Trane TSD, TSH 060 manual Low Ambient Operation, Cooling with an Economizer

Page 57

Operation

Low Ambient Operation

During low ambient operation, outside air temperature below 13ºC, the RTRM will cycle the compressor and outdoor fan motor "Off" for approximately three minutes after every 10 minutes of accumulated compressor run time. The supply fan motor (IDM) will continue to operate during this evaporator defrost cycle (EDC) and the compressor and outdoor fan will return to normal operation once the defrost cycle has terminated and the compressor "Off" time delay has been satisfied.

Cooling with an

Economizer

The economizer is utilized to control the zone temperature providing the outside air conditions are suitable.

Outside air is drawn into the unit through modulating dampers. When cooling is required and economizing is possible, the RTRM sends the cooling request to the unit economizer actuator (ECA) to open the economizer damper. The RTRM tries to cool the zone utilizing the economizer to slightly below the zone temperature setpoint. If the mixed air sensor (MAS) senses that the mixed air temperature is below 53ºF, the damper modulates toward the closed position. If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is full open, the RTRM energizes the compressor contactor (CC1). If the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open, the RTRM energizes the compressor contactor (CC2).

The ECA continues to modulate the economizer damper open/closed to keep the mixed air temperature that is calculated by the RTRM.

If economizing is not possible, the ECA drives the damper to the minimum position setpoint when the supply fan relay (F) is energized and allows mechanical cooling operation. When the unit is equipped with the optional fan failure switch, wired between terminals J7-5 and J7-6 on the RTOM, the RTRM will stop all cooling functions and produce an analog output if the fan failure switch (FFS) does not open within 40 seconds after a request for fan operation. When the system is connected to a remote panel, the "SERVICE" LED will flash when this failure occurs.

RT-SVX20A-E4

57

Image 57
Contents Installation Operation Maintenance Foreword General informationMaintenance contract WarrantyReception RefrigerantContents Unit Options Roof curb accessory Roof curb Installation TSD-WSD-YSD accessoriesReception of units Rooftop unitDimensions/Weights/ Clearances Unit weights and center of gravityMinimum recommended clearances Motorized Manual Factory-installed options and accessories net weights kgElectric Hot water Unit size Motor HeatersInstalling the unit Discharge ConversionUnit mounting on roof Downflow discharge units TSD,WSD,YSD Using the rooftop curb Installing the unit on the groundConnection of duct network Horizontal discharge units TSH,WSH,YSHDuct dimensions for horizontal units Duct dimensions for downflow units mmCondensate drain piping Gas leak check procedure Gas pipework installationGas burner models UnitSupply fan adjustment Filter installationFilter arrangement Unit EU2/G2 EU4/G4 Quantity SizeTo increase airflow To adjust beltTo decrease airflow Motor sheave / Fan speedComponent air pressure drops Pressure drop through accessoriesUnit Airflow Filter 100%Supply fan performances TSD 060 Available static pressureTSH 060 Available static pressure TSH 072 Available static pressure TSD 072 Available static pressureTSH 090 Available static pressure TSD 090 Available static pressureTSH 102 Available static pressure TSD 102 Available static pressureTSH 120 Available static pressure TSD 120 Available static pressureYSH 060 Available static pressure YSD 060 Available static pressureYSH 072 Available static pressure YSD 072 Available static pressureYSD 090 Available static pressure YSH 090 Available static pressureStandard drive Oversize drive YSH 102 Available static pressure YSD 102 Available static pressureYSH 120 Available static pressure YSD 120 Available static pressureWSH 060 Available static pressure WSD 060 Available static pressureWSH 072 Available static pressure WSD 072 Available static pressureWSH 090 Available static pressure WSD 090 Available static pressurePower wiring Factory supplied disconnect switch optionElectrical connection Over current protectionAmpacity Size Unit wiringPh/Hz Without Electric heat option With Electric heatSupply fan motor Compressor and condenser motorsUnit controlled by thermostat Control wiringUnit controlled by BAS Zone sensor wire and maximum lengthUnit controlled by Tracker supervisor MaximumCO2 sensor wire size SpecificationsCO2 sensors Wiring the duct-mounted CO2 sensor Wiring the wall-mounted CO2 sensorMounting the wall-mounted sensor Jumper settingsMounting the duct-mounted CO2 sensor CO2 sensor maintenanceRemote potentiometer Remote potentiometer dimensionsDuct mounting of fire thermostat Fire thermostatRemote fault relay High temperature safety thermostatClogged filter detector Smoke detectorThermostats Thermostat featuresCommunication Interfaces Other accessories availableRefer to separate documentation for more information Trane Communication Interface TCI-R boardHot water coil Down flow units onlyEthylene glycol percentage Soft Starter Electric Heater25% manual fresh air hood 25% fresh air hoodBarometric relief Economizer flow chart with barometric reliefTerminal strip Operation with a conventional thermostatInput / connection Function when energized Cooling mode Thermostat signals are as followsHeating mode Heat pump onlyUnoccupied mode Setting the economizer or 0-50% motorized hood optionCooling/Economizer Operation Cooling/Economizer Operation with ThermostatECA board LED Minimum fresh air adjustmentOperating checklist before start-up Test proceduresPower-up initialization Test mode procedure at the ReliaTel control boardStep Test Mode Auto Test ModeTest modes Unit start-up Gas type designation per countryGas burner data Final installation checklist Starting the unit in cooling modeCheck torque of power cables contact Operating pressuresEvaporator Fan Operation Cooling without an EconomizerCooling with an Economizer Low Ambient OperationEconomizer Set-Up Potentiometer SettingReliaTel Control Heating Operation Ignition ModuleLED status Final installation checklistEnd user routine maintenance Air filtersRefrigerant charge Service technician maintenance Condenser coilHot water coil option System Status Checkout Procedure TroubleshootingSystem failure Service FailureHeating Failure Cooling FailureZone Temperature Sensor ZTS Service Indicator Resetting Cooling and Ignition LockoutsClogged Filter Switch Fan Failure SwitchResistance Thermistor Resistance / Temperature ChartOutdoor Humidity Sensor To Test Humidity Sensors Return Air Humidity SensorHumidity sensor test DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.