Lennox Hearth LA41CF, LA41TCF Roof Pitch Model Flat to 6/12, 12 to 12/12, FTF8-S4 Stabilizer

Page 9

Step 4. Note: Chimney sections are constructed with a unique locking tab design, which en- sures an immediate, tight assembly between sections. Plan your chimney requirements care- fully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might become damaged. Be certain tabs are properly formed to ensure locking tabs engage properly.

Security Chimneys FTF10 chimney system is a two piece chimney, which snap together from the fireplace up. Start with the inner flue section with the lanced end up, snap lock it in to the matching collar on top of the fireplace. At all subsequent joints, the upper flue section fits into the preceding flue section. Each piece snaps together by means of locking tabs (9 locking tabs per joint). Check each piece by pulling up slightly from the top to ensure proper engagement before installing the next section. If the flue has been installed correctly, it will not separate when you test it. Also, the inner flue joint where each section is joined should be tight and flat without gaps (Figure 23 ).

Figure 23

Outer pipe section installs in just the opposite way; the lanced end goes down and each new section goes OVER the outside of the previous section installed (Figure 24 ).

Locking Tabs (Lances)

Figure 24

Note: Assemble one component of chimney at a time (inner section first, then outer section last) before proceeding with the next complete section.

Continue to assemble the chimney up through framed opening. Assemble just enough to pen- etrate the roof flashing openings (Figure 25 ). Always maintain 2" minimum air space to com- bustible materials and always check each chim- ney joint (inner and outer) to ensure proper engagement. Check vertical alignment of chim- ney so that it projects from the roof in true vertical position.

1"* Min. Air Space To Combustibles

Figure 25

Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary except in certain offset condi- tions (refer to page 12, Figure 36 ).

Step 5. The height of vertical chimney pipe supported only by the fireplace must not ex- ceed 30'. Chimney heights above 30' must be supported by a Model FTF10-S4 stabilizer in- stalled at 30' intervals.

Note: The Model FTF10-S4 adds 3" net effective height to the total chimney system.

Install the Model FTF10-S4 stabilizer by fitting inner section down into respective section of proceeding flue pipe and locking outer stabi- lizer section into place over the outer chimney pipe. Position for proper clearance through framed opening and nail straps securely (under tension in “shear”) into place on framing. Use 8d nails. Attach successive lengths of chimney pipe directly to stabilizer using same tech- niques as described in Step 4 (Figure 26 ).

FTF8-S4 Stabilizer

Figure 26

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Note: Do not apply excessive pressure to any subsequent chimney sections following the stabilizer when installing. Ensure each subse- quent chimney section is securely attached by testing as noted in Step 4.

Step 6. Select the proper Security Chimneys roof flashing based on pitch of roof. Use chart below for selection:

Roof Pitch

Model

 

 

Flat to 6/12

F10F6

 

 

6/12 to 12/12

F10F12

 

 

Next, slide roof flashing over extended chimney section that previously has been installed above the roof opening in Step 4. FTF10 flashings require flashing spacers. Slide flashing all the way down until the flashing base rests flat on the roof (Figure 27 ). Again, check the vertical position of the chimney and the 2" minimum air space to combustibles.

FTF10 Chimney

Do Not Seal

Flashing Spacers

FTF10 Flashing

Figure 27

Note: Do not caulk or seal the ventilating openings.

Step 7. Secure flashing by attaching along the perimeter into roof using 8d nails or equivalent. If shingled roof, slide upper end and sides of roof flashing under shingles (trim if neces- sary), seal the top and both sides of the flashing to the roof with roof caulking. Cover nail heads with roof caulking (Figure 28 ).

Figure 28

9

Image 9
Contents Retain These Instructions For Future Reference Wood Burning Fireplaces P/N 504,217M REV. E 04/2007WH Report No. J20017261-231 Table of Contents Precautions Typical InstallationIntroduction Clearances and Height RequirementsChimney Height Assembly OutlineChase Enclosure Before You StartPRE-INSTALLATION Notes Assembly StepsInstalling the Fireplace ClearancesBlocking Metal Safety Strips Fireplace SpecificationsFront Left SideFraming Specifications Installing the Chimney System Chimney 30 Offset Through Floor Or Ceiling8d Nail Or Equivalent 12 to 12/12 Roof Pitch Model Flat to 6/12FTF8-S4 Stabilizer FTF10 Chimney Do Not Seal Flashing Spacers FTF10 FlashingUsing a FTF10-CT1 Chase Termination Using a FTF10-CTDT Chase TerminationUsing a FTF10-CT2 Chase Termination TEN Foot Rule SummaryMultiple Terminations Special Offset InstructionsOffset Calculations FTF10 Vertical Elevation Chart Installing Offsets FTF10 Offset Elevation ChartOptional Equipment Considerations Cold Climate Insulation Glass DoorsFireplace Finishes Mantels and TrimUsing the k formula Minimum Hearth Extension DimensionsUsing the r formula Minimum Value per Inch Methods of Determining Hearth Extension and Wall ShieldValue = 1/k = r x thickness of material used Calculating Minimum Thickness if Multiple Materials are UsedInstallation Components Finish to Your TasteMin. Distance To Round Termination 63L423 504,217M REV. E 04/2007