Trane TSH 060, TSD manual Operation with a conventional thermostat, Terminal strip

Page 48

Operation

Operation with a conventional thermostat

The ReliaTel module has conventional thermostat connections as well as Zone Sensor Module connections. When a conventional thermostat is controlling the unit, operation differs as follows:

Supply Air Tempering feature is not available. If outdoor air is being introduced through the equipment, discharge air temperature may be cold when not actively heating.

Proportional Integral (PI) control is not available.

Zone Sensor Diagnostics are only available on the RTRM module on the J6 terminals, instead of at the Zone Sensor in the space.

Intelligent Fall-Back is not available. If a failure occurs in the device controlling the equipment, operation will cease.

Heat Pump Smart Recovery and Smart Staging is not available. Heat Pump operation becomes more costly unless the generic control being applied can accomplish this.

Remote Sensing Capabilities are not available on most mechanical thermostats.

Space Temperature Averaging capabilities are not available on most mechanical thermostats.

27½ to 50 VAV - Conventional thermostat input terminals are inactive.

Built in Night Set Back and Unoccupied Functions function differently with a conventional mechanical thermostat.

A built-in algorithm which allows for automatic reset of the discharge air temperature while economizing is not available.

The terminal strip for attaching the thermostat wires is located on the RTRM module in the control compartment.

When the unit is operating from a conventional thermostat or other binary input, the economizer setpoint feature, relative to the cooling and heating setpoints, is lost. The economizer control is based strictly on a signal from the thermostat, but still maintains mixed air temperature control of 53°±3°F when in the economizer mode. The economizer enable and disable function is still determined by the outside air sensor through the RTRM.

If a single-stage thermostat is used, only the economizer (if enabled) or the compressor (if economizer is disabled) will operate on a call for cooling. A twostage thermostat is required to achieve economizer operation and compressor operation at the same time.

With economizer enabled, a Y1 call for 1st stage cooling will be the economizer. The damper will modulate between minimum position and 100% to maintain mixed air temperature at 53°±3°. At 50°F the damper will be at minimum position. If the economizer is enabled, a Y2 call for 2nd stage cooling will start the first compressor if required. If the economizer is disabled, 1st stage (Y1) will be the first compressor. If the unit has two compressors, a call for 2nd stage cooling (Y2) will start the second compressor. When using a conventional thermostat, or other binary input, the ReliaTel controls will only allow two stages of cooling.

Figure 30 - Terminal strip

COM

T

X2

Y2

W2

G

W1/0

Y1

R

Customers occasionally require operation with a conventional thermostat rather than a zone sensor. In some cases there is a preference for a specific thermostat model, and in others there is reluctance to adopt newer technology that may not be as well understood as conventional thermostats. In addition, non-Trane Building Controllers typically provide an interface to HVAC equipment based on a conventional thermostat interface. Units applied with this type of controller need to accept conventional thermostat inputs.

48

RT-SVX20A-E4

Image 48
Contents Installation Operation Maintenance General information ForewordWarranty Maintenance contractReception RefrigerantContents Unit Options Roof curb Installation TSD-WSD-YSD accessories Roof curb accessoryReception of units Rooftop unitDimensions/Weights/ Clearances Unit weights and center of gravityMinimum recommended clearances Factory-installed options and accessories net weights kg Motorized ManualElectric Hot water Unit size Motor HeatersInstalling the unit Discharge ConversionUnit mounting on roof Installing the unit on the ground Downflow discharge units TSD,WSD,YSD Using the rooftop curbConnection of duct network Horizontal discharge units TSH,WSH,YSHDuct dimensions for downflow units mm Duct dimensions for horizontal unitsCondensate drain piping Gas pipework installation Gas leak check procedureGas burner models UnitFilter installation Supply fan adjustmentFilter arrangement Unit EU2/G2 EU4/G4 Quantity SizeTo adjust belt To increase airflowTo decrease airflow Motor sheave / Fan speedPressure drop through accessories Component air pressure dropsUnit Airflow Filter 100%Supply fan performances TSD 060 Available static pressureTSH 060 Available static pressure TSD 072 Available static pressure TSH 072 Available static pressureTSD 090 Available static pressure TSH 090 Available static pressureTSD 102 Available static pressure TSH 102 Available static pressureTSD 120 Available static pressure TSH 120 Available static pressureYSD 060 Available static pressure YSH 060 Available static pressureYSD 072 Available static pressure YSH 072 Available static pressureYSD 090 Available static pressure YSH 090 Available static pressureStandard drive Oversize drive YSD 102 Available static pressure YSH 102 Available static pressureYSD 120 Available static pressure YSH 120 Available static pressureWSD 060 Available static pressure WSH 060 Available static pressureWSD 072 Available static pressure WSH 072 Available static pressureWSD 090 Available static pressure WSH 090 Available static pressureFactory supplied disconnect switch option Power wiringElectrical connection Over current protectionUnit wiring Ampacity SizePh/Hz Without Electric heat option With Electric heatCompressor and condenser motors Supply fan motorControl wiring Unit controlled by thermostatZone sensor wire and maximum length Unit controlled by BASUnit controlled by Tracker supervisor MaximumCO2 sensor wire size SpecificationsCO2 sensors Wiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorJumper settings Mounting the wall-mounted sensorCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatHigh temperature safety thermostat Remote fault relayClogged filter detector Smoke detectorThermostat features ThermostatsOther accessories available Communication InterfacesRefer to separate documentation for more information Trane Communication Interface TCI-R boardHot water coil Down flow units onlyEthylene glycol percentage Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodEconomizer flow chart with barometric relief Barometric reliefOperation with a conventional thermostat Terminal stripThermostat signals are as follows Input / connection Function when energized Cooling modeHeating mode Heat pump onlySetting the economizer or 0-50% motorized hood option Unoccupied modeCooling/Economizer Operation Cooling/Economizer Operation with ThermostatMinimum fresh air adjustment ECA board LEDTest procedures Operating checklist before start-upPower-up initialization Test mode procedure at the ReliaTel control boardStep Test Mode Auto Test ModeTest modes Unit start-up Gas type designation per countryGas burner data Starting the unit in cooling mode Final installation checklistCheck torque of power cables contact Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerPotentiometer Setting Economizer Set-UpReliaTel Control Heating Operation Ignition ModuleFinal installation checklist LED statusEnd user routine maintenance Air filtersRefrigerant charge Service technician maintenance Condenser coilHot water coil option Troubleshooting System Status Checkout ProcedureService Failure System failureHeating Failure Cooling FailureResetting Cooling and Ignition Lockouts Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Fan Failure SwitchThermistor Resistance / Temperature Chart ResistanceTo Test Humidity Sensors Return Air Humidity Sensor Outdoor Humidity SensorHumidity sensor test DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.