Trane TSH 060, TSD manual Setting the economizer or 0-50% motorized hood option, Unoccupied mode

Page 50

Operation

Unoccupied mode

If the thermostat being used is programmable, it will have its own strategy for unoccupied mode and will control the unit directly. If a mechanical thermostat is being used, a field applied time clock with relay contacts connected to J6-11 and J6-12 can initiate an unoccupied mode as follows:

Contacts open: Normal occupied operation.

Contacts closed: Unoccupied operation as follows - Fan in auto mode regardless of fan switch position. Economizer closes except while economizing regardless of minimum position setting.

Cooling/Economizer Operation

If unit does not have an economizer, the Cool/Econ Stage 1 and Stage 2 will call directly for mechanical cooling (compressor) stages. If the unit has an economizer, the Cool/Econ stages will function as shown in Table 46.

Setting the economizer or 0-50% motorized hood (option)

The ECA board is mounted on the damper actuator. To access the ECA board on economizers:

Remove the filter access panel of the unit.

The electrical power must be disconnected to set the minimum position and check the economizer.

Disconnect the power supply, put the thermostat fan selector to "ON" and the "HEAT/COOL" selector to "OFF". This puts the damper in the minimum ventilation position.

To set the required minimum ventilation air position, turn the dial on the ECA clockwise to increase ventilation, or anti- clockwise to decrease ventilation. The damper will open at this setting whenever the fan circuit is powered up (see Figure 25).

When the arrow on the dial's adjustment screw is pointing to 8 o'clock, the minimum position is roughly 0%. When the dial is pointing to 12 o'clock it is roughly 25%, and when the dial is pointing to 4 o'clock it is roughly 50% (see figure 25).

Table 46 - Cooling/Economizer Operation with Thermostat

OK to

Thermostat Thermostat

Call for Economizer

Compressor Staging

Economize?

Y1

Y2

Cooling

Request

 

 

 

 

 

No

On

Off

Inactive

Compressor Output 1

No

Off

On

Inactive

Compressor Output 2

No

On

On

Inactive

Compressor

Outputs 1 & 2

 

 

 

 

Yes

On

Off

Active

Off

Yes

Off

On

Active

Compressor off

Yes

On

On

Active

Compessor

Notes:

40 to 50 ton CV only

This unit has 3 stages of cooling if using a zone sensor. If using a conventional thermostat it has 2 stages as follows:

Y1 = 1st stage

Y1 + Y2 = 3rd stage

VAV

Thermostat inputs are ignored on VAV units.

50

RT-SVX20A-E4

Image 50
Contents Installation Operation Maintenance General information ForewordReception WarrantyMaintenance contract RefrigerantContents Unit Options Reception of units Roof curb Installation TSD-WSD-YSD accessoriesRoof curb accessory Rooftop unitMinimum recommended clearances Dimensions/Weights/ ClearancesUnit weights and center of gravity Electric Hot water Unit size Factory-installed options and accessories net weights kgMotorized Manual Motor HeatersUnit mounting on roof Installing the unitDischarge Conversion Connection of duct network Installing the unit on the groundDownflow discharge units TSD,WSD,YSD Using the rooftop curb Horizontal discharge units TSH,WSH,YSHDuct dimensions for downflow units mm Duct dimensions for horizontal unitsCondensate drain piping Gas burner models Gas pipework installationGas leak check procedure UnitFilter arrangement Filter installationSupply fan adjustment Unit EU2/G2 EU4/G4 Quantity SizeTo decrease airflow To adjust beltTo increase airflow Motor sheave / Fan speedUnit Airflow Filter Pressure drop through accessoriesComponent air pressure drops 100%TSH 060 Available static pressure Supply fan performancesTSD 060 Available static pressure TSD 072 Available static pressure TSH 072 Available static pressureTSD 090 Available static pressure TSH 090 Available static pressureTSD 102 Available static pressure TSH 102 Available static pressureTSD 120 Available static pressure TSH 120 Available static pressureYSD 060 Available static pressure YSH 060 Available static pressureYSD 072 Available static pressure YSH 072 Available static pressureStandard drive Oversize drive YSD 090 Available static pressureYSH 090 Available static pressure YSD 102 Available static pressure YSH 102 Available static pressureYSD 120 Available static pressure YSH 120 Available static pressureWSD 060 Available static pressure WSH 060 Available static pressureWSD 072 Available static pressure WSH 072 Available static pressureWSD 090 Available static pressure WSH 090 Available static pressureElectrical connection Factory supplied disconnect switch optionPower wiring Over current protectionPh/Hz Without Electric heat option Unit wiringAmpacity Size With Electric heatCompressor and condenser motors Supply fan motorControl wiring Unit controlled by thermostatUnit controlled by Tracker supervisor Zone sensor wire and maximum lengthUnit controlled by BAS MaximumCO2 sensors CO2 sensor wire sizeSpecifications Wiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorJumper settings Mounting the wall-mounted sensorCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatClogged filter detector High temperature safety thermostatRemote fault relay Smoke detectorThermostat features ThermostatsRefer to separate documentation for more information Other accessories availableCommunication Interfaces Trane Communication Interface TCI-R boardEthylene glycol percentage Hot water coilDown flow units only Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodEconomizer flow chart with barometric relief Barometric reliefOperation with a conventional thermostat Terminal stripHeating mode Thermostat signals are as followsInput / connection Function when energized Cooling mode Heat pump onlyCooling/Economizer Operation Setting the economizer or 0-50% motorized hood optionUnoccupied mode Cooling/Economizer Operation with ThermostatMinimum fresh air adjustment ECA board LEDPower-up initialization Test proceduresOperating checklist before start-up Test mode procedure at the ReliaTel control boardTest modes Step Test ModeAuto Test Mode Gas burner data Unit start-upGas type designation per country Check torque of power cables contact Starting the unit in cooling modeFinal installation checklist Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerReliaTel Control Heating Operation Potentiometer SettingEconomizer Set-Up Ignition ModuleFinal installation checklist LED statusRefrigerant charge End user routine maintenanceAir filters Hot water coil option Service technician maintenanceCondenser coil Troubleshooting System Status Checkout ProcedureHeating Failure Service FailureSystem failure Cooling FailureClogged Filter Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Fan Failure SwitchThermistor Resistance / Temperature Chart ResistanceHumidity sensor test To Test Humidity Sensors Return Air Humidity SensorOutdoor Humidity Sensor DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.