUsing the r formula Minimum Value per Inch Methods of Determining Hearth Extension and Wall ShieldValue = 1/k = r x thickness of material used Calculating Minimum Thickness if Multiple Materials are UsedMin. Distance To Installation ComponentsFinish to Your Taste Round Termination 63L423 504,217M REV. E 04/2007